Command Center Terminal Board RTU-MP Controller (Opt)

Slides:



Advertisements
Similar presentations
Operating Functions.
Advertisements

1. Four LLs were published in February Transmission Relaying – Undesired Blocking 2.Lack of Separation for Critical Control Power Supply Leads.
Zone Control Air System Why? 1.Provides room by room comfort control. 2.Reduces equipment run time. 3.Eliminates hot/cold rooms. 4.Works with conventional.
Daikin Altherma™ Troubling Shooting
PACKAGE UNITS GPG 10 AND 12 SEER.
Thermostats. I would recommend that as you proceed through this power point presentation that you refer to your textbook, Unit 14, for some great visuals.
WebStat™ Programming and Configuration of Thermostats.
HEAT PUMPS.
Total HVAC Control from anywhere Easy control that can save a fortune
Setup/Installation/Operation of an Environmental Control Unit (ECU)
WIRED TYPE MULTI ZONE FANCOIL CONTROL SYSTEM MODEL : WSF- 700 SYSTEM
STAND ALONE CONTROL FOR TERMINALS
AC-SSC-1 Installation and operation manual
HVAC Commercial Ref.
1. 2 Maintenance & Troubleshooting 3 Maintenance Three-monthly checks Carry out the following checks every three months: check the power supply; check.
38GXC(Q)/40GXC(Q) Service Training Sizes 18 and 24K.
Graphic Symbol Location 1. DIN Terminal X52 The machine is powered by electricity using copper cable with 5 wires (3 phase wires + neutral wire +
GO ORDNANCE !!! ORDNANCECORPS 1 Antenna Mast Group We will now trace the electrical circuits of the antenna mast mast group. Be fore we get started you.
Clean Air Box Usage & Care CABs RAMs CO Monitors.
S8910U1000 Universal Electronic Ignition Modules Training Module
KLINGE’S NMR 262 Two Independent Systems Integrated into one Unit This Requires Special Features:  Total Redundancy of Refrigeration Components  Total.
Engineer Presentation
GO ORDNANCE !!! ORDNANCECORPS 1 Troubleshoot the DC Electrical Control System on the EPP III.
Siemens Building TechnologiesRWD heatpump controllers Xavier Zabalegui/David Jefferson 1 January 2003 RWD Heat Pump controllers RWD Heat Pump Controllers.
Product Introduction.
ST9120U1003 Universal Electronic Fan Timer Training Module
S9200U1000 Universal Integrated Furnace Control (UIFC) Training Module
Variable Speed Indoor Blower Motor Robert Helt Technical Conference - Panama City Beach, Fl
E2 Motors and Motor Starting
Electrical Electricity Fuses Relays Solenoids Electrical Testing
EGD ELECTRICAL ELECTRICAL SYMBOLS.
2-Stage Heat Pump Defrost Options Defrost options: –30, 60, 90, 120 or Auto (Infinity/Evolution only) Defrost initiate temp: 32° F Defrost terminate temp:
Troubleshooting Electric Control Devices
HYDRONIC HEATING AQUASTATS
Air Handler Terminology
Air Handler Terminology
Why Maintenance Tasks are Important Produced by Joe Marchese.
Roof Top Unit Overview (MAGNUM) Visit us at Revision- 12/17/2015.
ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.
CUE – Make Any Pump an E-Pump
World Leaders in Combustion Management Solutions End User Guide Lockout Codes Pressure Sensors Error Codes Flame Safeguard UV.
Unit 8 Gas-Burning Equipment. OBJECTIVES State the difference between a natural gas and an LP gas system. Describe several control sequences for gas heat.
BASIC AUTOMATIC CONTROLS UNIT 16 ADVANCED AUTOMATIC CONTROLS
We apply 120 VAC to the HM Unit (Remember to check polarity!) Our primary step down T/X provides power to terminal “X” and “COM” on the ignition control.
AIR CONDITIONING (COOLING)
BASIC ELECTRICITY AND MAGNETISM
2013 CHIGO Product CHIGO CMV VRF Control System.
E3 HVACR Controls and Devices
shift to the Test Mode (Forced Operation).
Duct Free System.
Two Stage Communicating System
E1 – Electrical Fundamentals
© 2004 Refrigeration Training Services - Refrigeration Categories v1.1
E3 HVACR Controls and Devices
E2 Motors and Motor Starting
GROUND-FAULT GROUND-CHECK MONITOR
Voyager II and III – Energy Recovery Modules
Roof Top Unit Overview (MAGNUM)
Flotection: Building Main Shutoff System
VITALITY Large Splits Johnson Controls PowerPoint Guidelines | July 21, 2009.
S8910U1000 Universal Electronic Ignition Modules Training Module
Universal Interrupted Electronic Oil Primary R7184U Training Module
Error codes for split systems
Replacing TrueAir Thermostat with Ecobee SI
Presentation transcript:

