For The Driver Operator

Slides:



Advertisements
Similar presentations
QA September 2001 Fire Topic
Advertisements

Fire Apparatus Pump Theory

Master Streams. Master Stream Training Available...  Awareness and Operations Training  Portable Monitors  Offensive Strategies  Defensive Strategies.
TFT Blitzfire.
Blitzfire Deck Gun Ground Monitor
Fuel Injection System Dr Jehad Yamin.

Fuel Oil Burners.
Adapted From Cody Fire School Presentations Amsterdam Fire Regular Fire Training February 16, 2009.
FIREFIGHTING NOZZLES and FIRE HYDRAULICS
Automatic Nozzles. 1960’s & 70’s  Automatic pressure regulating nozzles invented 1960’s & 70’s  Automatic pressure regulating nozzles invented Hand.
Nozzle Pressure. Designed Nozzle Pressures  Smooth Bore Nozzle - Handline 50 PSI  Smooth Bore Nozzle - Master Stream 80 PSI  Combination Nozzle - (all.

Nozzles and Fire Streams
Nozzles, Fire Streams, and Foam
Pumping Apparatus Driver/Operator
Fire Streams Geronimo Vol. Fire Dept.. Extinguishing Properties of Water G Water extinguishes fires by G Cooling G Remove heat from the fire G Smothering.
State of Georgia BASIC FIRE FIGHTER TRAINING COURSE
Hydraulic Calculations
Augmenting Fire Standpipe Systems
5/4/2015Dixon High School Fire Department1 Introduction The Recruit will also practice and masters certain skills and will be tested on these skills. At.
Discharging CAF Streams In reality anything that will let the stuff out of the end of the hose will work. The early mantra was that a shut off gate and.
Nozzles and Fire Streams 1. Introduction Fires usually extinguished by water Water delivered using nozzles and fire streams Nozzle selection important.
Driver Recert 2013 Topics Review of Water Supply SOG’s MAWW Main St. Tank OOS BlitzFire Deployment with Water Thief Tower Operations Foam System Review.
HYDRAULICS LET’S DO SOME MATH!.
Tie Rod Case Study.
Service Delivery 3 Hydraulics. Aim To ensure students can explain the principles of obtaining and delivering water.
Pumping Apparatus Driver/Operator
HH H OUSTON H OUSTON F IRE F IRE D EPARTMENT P UMP P UMP O PERATOR O PERATOR P ROGRAM VAL JAHNKE TRAINING FACILITY.
Fire Streams SFFMA Training Objectives: –
Nozzles, Fire Streams, and Foam
HYDRAULICS.
California State University, Chico
Flushing. Annual flushing is enough for many systems, but some water and emitter combinations require almost daily flushing to control clogging. If frequent.
Purpose of Standpipe and Hose Systems
Pressure Drop Basics & Valve Sizing
NOTRE DAME FIRE SCHOOL 2004 FIRE PUMPS 101 CAPTAIN TROY KERCKHOVE SOUTH BEND FIRE.
Mathematics for the Driver/ Operator
C L A S #4 Driver Operator Refresher Training.
Pumping Apparatus Driver/Operator
The Centrifugal Pump.
Basic Hydraulics Irrigation.
Fire vs. Water Flow. What’s the best size for an “attack line?”  Maximum flow  Maximum mobility  Speed-How fast and how much  Ease of deployment and.
Intermediate SFFMA Objectives: – Hrs received.
MER Design of Thermal Fluid Systems Pumps and Fans Professor Anderson Spring Term
Instructor Lee Lautzenheiser
Pumping Apparatus Driver/Operator
Example 1 Velocity measurement by a Pitot tube
Fire Stream and Line Selection Firefighter II. Copyright © Texas Education Agency All rights reserved. Images and other multimedia content used.
Fire Service Pump Operator ch 04 Mathematics for the Driver/Operator
SIZING PNEUMATIC SYSTEMS. Introduction Pneumatic systems are sized to meet output power requirements. The air distribution system is sized to carry the.
Mahoney, Hannig, Fire Department Hydraulics, 2nd Ed. ©2009 by Pearson Education, Inc., Upper Saddle River, NJ Fire Department Hydraulics Chapter 8 Required.
Fixed & Selectable Flow Nozzles. Combination (Fog) Nozzle Development.
Firefighter III Module B Water Supply (4-19) (4-19)
HYDRAULICS & PNEUMATICS
Achieving Maximum Flows The Water Triangle.... The FIRE Tetrahedron.
Learning Objective 1 Explain the way vaporization and steam relate to the extinguishing properties of water.
IFSTA Chapter 16 Fire Streams
Relay Pumping Operations Sugar Land Fire Department Driver/Operator-Pumper Academy Spring 2003.
Fire Hose Nozzles & Flow Rates
Chapter 6: Hydraulic Cylinders and Cylinder Cushioning
HYDRAULICS & PNEUMATICS
Dual Pumping Definition: An operation where a strong hydrant is used to supply two Engines by connecting the Engines intake-to-intake. The second Engine.
Fire Attack and Foam (Fire Fighter I)
Essentials of Fire Fighting
KINEMATICS 1. A nozzle is so shaped that the velocity of flow along the centre line changes linearly from 1.5 m/s to 15 m/s in a distance of m. Determine.
Chapter 4. Analysis of Flows in Pipes
Fire Hose, Nozzles, Streams, and Foam
8. FLUID FLOW: mechanical energy equation
Presentation transcript:

