The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.

Slides:



Advertisements
Similar presentations
AIR DISTRIBUTION (Additional information. Also see Chapter 18) General The proper delivery of air for heating, cooling, or ventilation is a crucial part.
Advertisements

HEALTHCARE BUILDING AUTOMATION
Carrier Controls Demand Controlled Ventilation. Comfort = Temperature + Ventilation Comfort Is More Than Just The Right Temperature… Ventilation Control.
Controlling the amount of ventilation to a space based on demand Reset based on occupancy: Use carbon dioxide sensors to track space CO2 levels and raise.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Commercial Mechanical Requirements
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Components of HVAC System
Data Center Controls Mark Hydeman, P.E., FASHRAE Taylor Engineering, LLC
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
Break Out Session 3: Group A: Ventilation and Air Quality Chris Cosgrove, Cosgrove FDS, Inc.
COMPLY © Copyright 2008 HVAC Design Solutions1 Quick and Easy “Ventilation Rate Procedure” Compliance Calculations Quick and Easy “Ventilation.
BRE Energy Efficient Office of the Future
Ventilation Effectiveness & Indoor Air Quality Douglas Spratt February 2001.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
Lindab Pascal - Simplified VAV solution with full potential...
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Welcome to S&P USA & the 2012 International Residential and Mechanical Code for Ventilation.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Indoor Air Quality Trina Redford Industrial Hygienist National Naval Medical Center IH Services North.
Objectives Discuss Project Topics Learn to design VAV and DOAS System.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
© American Standard Inc Fan Pressure Optimization The Trane Company.
Air Side System Evaluation
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By Klas C. Haglid, P.E., R.A., CEM 1.
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
HVAC for Educational Facilities
Lecture Objectives Discuss specific class of problems
ASHRAE A Ventilation Standard for Residential Structures Ventilation and Acceptable Indoor Air Quality in Low- Rise Residential Buildings.
Ductless Heat Pumps Ventilation Gary Nordeen Bill Kingrey, P.E. 11/5/08 AFE Webinar.
HVACR416 - Design IAQ / Ventilation / Pathways. Ventilation Most air handling units distribute a mix of outdoor air and re-circulated indoor air. Some.
Improved Precision Leading to Improved Energy Efficiency Edward Decker AE 790 – Intelligent Buildings June 6, 2006.
Grocery VSD Measure Deemed Savings Reid Hart, PE & Ken Anderson September 28, 2010.
Final Projects Grading criteria is posted on the course website Preliminary results are due Next Tuesday Final Project delivery on Monday Dec. 7 th –Final.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
VRF Applications in PNW RTF RTUG Meeting October 26, 2011 Kevin Campbell Reid Hart, PE Technical Research Group.
Objectives Ventilation analysis with HOP Human exposure/IAQ Ventilation and energy.
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
Day 3 Part 3 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Contract: EIE/07/069/SI Duration: October 2007 – March 2010Version: July 7, 2009 Ventilation for non-residential buildings - Performance requirements.
Implementing DCV with ASHRAE 62.1 John Murphy, LEED ® AP BD+C, ASHRAE Fellow Applications Engineer Trane Ingersoll Rand La Crosse, Wisconsin 9 March 2016.
HCB 3-Chap 19B: All-Air_Multizone_Reddy1 Chapter 19B: ALL-AIR SYSTEMS FOR MULTIPLE SPACES Agami Reddy (July 2016) 1)CAV terminal reheat 2)CAV multizone.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Airflow Measuring Stations
Revoir titre.
Maria’s Restaurant Chapter 1 Section 4
CHAPTER 8 Ventilation.
Mark Hydeman, PE of Taylor Engineering
The Data Center Challenge
ASHRAE Stsdddddsd Update Standard
Lesson 24 Appendix F Outside Air Calculation
Presented by Harry C. Elinsky, Jr. Filtech, Inc.
By Klas C. Haglid, P.E., R.A., CEM
SMART VENTILATION BEST PRACTICES
Data Center Controls Mark Hydeman, P.E., FASHRAE Taylor Engineering, LLC
Placement Considerations
Lecture Objectives Learn about particle dynamics modeling
HCB 3-Chap 19A: All-Air Systems_Single Zone
Objectives Further discuss the Exam problems
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Manual D Duct Sizes Room Cooling CFM % Total CFM Heating CFM Kitchen GR Dining Bed Bed 3.
Mandatory Design Requirements
A Ventilation Standard for Residential Structures
Objective Revie the Cooling Cycle Learn about air distribution systems
Lesson 24 Appendix F Outside Air Calculation
Chapter 3B: INDOOR AIR QUALITY
Presentation transcript:

The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter

Introduction Proper operating controls are fundamental to providing acceptable indoor air quality Many control factors must be considered to be effective in maintaining air quality

Topics of Discussion Control fundamentals Relative humidity control Building pressurization control Ventilation control  ASHRAE Standard  Ventilation Rate Procedure  Demand Controlled Ventilation

ASHRAE Standard u 5.4 Ventilation System Controls. Mechanical ventilation systems shall include controls, manual or automatic, that enable the fan system to operate whenever the spaces served are occupied. The system shall be designed to maintain the minimum outdoor airflow as required by Section 6 under any load condition.

IMC Section Mechanical Ventilation u The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the space is occupied, except as otherwise stated in other provisions of the code.

