Unit 8 Gas-Burning Equipment. OBJECTIVES State the difference between a natural gas and an LP gas system. Describe several control sequences for gas heat.

Similar presentations


Presentation on theme: "Unit 8 Gas-Burning Equipment. OBJECTIVES State the difference between a natural gas and an LP gas system. Describe several control sequences for gas heat."— Presentation transcript:

1 Unit 8 Gas-Burning Equipment

2 OBJECTIVES State the difference between a natural gas and an LP gas system. Describe several control sequences for gas heat and warm-air furnaces. Describe the difference between a standard-efficiency furnaces and a high-efficiency furnace. After studying this Unit, the student should be able to:

3 TYPES OF FURNACES Upflow – Stands vertically, top air discharge Low Boy – Used where there is little headroom –Both supply and return are at the top –Blower located behind the furnace Downflow – Stands vertically, bottom air discharge Horizontal – Left or right discharge Multipoise – Multi-positional

4 THE UPLOW FURNACE Return AirSupply Air Floor Blower Heat Producing System

5 THE LOWBOY FURNACE Return AirSupply Air Floor Blower Heat Producing System

6 THE DOWNFLOW FURNACE Return Air Supply Air Floor

7 THE HORIZONTAL FURNACE INSTALLED IN A BASEMENT Return AirSupply Air Floor

8 TWO-STAGE FURNACES Two-stage gas valves and combustion blowers –First stage provides 50% to 70% of heating output –First stage gas pressure is 1.75 in. W.C. –Second stage provides 100% of total heating output –Second stage gas pressure is 3.5 in. W.C. Two pressure switches to prove flame –Low pressure switch for low blower speed –High pressure switch for high blower speed Provide better control of space temperature

9 MODULATING FURNACES Follows the heat loss of the structure Discharge air temperature is modulated for even heating of the structure Adjusts to changes in gas heating values and air density Determines exact heating requirements for the space Optimizes furnace efficiency and performance Utilize variable speed blowers

10 THE FAN SWITCH Turns the blower on and off automatically Can be controlled by time or temperature Blower operation is delayed at both the beginning and the end of the heating cycle –Gives the heat exchanger time to heat up at the beginning of the cycle –Allows the heat exchanger to cool off at the end of the heating cycle Electronic modules can be used to control the blower

11 THE FAN SWITCH Shaft Bimetal element (located near the heat exchanger) Cams Set lever Dial Switch

12 THE LIMIT SWITCH Used as a safety device to open the gas valve circuit if the heat exchanger overheats Normally opens between 200°F and 220°F Fan switch and limit switch can be combined into a single unit –Can be line voltage, low voltage or a combination –Fan and limit contacts controlled by the same bimetal –Internal jumper removed to separate the controls –Can be automatic or manually reset devices

13 SAFETY DEVICES – STANDING PILOT Flame-proving devices prevent gas from flowing through the valve if the pilot is out Thermocouples and thermopiles – As long as the pilot is lit, the thermocouple will stay hot and the gas valve will remain open Bimetallic safety device – Heated by the pilot Liquid-filled remote bulb – Heated by the pilot If the pilot goes out, the device will initiate the closing of the gas valve

14 Thermocouple Pilot burner Power unit coil Valve

15 FLAME RECTIFICATION Uses the flame as a switch Flame is located between electrodes The flame completes the rectification circuit Rectification circuit converts ac power to dc The furnace recognizes the dc power and opens the gas valve Can be used on spark to pilot or DSI systems Integrated Furnace Controllers (IFC)

16 HIGH EFFICIENCY GAS FURNACES Annual Fuel Utilization Efficiency (AFUE) Efficiency increased by keeping excessive heat from being vented to the atmosphere Have multiple heat exchangers Range from 87% to 97% AFUE ratings 35°F to 65°F rise across the heat exchanger 110°F to 120°F stack temperature Condensing furnaces

17 ELECTRONIC IGNITION MODULES & INTEGRATED FURNACE CONTROLLERS (IFC) Control the ignition and sequence of operations 100% shutoff and non 100% shutoff systems Soft lockout – allows time to light or relight pilot Hard lockout – power must be interrupted and restored after allotted time has elapsed Pre-purge, inter-purge and post-purge IFCs provide sequence of operation for the system

18 Unit Summary The gas furnace consists of a heat producing system and an air distribution system Furnace configurations include upflow, downflow, lowboy, horizontal and multipoise The fan switch controls blower operation The limit switch is a safety that opens its contacts if the heat exchanger temperature rises too high Flame rectification devices convert ac to dc and are used on spark to pilot or DSI systems High efficiency furnaces have 87% to 97% AFUE ratings (Annual Fuel Utilization Efficiency) Two-stage furnaces use two-stage gas valves High efficiency furnaces use small blowers to remove the flue gases