For The Driver Operator Field Hydraulics For The Driver Operator

Hydraulics Theory and application allowing control and use of fluid pressure

Hydraulic Theories Understanding the theoretical and practical application of hydraulics essential for pump operation. The study of fire ground hydraulics is divided into two categories, theoretical and rule of thumb. The driver/operator must be able to apply both.

Elements of Hydraulic Calculation Nozzle Loss Attack Line Loss Elevation Loss Manifold/ Appliance Standpipe Loss Supply Line Loss

Terminology in Friction Loss Formulas NP - Nozzle Pressure FL - Friction Loss AL - Appliance Loss EL - Elevation Pressure TPL - Total Pressure Loss NPDP - Net Pump Discharge Pressure

Theoretical In the classroom and non-emergency activities of the fire department, mathematical equations are used to calculate the flow characteristics of our equipment and systems. This method of calculation is commonly referred to as “Theoretical Hydraulics”. By using mathematical formulas, a relatively accurate calculation of the total probable friction loss is obtained. This method is normally more accurate than Rule of Thumb.

Theoretical Formula There are many formulas and methods for figuring friction loss but the Renton Fire Department has adopted the following for use in its training program. FL = CQ2L Where Q = Quantity C = Coefficient L = Length in 100’s

Hose Coefficients Coefficients for Renton Fire Department hose:

Siamesed Hose Lines Coefficients Two 2 ½” 0.5 Three 2 ½” 0.22

Rule of Thumb On the fire ground, the driver/operator normally works with a condensed and simplified application known as “Rule of Thumb Hydraulics”. Rule of thumb hydraulic formulas are a chosen series of fixed, rounded values that can be applied to an operation sequentially to build a water delivery system.

Fixed Rounded Value Examples Rule of Thumb Fixed Rounded Value Examples 2 ½” Combination Nozzle 250 GPM 1 ¾” Combination Nozzle 125 GPM 1 ¾” Hose 25 psi FL / Section 2 ½” Hose 06 psi FL / Section Master Stream Devices 25 psi FL Appliances (Wye etc…) 0 FL @ <350 gpm Appliances (Wye etc…) 10 psi FL @ > 350 gpm Elevation 05 psi FL / Floor

Appliance Pressure Loss < 350 gpm no calculated loss > 350 gpm 10 psi per appliance 25 psi for all master stream devices 25 psi for all standpipes

Nozzles and Tips Types of Nozzles Broken Stream Solid Stream Periphery Deflected (Combination ) Impinging stream (Naval type)

Nozzle Design Restriction The purpose of any nozzle is to provide a restriction of the flow to build pressure. This restriction, and subsequent created pressure, provides a usable velocity to project the water stream. For any one flow, there is one correct nozzle size (restriction) to develop the optimum pressure and velocity. Restriction

Designed Nozzle Pressure Smooth Bore Nozzle - Hand line - 50 PSI ½” thru 1 ¼” nozzles Smooth Bore Nozzle - Master Stream - 80 PSI nozzles 1 ¼” and over Fog Nozzle - 100 PSI all nozzles Pump Pressure

Solid Stream - Characteristics The mechanical characteristics of a solid stream nozzle produce a compact stream that has a higher mass and velocity. These features typically yield better reach and penetration.