Command Center Terminal Board RTU-MP Controller (Opt) New Control Box (Cleaner) Design Command Center Terminal Board RTU-MP Controller (Opt) Gas Controller

Controls: Cooling High Pressure Switch Low Pressure Switch Indoor Fan Motor Overloads: Linebreak Thermik (pilot-circuit) External circuit-breaker

Controls: Cooling Control Transformer 75 va 3.2-A circuit breaker on transformer housing CLO -- Accy or FIOP

CLO Connections

Controls: Heating Integrated Gas Controller (IGC) IGC Inputs Flame Sensor Hall Effect W1 Demand Speed Sensor Rollout Switch 24-v Limit Switch IGC Outputs Diagnostic LED Inducer Motor (CM) Indoor Blower (BM) IFO signal Gas Valve Sparker

Hall Effect Ref: Honeywell

Hall Effect Sensor Includes: Current field Integrated circuit Transistor Amplifier circuit

Hall Effect: Pulse Output Signal Speed Sensor Logic Criteria Speed > 2400 RPM: Inducer Motor OK Speed < 2000 RPM: Combustion Terminated

IGC Alarms

IGC Troubleshooting

IGC Error Codes: From NSMM 2003 (SPP PPT) in HVACPartners Fault 2 – Limit Switch Open If limit opens: Gas valve and ignitor will be disable Indoor blower will immediately energized. Inducer shall remain energized The indoor blower will turn off after the fan off delay if “W” goes away. If limit closes again the fault will clear. If you still have “W”, the gas valve still open and re-igniton will occur.

IGC Service Reference Material NSMM 2003 SPP PPT IGC Alarms Technical Base / Hall Effect Service Training GT54-01

Heat Pump Defrost Board New PN: HK32EA005 Thermostat demands for 1 or 2 stage Cooling 2 stage Heating Emergency Heating Defrost Control in Heating Mode Based on RES HK32EA003

Controls: Heat Pump HPS High Pressure Switch Opens 660PSI. Close 505PSI LPS Low Pressure Switch (A/C’s) Opens 54PSI. Close 117PSI Liquid Line Loss-of-Charge (HP’s) Opens 27PSI. Close 44PSI Freeze Protection Thermostat (FPS) Opens 30F. Close 45F Connects to new defrost board

Reversing Valve Operation No O or B signal required Energized in Cooling Reversing Valve does not shift mode in Off cycle (No Dump)

Heat Pump Compressor Seq Cooling Stage 1: Reversing Valve 1 + Compressor Cooling Stage 2: (2-comp models only) Rev Valves 1+2 + Compressors 1+2 Heating Stage 1: Compressor(s), No Reversing Valve

Heat Pump Electric Heat Heating Stage 2 Concurrent with compressor(s) Emergency Heat Electric Heat WITHOUT compressors Defrost Tempering

Heat Pump Defrost Time-Temperature Sequence 1. Heat Run Time (30,60,90 or 120 mins) Factory 60 mins 2. Initiate if tube temperature (DFT) low 3. Terminate when tube temperature (DFT) rises or defrost run period reaches 10 min HH18SA261DFT Settings: Open: 30F Close: 80F

Defrost Speed-Up JMP17-JMP18 (flat/slot screwdriver) 1-5 secs: Speed-Up (0.1 sec/min) 5-20 secs: Forced Defrost Run to normal termination or 30 secs minimum