Control System Goals Provide required amount of ventilation air throughout the complete range of operating conditions without wasting energy Must function reliably over a long time Must be usable by the building operating staff Control Fundamentals

Control Reliability Accuracy and inaccuracy Measure controlled parameter Capable controls Commissioning Control Fundamentals

Control Accuracy Describes the total of all deviations between the true value and the measured value Typically expressed as the percent of full-scale range Inaccuracy refers to the departure from the actual value to which all causes of error contribute Total Error = SQRT [ (error 1 ) 2 + (error 2 ) 2 + … + (error n ) 2 ] Accuracy Control Fundamentals

Ventilation Control Strategies for VAV Common OSA Control Methods  Fan tracking  Use of commissioning data  Plenum pressure differential  Flow monitoring Control Fundamentals

Outside Air Control A fixed minimum outside air damper position with no control is not a valid control strategy for a VAV system under any condition Control Fundamentals Not Recommended

Fan Tracking OSA Control Methods n Assumption: The difference between the measured supply airflow and return airflow is the amount of outside air. Control Fundamentals 100,000 cfm SA 85,000 cfm RA 15,000 cfm OSA 3% sensing accuracy 3,000 cfm SA error 2,550 cfm RA error 37% Error on OSA Not Recommended

Use Commissioning Data u Assumption: u That for any given airflow in a system, there is some OSA damper position that provides the required OSA quantity OSA Control Methods Control Fundamentals Not Recommended

Plenum Pressure Control  Maintain a fixed MA plenum pressure differential by modulating the RA damper OSA Control Methods Control Fundamentals

Measure the amount of ventilation air to control Flow measurement  Velocity must be high enough  Typically need minimum 2D before & 1D after the flow element (will increase if turning vanes are not used) Flow sensing built into dampers Flow Monitoring OSA Control Methods Control Fundamentals

Measuring Airflow Different sensing means advantages can depend on the application  <1000 fpmThermal anemometry  >1000 fpm Pitot tube Understand how accuracy can impact the control method selected Caution when controlling differential Accuracy Control Fundamentals

 Combination damper-flow station Flow Monitoring (continued) P V = P T - P S OSA Control Methods Control Fundamentals

Relative Humidity Control Humidity control is required for good IAQ ASHRAE Standard 62.1 Section 5 recommends that RH be maintained below 65% Controls for Good IAQ

Building Pressurization Control Negative building pressure causes infiltration Infiltration in hot and humid climates can cause IAQ problems Controls for Good IAQ

Standard Ventilation Control Classifications  Ventilation Rate Procedure  Indoor Air Quality Procedure Variable Supply Air Operations and Maintenance Demand Controlled Ventilation Ventilation Control

Standard Ventilation Rate Procedure New procedure for calculating outside air flow rates Default values for ventilation system efficiency and multiple spaces effects for simplicity Reduced rates in most occupancies Ventilation Control Standard 62.1

Standard Ventilation Rate Procedure People Component Building Component Breathing Zone Outdoor Airflow CFM Minimum CFM/Person Zone Population Minimum CFM/ft 2 Zone Floor Area V bz = R p P z + R a A z Ventilation Control Standard 62.1

Excerpt from Table 6.1 of Standard Minimum Ventilation Rate In Breathing Zone cfm/personcfm/ft 2 Offices Office space50.06 Reception areas50.06 Conference rooms50.06 Public Spaces Corridors and utilities0.06 Public Restroomsnote Application

Standard Ventilation Rate Procedure n Terms u Vbz Breathing Zone Outdoor Air u Ez Zone Air Distribution Effectiveness u Voz Zone Outdoor Airflow u Vpz Zone Primary Airflow u Zp Primary Outdoor Air Fraction u Vot Uncorrected Outdoor Air Intake u Ev System Ventilation Efficiency u Vot Outdoor Air Intake Ventilation Control Standard 62.1

Standard Reset  Dynamic Reset. The system may be designed to reset the design outdoor air intake flow (Vot) and/or space or zone airflow as operating conditions change. Variations on occupancy Variations in the efficiency with which the outside air is distributed Higher fraction of OSA due to free cooling or exhaust air makeup

Demand Controlled Ventilation (DCV) It is “any” method used to control ventilation that modifies intake rates based on changing “demand” “Demand” is usually measured as a change in the occupancy CO 2 sensing is typically used as an occupancy indicator Ventilation Control

Understanding CO 2 CO 2 is not an indicator of IAQ If ventilation rate is 15 cfm per person (1.2 met units) the resulting steady-state CO 2 concentration relative to outdoor is 700 ppm differential Standard 62.1 Appendix C Ventilation Control DCV Using CO2

Demand Controlled Ventilation Avoid CO 2 sensors in RA ducts Zone sensors in breathing zone Outdoor ventilation control  Minimum 0.15 cfm/ft2 OSA  Modulate airflow rate to space first  Modulate OSA rate to maintain the CO 2 setpoint of ppm Ventilation Control DCV Using CO2

Demand Controlled Ventilation Good candidates  Unpredictable variations in occupancy  Climate where cooling and heating is required most of year  Low pollutant emissions from non- occupant sources DCV guidance is available Centralized CO 2 monitoring Ventilation Control DCV Using CO2

IAQ Control System … Must understand system relationships and accuracy Requires careful selection Should be commissioned Must be usable by the building operating staff Must function reliably over a long time Controls for IAQ

For Further Information ASHRAE Publications  Standard  ASHRAE Guideline  Research Project RP-980  Techniques for Measuring and Controlling Outside Air Intake Rates in Variable Air Volume Systems  ASHRAE Journal Articles  Transactions  Humidity Control Design Guide Trade journals Controls for IAQ