Solid Stream - Composition The interior diameter of the nozzle is gradually decreased until it reaches a point just short of the outlet. At this point the straight cylindrical bore has a length from 1 to 1 ½ times its bore, this area is known as the stream shaper

Solid Stream Mechanics Water flowing through a nozzle is subject to the same physical principals of friction as hose. The net effect of friction in a solid stream nozzle is the creation of a laminar flow. The center of the flowing stream is faster than the edge. This creates a peripheral turbulence that is visible after the stream exits the nozzle.

Solid Stream - Formulas Discharge Volume: 29.7 x D2 x NP Nozzle Reaction: 1.57 x D2 x NP

Fog Stream - Characteristics A stream of water remains in a solid mass, not losing continuity until it strikes an object, is overcome by gravity or is changed by friction with the air. Fog stream nozzles are designed around this theory and are commonly called broken stream appliances

Fog Stream - Composition All fog streams are of two mechanical types, Periphery-deflected or impinging stream. The shape and reach of a fog stream are results of the appliance shape and the velocity/pressure of the water.

Impinging Stream Impinging Stream fog patterns are produced by driving jets of water together at a set angle to break the streams into finely divided particles. These appliances generally produce wide angle fog patterns.

Periphery-Deflected Periphery –Deflected streams are produced by deflecting water from the periphery of an inside circular stem to the inner circumference of the adjustable barrel. The position of the barrel varies the shape of the stream from a light fog to a straight stream. There are two common types of these nozzles, automatic and non-automatic.

Periphery-Deflected, Automatic Automatic Periphery-Deflected nozzles have a spring loaded baffle assembly that reacts to incoming pressure. The baffle is calibrated to function at 100 PSI. The model illustrated has a sliding valve which allow the firefighter to meter the flow at the nozzle.

Periphery-Deflected, Automatic When pressure at the nozzle is less, the baffle moves in to maintain the pattern. When the pressure is greater than 100 PSI the baffle moves out to allow more volume and minimize the nozzle reaction.

Periphery-Deflected, Automatic Task Force Tip nozzles have a slide valve assembly that allows the water flow at the tip to be metered. By using this valve design, the nozzle has a smoother flow and less turbulence. Note the valve position in the illustrations.

Fog Stream - Formulas Nozzle Reaction: 0.0505 x Q x NP

Slide Valve Operation Slide Valve Gated ½ Way

Ball Valve Operation Ball Valve Gated ½ Way

Nozzle Reaction Nozzle reaction is the force that a firefighter feels when he is operating a nozzle. Nozzle reaction is primarily a result of discharge pressure at the nozzle. If the nozzle pressure is lowered, the firefighter will note a corresponding decrease in the nozzle reaction.

Nozzle Reaction To calculate the nozzle reaction use the following formulas, note same flows can often be developed at a far lower nozzle reaction in solid stream nozzles. Traditional thought is that solid bore hand lines should be pumped at 50 psi. Any nozzle pressures higher than 65 psi becomes unmanageable. In the following table review and compare the reaction force of various fire streams. Nozzle Reaction: Solid Stream 1.57 x D2 x NP Nozzle Reaction: Fog Stream 0.0505 x Q x NP