Controls: Electric Heat Accessory installation 1 or 2 stages Fan housing limit switch (pilot, manual) Element line-break (or secondary contactor) Heater control contactor(s)

Electric Heat: Single-Point Box Required with all electric heater installations Splice box with cover Power terminal block Tap conductors If FLA > 48-A: Fuse blocks and 60-A fuses

CONTROLS TERMINAL BOARD SERVICE MANUAL CONTROLS TERMINAL BOARD CONVENIENCE OUTLETS SMOKE DETECTORS

Installation Instructions and Service Manuals (SM) The complete unit installation procedure (rig and position through start-up) will require reference to two (or more) technical manuals. Mechanical Installation: SI (II) Configure/Start-up/Troubleshoot: SM

Service Manual: LP Gas Conversion

Service Manual: Heat Pump Piping

Service Manual: Appendix

Specific Topic Tech Support Smoke Detectors: Application Tip Cat# HKRNKA-1XA (integration with building alarm systems) PremierLink: Form 33CS-58SI (configuration, t-s) RTU-MP: Form 48-50H-T-2T (configuration, t-s) RTU-MP 3rd Party Integration Guide

Controls Terminal Board aka Light Commercial Terminal Board (LCTB) Command Center Terminal Board Carrier PN HK50AA049 UTEC PN CEPL130904-01 Array of terminal strips, housings and QCs Contains NO LOGIC, no software

Controls Terminal Board Gas Controller Provides: - Clean connection points - Insures positive connections - Visual aid Phase Monitor OR Fire / Remote Shutdown OR Smoke Alarm LPS HPS

Controls Terminal Board 11 terminal strips: J1-J2: Screw terminals (thermostat wires) 0.046-in square pin 18 quick-connect terminals

CTB: Jumpers JMP1 Phase Monitor JMP2 Occupancy Control JMP3 Smoke Detector Shutdown JMP4 Remote Shutdown JMP5, 6, 7 Heat Pump / Reheat JMP1 JMP4 JMP3 JMP2

CTB: Actual vs Schematic View

2010 FIOPs Convenience Outlets Smoke Detectors CO2 Sensor (new)

Convenience Outlets Non-Powered Unit-Powered Neither is connected as delivered Hinged cover shipped loose (in control box)

Convenience Outlets Non-Powered: Duplex GFCI Weatherproof box Hinged cover Powered: Duplex GFCI Weatherproof box Transformer 15-A fuse/switch Hinged cover

Non-Powered CO Provide a separate 115-v 15-A power supply and circuit disconnect from the building Connect to the duplex outlet in the unit’s splice box Install the weatherproof hinged cover

Powered CO Check local codes to determine if connecting the convenience outlet transformer to the LINE side of the unit disconnect is acceptable. If acceptable: Connect primary leads at the power transformer together as required for unit line voltage and connect to unit disconnect’s line side terminals. If not acceptable: Connect primary leads at the power transformer together as required for unit line voltage and connect to unit disconnect’s load side terminals. Install the weatherproof hinged cover.

Powered CO: Label

Powered CO: Transformer Primary Connections

Weatherproof Hinged Cover

Powered Convenience Outlet: Duty Cycle Limit

Smoke Detector FIOPs Supply Air (on supply fan housing) Return Air w/o Economizer Return Air with Economizer Combine S/A and R/A R/A Smoke Detector is for VERTICAL only “Some assembly required”

Smoke Detector Hardware Controller Module (one per unit) Sensor Module (one or two required) R/A application: Sensor tube

Smoke Detectors

R/A Sensor: Site Installation

Smoke Detector: LED

Smoke Detector: Alarm Integration Application Tip Cat# HKRNKA-1XA

NEW FIOP: Unit-Mounted CO2 Sensor Same control logic as on accessory CO2 No LCD display on sensor Requires PC access to configure Software and cable available thru RCD Details to follow in full training program

2010 SRT FIOPs Economizers (15th digit) CO2 sensors (9th digit) Smoke Detectors (9th digit) Louvered Hail Guard (11th digit) 2-position Damper (15th digit) Convenience Outlet (16th digit) Thru-The-Base Connections (17th digit) PremierLink (14th digit) RTU-MP/Open (14th digit)

