Compact line ‘EW*D~J-’ water-cooled chiller range - Product presentation - Applied Systems - Strategic Marketing Daikin Europe NV
CONTENTS 1. What’s changing? 1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range 2. What are we going to offer? 2.1 Features & benefits 2.2 Capacity classes 2.3 Operation range 2.4 Energy efficiency 2.5 Dimensions 2.6 Connections 2.7 Options 3. Conclusion
Chapter 1 --------------------------------- What’s changing?
1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range Current product portfolio: COOLING CAPACITY (kW) 50 100 250 500 750 1000 1250 1500 2000 R-410A & 407c Hydrocube EWWP012-065KBWN (incl. EWLP) EWWQ~B- R-134a EW*D~MB REPLACEMENT EW*D~J- EW*D~G- EWWD~H- (Flooded technology) EW*D~I- INVERTER EWWD~FZ DWSC/WDC (Centrifugal Chiller) (DWSC up to 4.500 kW) (DWDC up to 9.000 kW) 4
1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range Current range overview: MODEL CHANGE! Model change includes: 1 Complete range will feature: - extended capacity range - new compressor - new controller 2 Complete range will be updated with regard to: - option configuration - warranty 1year standard instead of 3 extendable up to a maximum of 4 years warranty applicable on parts only
1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range Product Water-cooled chiller with single screw compressor Refrigerant R-134A Series name EW*D~J- ¹ Cooling capacity From 120 kW up to 570 kW (nominal conditions) Circuits 1/2 circuits (1/2 compressors) Efficiency versions S Standard efficiency Sound versions S Standard sound New range overview: Note ¹ Also available as condenserless series ‘EWLD~J-’
1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range New range overview: Product line-up: ‘EW*D~MB’ replaced by ‘EW*D~J-‘ range Current situation New situation
1.1 Replacement of EW*D~MBYNN 1.2 Position in our W/C range Product positioning: WATER COOLED EW*D~G- EWWD~H- NEW Direct expansion EWWD~FZ Flooded EW*D~I- EW*D~J- DWSC/DWDC EWWQ~B-
Chapter 2 --------------------------------- What are we going to offer?
2.1 Features & benefits wide capacity range: 120 – 570kW 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options wide capacity range: 120 – 570kW compact design to allow easy indoor installations or retrofit operations availability of both standard and condenserless units high energy efficiency (EER up to 4.41, ESEER up to 5.37) upgrade of chiller controller to Microtech III easy integration with control systems (BMS, sequencing panels) extensive option list, including heat pump version
extended capacity range 2.2 Capacity classes 2.1 Features 2.2 Capacity 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Standard unit: ● Standard efficiency – standard sound Current situation New situation extended capacity range additional sizes
extended capacity range 2.2 Capacity classes 2.1 Features 2.2 Capacity 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Condenserless unit: ● Standard efficiency – standard sound Current situation New situation extended capacity range additional sizes
Standard efficiency – standard sound 2.3 Operation range 2.1 Features 2.2 Capacity 2.3 Operation 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Standard unit: Standard efficiency – standard sound Operation with Glycol ICE mode Operation with Glycol (below 4°C ELWT) = Units should not be able to reach the minimum capacity when working in part load
Standard efficiency – standard sound 2.3 Operation range 2.1 Features 2.2 Capacity 2.3 Operation 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Condenserless unit: Standard efficiency – standard sound Operation with Glycol ICE mode Operation with Glycol (below 4°C ELWT) = Units should not be able to reach the minimum capacity when working in part load
2.4 Energy efficiency levels 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Standard unit: New range Current range EER comparison Up to 8% increase in EER
2.4 Energy efficiency levels 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Standard unit: New range Current range ESEER comparison
COMPACT LINE! 2.5 Unit dimensions Current situation New situation 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Dimensions Dimensions of the new units will be the same as the current EW*D~MB range COMPACT LINE! Current situation New situation
2.6 Connections Connections: Hydraulic side (dual compressor unit) 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Connections: Hydraulic side (dual compressor unit) Note 1 – Units are mechanically linked Note 2 - Connection pipes are NOT provided by Daikin Evaporator water IN Condenser water OUT Condenser water IN Evaporator water OUT - Evaporator water inlet/outlet: 76,2mm - Condenser water inlet/outlet: 4’’ (2½’’ on size 120)
2.6 Connections Connections: Electric side (dual compressor unit) 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Connections: Electric side (dual compressor unit) One Microtech III controller on the superior unit (master) is connected through RS485 with control modules on the lower unit (slave) Communication through cables between the two units Main switch Cables IN (side entry)
Microtech III controller (Siemens) 2.6 Connections 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options Connections: Electric panel Current situation New situation Microtech III controller (Siemens) Microtech II controller (Carel) Emergency stop (standard) Emergency stop (standard) Main switch (standard) Note: Main switch available as option
2.7 Options & accessories A) Options Compared to MB-series: 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options A) Options 1) Standard factory mounted The base model will include here below standard factory mounted options: Compared to MB-series: electronic expansion device: STD suction shut off valve: STD main switch: STD compressor fuse protection: STD
Extensive list of options 2.7 Options & accessories 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options 2.7 Options 2.7 Options A) Options 2) Options on request Below mentioned options will be available for the new ‘EW*D~J-‘ range: Current situation New situation Extensive list of options
2.7 Options & accessories B) Accessories 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options B) Accessories The R-134a ‘EW*D~J-‘ range will feature the new Microtech III controller Main features: ▫ Unit controller fully programmed and engineered by Daikin on Siemens hardware ▫ P.I.D. logic (proportional, integrative, derivative) ▫ Easy visual interface with 4 rows display and 3 keypads ▫ Push and roll navigating wheel ▫ Modular control solution: ▫ Freely programmable controllers ▫ Extendable with additional I/O modules ▫ Extended temperature range (-40ºC up to +70ºC) ▫ Field installable COMM modules (integration) ▫ Advanced (remote) servicing possibilities Microtech III
2.7 Options & accessories Current situation New situation 2.1 Features 2.2 Capacity 2.3 Operation 2.4 Efficiency 2.5 Dimensions 2.6 Connections 2.7 Options 2.7 Options B) Accessories Below accessories will be available: Current situation New situation
Chapter 3 --------------------------------- Conclusion
Superior control logic Small package, great chiller The new compact line ‘EW*D~J-’ chiller range features compact design, maximum efficiency and superior control logic, offering flexible solutions for a wide range of comfort and process applications Application flexibility Easy indoor installation & retrofit operation The EW*D-J- series is available in a wide range of capacities (120 - 570kW), allowing project solutions for an extensive range of applications. Water cooled units are typically intended for indoor installation and operation, resulting in acoustic isolation and also zero impact on the building layout. Thanks to the compact design, the EW*D-J- series allow easy indoor installations and retrofit operations. Superior control logic New MicroTech III controller provides easy to use control environmental and an easy interface with LonWorks, BACnet, Ethernet TCP/IP or Modbus communications