Handline Nozzle Reaction Chart 125 GPM 3/4” tip @ 56 NP = 49 NR combination @ 100 NP = 63 NR 150 GPM 7/8” tip @ 44 NP = 53 NR combination @ 100 NP = 76 NR 175 GPM 7/8” tip @ 60 NP = 72 NR combination @ 100 NP = 88 NR 200 GPM 1” tip @ 46 NP = 72 NR combination @ 75 NP = 87 NR combination @ 100 NP = 101 NR 250 GPM 1” tip @ 72 NP = 113 NR 1-1/8” tip @ 50 NP = 99 NR combination @ 100 NP = 126 NR 300 GPM 1” tip @ 100 NP = 157 NR 1-1/8” @ 64 NP = 127 NR combination @ 100 NP = 152 NR 325 GPM 1” tip @ 120 NP = 188 NR 1-1/8” tip @ 75 NP = 149 NR 1-1/4” tip @ 50 NP = 123 NR combination @ 100 NP = 164 NR

Friction Loss Problems

Theoretical Formula FL = CQ2L Where Q = Quantity C = Coefficient L = Length in 100’s

Hose Coefficients Coefficients for Renton Fire Department hose:

Siamesed Hose Lines Coefficients Two 2 ½” 0.5 Three 2 ½” 0.22

125 gpm 125 gpm 2 ½” – 400 ‘ 1 ¾” – 150’ 1 ¾” – 200’

Answer 100 psi NP 48 psi FL 1 ¾”, 200’ 50 psi FL 2 ½”, 400’ 198 psi NPDP (36 psi FL 1 ¾”, 150’ plus 5 psi elevation is less than 200’. Pump to the highest friction loss)

200 gpm 250 gpm 200’ of 5” 200’ 1 ¾” 200’ 2 ½”

Answer 100 psi NP 5 psi elevation 124 psi 1 ¾”, 200’ 10 psi appliance loss (>350gpm) 3.24 psi 5”, 200’ 242.24 psi NPDP (2 ½” FL is 25 psi, pump to the highest loss)

600 GPM 2 ea. 2 ½” 50’ 1 ½” tip 200’ of 5” 2 ½” 200’ 250 GPM

Answer 100 psi NP 25 psi FL, 2 ½” 10 psi AL 11.56 psi FL 5” 146.56 psi NPDP (NP 80 psi, 1 ½” tip 600 gpm / 25 psi FL Masterstream / 9 psi FL 2 ½” Siamese = 114 psi. Pump to the highest loss. Gate down the Master stream if necessary)

1 ¼” Solid Bore 1 ¾” 150’ 200 gpm 250’ 2 ½’ 125 gpm 2 ½’” 200’ 250 gpm 1 ¾” 200’

Answer 2 ½” 25 psi FL 1 ¾” 125 gpm, 48.4 psi FL 100 psi NP 1 ¾” 200 gpm, 93 psi FL 1 ¾” 125 gpm, 48.4 psi FL 50 psi 2 ½” with 1 ¼” 328 gpm, 53.7 psi 193 psi NPDP, pump to the highest friction loss

150 gpm 40’ 200’ 1 ¾”

Answer 100 psi NP 17.36 psi EL (.434/ft) 69.75 psi FL 187.11 psi NPDP

200’ 1 ¾” 150 gpm 100” Siamesed 2 ½”

Answer 100 psi NP @ 150 gpm 69.75 psi FL 1 ¾”, 200’ 34.72 psi EL (.434 psi X 8 floors above the 1st) 25 psi FL Standpipe 01.125 psi FL Siamesed 2 ½” 230.59 psi NPDP

200’ of 1 ¾” @ 200 gpm 100’ of 2 ½”

Answer 100 psi NP @ 150 gpm 124 psi FL 1 ¾”, 200’ 34.72 psi EL (.434 psi X 8 floors above the 1st) 25 psi FL Standpipe 08 psi FL Siamesed 2 ½” 291.72 psi NPDP What single adjustment could you make to cut the friction loss by NPDP by 25 psi?

180 GPM 250 GPM 150’ of 2 ½” 150’ of 1 ¾” 150’ of 2 ½” 2 ea. / 100’ of 2 ½”

Answer 100 psi NP @ 180 gpm 75.33 psi FL 1 ¾”, 150’ 26.04 psi EL (.434 psi X 6 floors above the 1st) 25 psi FL Standpipe 09.25 psi FL Siamesed 2 ½” 245 psi NPDP The 2 ½” NPDP was 187.72 pump to the highest friction loss. How would the excess pressure be dealt with in this line?