2010 SRT Accessories Economizers & Roofcurbs CO2 & Enthalpy sensors Power Exhaust Motormasters (low ambient) and winter start LP Conversions High Altitude Kits 2-pos damper / Man damper Thru-The-Base Louvered Hail Guards Electric Heat / Single Point Phase Monitor, Status switch, time guard PremierLink

Economizer Plugs Command Center aka Low Voltage Terminal Board (LVTB) ECON 10pin Plug Used for all Economizers SAT/OAT 4pin Plug Used for Econ 2 only OCCUPANCY Terminals Used for Econ IV and 2-pos Damper 12-Pin Plug (male) – Unit Side plug in Econ Section Same plug and arrangement as old units 12-Pin Plug (female) – Econ Side Comes with specific FIOP or Accessory Small change on the Econ IV plug

Economizer Plugs Table to help Troubleshoot Economizer wiring at the LVTB and the 12-pin plug

Economizer IV Electro-mechanical Unit Economizer Stand alone operation with Honeywell W7212 controller. Compressor control runs through the W7212 If no econ then jumpers must be in 12-pin plug for cooling to operate Actuator is 2-10 vdc pre-programmed ready for W7212 output SAT in 12-pin plug (PL6) Same economizer as the R-22 machines.

Economizer IV Added occupancy control Low Ambient Lockout The “N” terminal tells the controller when occupied R-22 units had W7212 main power fed from the IFC and jumper to the N terminal 410a units have main power fed from transformer, and IFC feeds the N terminal trough the Occupancy terminals So W7212 is powered up when the unit is, instead of only when the fan is on Low Ambient Lockout The “LA” switch is installed on the Y2 input to the controller Part number HH18HA286, Contacts Open: 42°F ±5°F, and Contacts Close: 57°F. ±5°F. Below 42°F the second compressor will not run, econ will be stage one and 1st comp is stage 2 Power exhaust wire Tan wire that is connected to 24Vac HOT, move to EF1 Add jumper from 24Vac HOT to EF Connect other end of the tan wire to the tan wire in the PE Kit harness Connect the Grey wire in the PE kit harness to the 24Vac COM terminal

Economizer IV CO2 Sensor Enthalpy Power Exhaust (PE) IAQ install, uses 24Vac (TR & TR1), and 0-10Vdc signal (AQ & AQ1), TR1 & AQ1 are common Demand Control Ventilation (DCV) is the only CO2 control available for Econ IV. DCV SET (POT) tells the controller at what input vdc from the IAQ sensor do we want to start opening the damper DCV MAX (POT) tells the controller at what damper position do you want us to stop opening for DCV The damper will modulate between the MIN POS (POT) and DCV MAX (POT) settings proportional to the IAQ vdc input from DCV SET (POT) to 10Vdc Enthalpy The Single Enthalpy sensor uses the same terminals as dry bulb (SO+ & SO). For Differential Enthalpy, 2 enthalpy sensors required. One installed per above and the other on terminals SR+ & SR (after removing the resistor). Set the cross over POT to “D” Whichever is lower is the air used for cooling Remember O for outdoor and R for Return Enthalpy sensors are HH57AC078 and Dry bulb are HH57AC074 Power Exhaust (PE) Terminals EF and EF1 are dry contacts and switch when the damper pos (in Vdc) gets above the EXH SET (POT) setting (in vdc) DCV – have to work with air balancer to determine the position of the damper and convert to input volts to the actuator. That Vdc is what MIN POS and DCV MAX need to be based on. For IAQ convert the Vdc output to PPM 0-10vdc to 0-2000PPM, each vdc is 200 ppm.

