Presentation is loading. Please wait.

Presentation is loading. Please wait.

UniTrane™ Terminals High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line

Similar presentations


Presentation on theme: "UniTrane™ Terminals High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line"— Presentation transcript:

1 UniTrane™ Terminals High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line
Blower coil: B-Line Product Presentation – September 2016

2 Blower coil: B-Line Agenda
BFS Product overview Key features Capacity Range Performances Accessories Controls

3 Blower coil: B-Line Product Overview
BFS The Unitrane™ B-Line fan coils range has been developed to deliver a greater available static air pressure for concealed installation and connection to a duct system. Compliant with ERP 2015 Regulation (EU) No. 327/2011

4 Blower coil: B-Line Product Overview
BFS 4.2 kW 33 kW 5.8 kW 61 kW Performances Size 1 to 5: from 1000 m3/hr up to 4400 m3/hr Size 6 to 7: from 2200 m3/hr up to 7500 m3/hr 49 to 81 dB(A) Capacity range AC EC 2P 4P Airflow range Static Air pressure Sound power level B-Line Version Feature BFS AC motor only 5-speed fan assembly 5+2 Models Sizes Compliant with ERP 2015 Regulation (EU) No. 327/2011 Sizes from 1 to 5: up to 160 Pa Sizes from 6 to 7: up to 425 Pa

5 Blower coil: B-Line Product Overview
BFS Configuration Available in 7 casings and both 2-pipe and 4-pipe configurations The connections are on the left hand side looking from the air inlet of the unit, right side can be factory or site fitted Same options, accessories and controls as the D-Line Sizes 1-5 2 pipes 3 rows 4 rows 4 pipes +1 Rows +2 Rows Size 6-7 2 pipes 4 rows 6 rows 4 pipes +2 rows

6 Blower coil: B-Line Key Features
BFS Casing Made from 1 mm galvanized steel insulated with polyolefin (PO) foam (class M1) Suitable only for horizontal installations Dimensions (mm) Coil Model A B C D E F G H L M N Main Additional BFS 1 1133 698 310 255 991 620 1185 54 245 50 249 1) In 2) Out 3) In 4) Out BFS 2 ¾ ” BFS 3 360 305 295 299 1” ¾” BFS4 1445 853 293 1302 775 1497 58 291 BFS 5 435 368 367 370 1¼ ” BFS 6 1535 1100 488 421 1393 1022 1587 59 416 55 BFS 7 110 588 521 516

7 Blower coil: B-Line Key Features
BFS Motor Quiet centrifugal fans in galvanized steel with two impellers Directly driven single phase, four speed motor, 230V 50Hz, with capacitor, insulation class B Model BFS 1 BFS 2 BFS 3 BFS 4 BFS 5 BFS 6 BFS 7 230/1 50Hz W 240 412 523 765 885 1437 2817 A 1,09 1,91 2,45 3,62 4,01 6,38 12,40

8 Blower coil: B-Line Key Features
BFS Heat-exchanger Constructed using drawn copper tube with mechanically bonded aluminium fins Connections on the left hand side looking from the air inlet of the unit, right side can be factory or site fitted Sizes 1 to 5 are available with the combination of either 3 or 4 row coils with the possibility to add a 1 or 2 row coil (3+1, 4+1, 3+2, 4+2 versions for 4 pipe systems) Sizes 6 and 7 are available with the combination of either 4 or 6 row coils with the possibility to add a 2 row coil (4+2, 6+2 versions for 4 pipe systems). 2 pipe unit 4 pipe unit

9 Blower coil: B-Line Key Features
BFS Condensate collection tray Made from galvanized steel insulated with cross-linked polyolefin (PO) foam (class M1) Filter Washable synthetic filter encased in a metal frame which fits into special sliding guides to allow for easy insertion and removal.

10 Blower coil: B-Line Capacity range
BFS MODEL BF-2P-14 BF-2P-24 BF-2P-34 Speed 1 2 3 4 Air flow m3/h 940 1115 1315 1575 1835 855 1160 1535 2005 2360 1795 2060 2265 2550 2745 Cooling total capacity kW 4,8 5,33 5,88 6,53 7,07 5,22 6,4 7,63 8,92 9,77 9,32 10,13 10,7 11,46 11,95 Cooling sensible capacity 3,85 4,38 4,96 5,67 6,33 3,88 4,92 6,08 7,4 8,33 7,28 8,06 8,63 9,41 9,92 Heating capacity 8,76 9,95 11,22 12,77 14,2 8,77 11,13 13,76 16,69 18,71 16,43 18,2 19,5 21,22 22,36 Dp Cooling kPa 6 7,3 8,8 10,6 12,4 6,7 9,8 13,5 18,1 21,4 16,3 19 21 23,9 25,8 Dp Heating 3,9 4,9 6,1 7,8 9,5 3,7 5,8 8,6 12,3 15,2 9,9 12 13,7 16,1 17,7 Fan consumption W 130 151 173 204 232 180 222 268 322 380 426 464 505 520 Sound power outlet dB(A) 49 52 56 60 63 47 53 59 64 68 62 66 Sound power inlet + radiated 40 43 51 54 38 44 50 55 57 BF-2P-44 BF-2P-54 2245 2560 2820 3085 3340 2885 3240 3505 3920 4330 11,92 12,91 13,67 14,42 15,07 15,53 16,68 17,49 19,8 9,24 10,18 10,93 11,68 12,36 12,17 13,29 14,1 15,34 16,5 Heating capacity 20,86 23,02 24,69 26,36 27,91 27,08 29,56 31,31 33,96 36,49 15 17 23 15,4 16,8 21,2 9 11 14 8 447 508 551 606 684 536 612 689 766 868 65 67 69 72 71 73 75 58

