Duct Free System.

Similar presentations


Presentation on theme: "Duct Free System."— Presentation transcript:

1 Duct Free System

2 DFS Long Line Guide

3 DFS Long Line Guide

4 DFS Long Line Guide “ accessories ”

5 DFS Long Line Guide “ all specifications ”

6 DFS Long Line Guide “ DFS Pistons…”

7 New DFS Puron Units 40/38 MVC & 40/38MVQ

8 DFS PRODUCT CONCEPT 13 SEER fixed speed, R410A Carrier Phase 1:
115 volt 9 & 12 KBTU/Hr Cool only & heat pump 208/230 volt 18 KBTU/Hr Cool only Phase 2: 12 KBTU/Hr cool only & heat pump 18 heat pump 24 KBTU/Hr cool only & heat pump Carrier brand picture

9 High wall unit’s Control
The remote control and emergency control are the only way to operate and control the highwall units. 76 F set point No wired control available. Remote control only or emergency button. One way communications.

10 High wall display board
( Cooling and Heat Pump ) 9 K

11 High wall display board
( Cooling and Heat Pump ) 12 K

12 High wall display board
( Cooling Only 018 & 024 )

13 High wall display board
( Cooling and Heat Pump 018 & 024 )

14 Operating Conditions Cooling: Heating: Outdoor Ambient: 55° F – 125° F
Low ambient: -20° F to 55° F Indoor Set point range: 64° F – 85° F Heating: Outdoor Ambient: 5° F – 75° F Low ambient: -20° F to 55° F Indoor Set point range: 55° F – 80° F

15 Operation… Run time: Reversing valve: Temperature offset:
Minimum run time – (3 seconds), none…. Minimum off time – 3 minutes Reversing valve: Energized in the heating mode Temperature offset: 1°C above and below set point. 3.6°F swing

16 System Wiring 009 & 012 K units Field Wiring 35 VDC 115 V

17 System Wiring 012 K units Field Wiring 35 VDC 208/230 V

18 System Wiring 18 & 24 K units 208/230 V Field Wiring
The “S” terminal – signal terminal carriers a 24vdc voltage. However if you measure VAC from the “S” terminal to L1 or L2 you will measure approximately 200VAC. There are no amps behind this voltage > 0.5ma.

19 High wall (system) trouble shooting
LED’s indicators: solid or flash code for errors

20 Line lengths….. Unit’s charged for 25’ Minimum line of 10 feet…
If line set is over 25’ a crankcase heater is required…

21

22 Service Manual – board voltages

23 Service Manual – flow charts

24 Service Manual – flow charts

25 Service Manual – sequences

26 Service Manual – sequences

27 Service Manual – long line/charge

28 Service Manual – piping diagram

29 Service Manual – wiring diagram