Economizer IV

Economizer 2 Econ2 No controller, requires Plink or RTU-MP/open Jumper wires in 12-pin plug for cooling operation Actuator is 2-10vdc pre-programmed 500 ohm resistor (pre-installed) required for 4-20 controller output OAT in 12-pin plug (PL6)

Economizer 2 CO2 Sensor Enthalpy (only field installed) PE IAQ is installed on the specific controller via PL18 for FIOP and direct to controller when field installed DCV is set in the specific controller with a user interface. Enthalpy (only field installed) Single or Differential control from the DDC controller Uses the 2 loose Grey wires near unit’s 12 pin plug Sensor wires run to the LVTB and then to DDC PE Wires provided with the PE accessory have to be run to the control box specifically to which ever DDC is installed Switch one stage on and off based on damper position

Economizer 2 Cooling jumpers must be in harness for cooling to work Resistor must be between the White signal wire and Black actuator common Actuator is 2-10v and controllers output 4-20mA Enthalpy sensor power from Actuator power Switch signal using 2 grey wires When troubleshooting Read vdc across resistor Determine if it’s the actuator or the controller Shorting the actuator signal to 24VAC will drive it 100%, but disconnect the actual signal first Spring return Closed Direction switch set to same direction as the spring return

2-Position Damper Opens to set position whenever the fan is running To set position, set the screw on the actuator face near the shaft opening

Low Ambient Winter start Kit (CRWINSTR001A00) Motormaster I (32LT) 3 minute timer relay to bypass low pressure switch Field supply wires to tie into the LVTB, contact across LPS and coil between HPS and compressor contactor Current Literature – IIK-CRWNTRAN01-01 Motormaster I (32LT) Wave Chopper, varies voltage to vary fan speed, single phase approved motors, clip on sensor May need to replace motor and capacitor. Usage chart in literature. Copper Coil Controller with sensor – 32LT900301 (230v), and 32LT900611 (460v) MCHX coil controller with sensor – 32LT901247 (230v), and 32LT901647 (460v) Tries to maintain 100 deg SCT, unit operation down to -20 deg Current Literature – IIK-32LT903-01

Low Ambient Motormaster II (CPLOWAMB001A00) Motormaster V Fan cycle switch, on/off only, single phase motors, clip on sensor Tries to maintain 130-110 high and 70-50 low SCT, unit operation down to -20 deg Motormaster V Kits CRLOWAMB030A00, 031A00, and 032A00 for specific voltage For use on three phase motors (48/50TC 14 and 50TCQ 12) VFD, varies frequency (HZ) to vary fan speed, 3 phase approved motors Pressure sensor on liquid line, unit operation down to -20 deg

Gas Conversion Kits High Altitude Conversion Four kits for use with LP and/or high altitude applications. Each contain 25 spuds, 5 of 5 different sizes. Manifold Pressure Natural Gas still 3.5-in.wc. LP now 10.5-in.wc. High Altitude Conversion Pick kit based on orifices needed Use only spuds and High-Alt label in kit Some spuds may have to be purchased separately Literature contains conversion tables

Gas Conversion Kits LP Conversion New, low pressure switch on supply side Closes at 10.2-in.wc. and opens at 7.2-in.wc. Gas piping included in kits Kits include springs for gas valve to operate at higher pressure Labels for LP and high alt (if needed) Chose Kit based on orifices needed, some orifices may have to be purchased separately LPS

Controls PremierLink RTU-MP RTU-Open FIOP or Accessory. If field installed make sure the CRPREMLK001A01 kit was also purchased. It has the harness for LVTB and the TB to install other accessories to. RTU-MP FIOP only and only available through mid-2009 Overview training PES0810302 on partners Controller training PES0803241 on Partners Other information and tools on HVACpartners (CCN Support – Multi-Protocol Controls) RTU-Open Only FIOP until 3 Qtr 2009, then the retrofit should be available Replaces the RTU-MP, direct replacement Improved control and improved networking Fixes battery memory with flash memory, otherwise hardware is the same

RTU-Open Support Contact Equipment Product support for: Open release – FIOP around June 2009 – Accy around July 2009 Contact Equipment Product support for: Specific base unit operation or problems Questions/problems with the Controller or how it controls the unit, if it was Factory installed (FIOP) Questions/problems with how the FIOP was installed Controller operation, start-up, configuration, and troubleshooting questions Contact CCN support for: Network Integration and Communication questions or problems Questions/problems with the controller if it was field installed (accessory) Questions/problems with the accessory installation

What’s Next Bynum Training program 4th Qtr

Questions???