11 Blower coil: B-Line capacity range
BFS MODEL BFS-2P-64 BFS-2P-66 BFS-2P-74 BFS-2P-76 Speed 1 2 3 Air flow m3/h 2200 3580 5200 2190 3570 5170 3960 5210 7480 7435 Cooling total capacity kW 14,55 20,22 25,38 16,99 24,4 31,3 23,17 27,52 34,04 27,81 33,59 42,28 Cooling sensible capacity 10,71 15,58 20,42 11,96 17,83 23,73 17,76 21,63 27,96 20,16 24,99 32,7 Heating capacity 9,0 16,4 24,6 11,6 22,2 34,8 14,6 19,8 29,1 18,6 26,1 39,5 Dp Cooling kPa 23,77 35,01 46,21 26,09 39,57 53,27 39,61 48,83 63,38 44,57 55,84 73,68 Dp Heating 4,9 9,9 16,3 5,7 12,1 20,6 8,6 12,5 20 14,8 Fan consumption W 718 943 1437 715 933 1407 1717 1970 2817 2764 Sound power outlet dB(A) 61 69 76 68 74 81 Sound power inlet + radiated 52 60 67 59 65 72

12 Blower coil: B-Line Performances
BFS

13 Blower coil: B-Line Accessories
BFS 3 way valves with connection kit and micrometric lockshield valve 3 way valves with semplified connections kit 2 way valves with connections kit 230 Volt For Main coil and Auxiliary coil 230 Volt, ON-OFF actuators TO BE USED ONLY WITH ON/OFF 230 V CONTROLS (QCV-MB-A, T-REM and T-TMO) 24 Volt 24 Volt, 3 points actuators TO BE USED ONLY WITH QCV-MB-A Oventrop PICV valve kit

14 Blower coil: B-Line Accessories
BFS Electric heater Insulated casing made of galvanized steel Electric resistances Security thermostat included G3 synthetic filter Made of washable synthetic fibre Flame-proof according to Class F1 DIN 53438 84% efficiency – Eurovent EU3 The filter is supplied as an accessory and must be fitted on the unit on-site in place of the standard G0 filter F6 synthetic filter High efficiency compact filter in glass microfiber paper Class F6 according to EN779 fitted on-site in place of the standard filter Model A B C WATT V BEM-230 1 1098 297 300 3000 230 BEM-230 2 4500 BEM-400 1 400 BEM-400 2 BEM-400 3 347 7500 BEM-400 4 1410 BEM-400 5 422 15000 BEM-400 6 1500 472 BEM-400 7 572

15 Blower coil: B-Line Accessories
BFS 1 GAV Antivibrating connection PMM Intake/Supply Spigot plenum 3 2 Inlet and outlet grids BCM Auxiliary condensate trays Drain pump for vertical or horizontal installations Built-in electric heater with integrated safety thermostats and relay control board 4 5 6

16 Blower coil: B-Line Controls
BFS M-3V T-TMO Control feature ON/OFF switch O Manual 3 speed switch Manual summer/winter switch Electronic room thermostat for fan coil ON/OFF Electronic room thermostat for valves ON/OFF – fan keeps working Low temperature control cut-out thermostat TMM Chilled valve control ON/OFF Electric heater control (BEL) M-3V T-TMO M-3V For models 1-2 use only WM-3V contol For models use the WM-3V + SEL-S For model 7 use the WM-3V + No. 2 SEL-S T-TMO For models 1-2 use only WM-T contol For models use the WM-T + SEL-S For model 7 use the WM-T + No. 2 SEL-S

17 Blower coil: B-Line Controls
BFS COM T-REM Control feature ON/OFF switch O Manual 3 speed switch Remote manual speed control 4 position commutator ( OFF, 1st speed, 2nd speed, 3rd speed) Manual summer/winter switch Control for low temperature cut-out thermostat TME Simultaneous thermostatic valves + fan control Water valves (2 or 4 pipes) control Thermostatic valves control (ON/OFF) Electric heater control (BEL) Electric heater/IAQ filter activation button Energy saving function COM T-REM T-REM For models 1-2 use only WM-TQR control For models use the WM-TQR + SEL-S For model 7 use the WM-TQR + No. 2 SEL-S

18 Blower coil: B-Line Controls
BFS QVC-MB control board Suitable for valves with 230V/on-off actuator Suitable for valves with 24V/3 point actuator (working as modulating valve) Fan operation control depending on the coil temperature (cut-out T3 probe fitted) – it can be activated only in heating mode or heating and cooling mode. Automatic switch of the operating mode by means of T2 water probe (optional) applied on the 2 pipe system Seasonal switch by means of remote contact ON/OFF of the fan coil by means of the remote contact (window or clock contact) Electric heater control RS 485 serial connection to manage several fan coils in Master/Slave configuration or to create a supervisory network

19 Blower coil: B-Line Controls
BFS IR-MB ModBus controller (included with the QCV-MB control board) Possibility to be inserted in a network with ModBus Possibility to control two electrovalves ON / OFF 230Vac (2 or 4 pipes) Control of an AC motor at three speeds. To facilitate wiring double terminal for the RS485 serial line. Probe included inlet air (T1) Minimum water temperature probe included (T3) 2 digital inputs 1 digital output Analogue alarm probes


Download ppt "UniTrane™ Terminals High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line"

Similar presentations