Basic Troubleshooting FC 100/200/300. | Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 2 Main Session Topics Required Tools and.

Slides:



Advertisements
Similar presentations
Variable Frequency Drives Bypass Options
Advertisements

Electrical Systems Chapter 9.
MANUAL TRANSMISSION ELECTRICAL. OBJECTIVES n Diagnose electrical problems by logic and symptom description. n Perform troubleshooting procedures using.
Club Car IQ Technical Information
The D.C. Scout Battery Distribution System Ground Locator
Isolation Verification Control Mining - Marine - Transit – Solutions LIVE Distributed By Locksafe Industrial Safety Equipment.
Brio 2000 / Brio 2000-M E-Learning Service Manual Rev. 0.0.
Daikin Altherma™ Troubling Shooting
Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.
Programming Logic Controllers
38GXC(Q)/40GXC(Q) Service Training Sizes 18 and 24K.
Trouble - Shooting ELR - Electric Latch Retraction.
Microprocessor Motor Control Spring Introduction  Stamp projects Robots  Sensors  Motor control  Logic Rocketry  Reading acceleration (“g”
COMPUTERS AND INPUT SENSORS. cbc MICROCOMPUTER OPERATION HAPPENS IN STAGES Memory.
Voltage and Its Measurements
Diagnostic procedure Training for the future. So, where do we start? Diagnostic Procedure.
Graphic Symbol Location 1. DIN Terminal X52 The machine is powered by electricity using copper cable with 5 wires (3 phase wires + neutral wire +
Tool removed during cycle Fault #2 Conditions for setting Tool cocked prox switch goes open during cycle AND force on load cell drops below limit in fault.
GO ORDNANCE !!! ORDNANCECORPS 1 Troubleshoot the DC Electrical Control System on the EPP III.
electronics fundamentals
CircuitProtection, Tips, and Troubleshooting Spring 2015 ECE 445.
Chapter 8 Output Modules.
Digital I/O Connecting to the Outside World
TEST METER OPERATION. Electrical Test Instruments Analog Or Digital Voltmeters – Measuring Potential Difference Ammeters – Measuring Current Flow – Clamp.
Electric Meters Electricity for Refrigeration, Heating and Air Conditioning 7th Edition Chapter 4 Electric Meters.
Charging System Service
Circuit Testers and Digital Meters
AccuMax Multi-Point Injection Mechanics
Chapter 19 Charging Systems.
Electrical Electricity Fuses Relays Solenoids Electrical Testing
SCADA and Telemetry Presented By:.
Chapter 9 Cranking Systems.
CHAPTER 9 Oscilloscopes and Graphing Multimeters
7.2.4 Student Book © 2005 Propane Education & Research CouncilPage Identifying Procedures for Measuring Current Between Two Given Points in an.
1 Advanced D-TAC Testing. 2 D-TAC testing – Part 2 This presentation is meant to be viewed after the introductory presentation ‘D-TAC testing – Batteries.
7.2.3 Student Book © 2005 Propane Education & Research CouncilPage Identifying Procedures for Measuring Resistance Between Two Given Points in.
Turbine Crane CRANES TURBINE NEA39. Turbine Crane PLANT STATUS! PV Daily Status Report.
TA: Chris Reilly Group 5: Benjamin, Ramie, Zachary, Dinal.
Electrical Power Systems
20.3 Electric Circuits
Lab 10 Experiment 21 Design a Traffic Arrow. Just so it is clear This is it. – Last official experiment for the semester. It is your option as to whether.
CircuitProtection, Tips, and Troubleshooting Fall 2015 ECE 445.
YASKAWA VS-606 V7 COMPACT VECTOR - CONTROLLED INVERTER FOR GENERAL USE 230V (Single-Phase).1Kw ~ 3.7Kw (.13HP ~ 5HP) 230V (Three-Phase).1Kw ~ 7.5Kw (.13HP.
Inverter power supply symptoms can be typically broken down into the following categories: 1. All Outputs Normal: 2. All Outputs Dead (no output): 3.
1 Electrical Skills Voltage and Its Measurements.
Unit 13 Electric Circuits
Electrical Measurements ─ Meters
Tool Removed During Cycle Fault #2 Conditions for Setting Tool cocked prox switch goes open during cycle AND force on load cell drops below 5 lbs. Active.
Electrical Testers Basic test equipment used in today’s shops may include an analog type meter, a VAT (Volt-Amp-Tester), DMM (Digital Multimeter),
Using electrical Test Equipment To accompany the Georgia Agriculture Curriculum Course: AG-AG-AMII Using Electrical Test Equipment 2010 VGP.
WATER LEVEL INDICATOR AND AUTOMATIC MOTOR SWITCHING SYSTEM
TROUBLESHOOTING ELECTRIC MOTORS
CGS Ground School Technical The Vigilant Electrical System © Crown Copyright 2012 No Part of this presentation may be reproduced without the permission.
Lesson 1 PLC BASICS. PLC Definition  Programmable Logic Controllers are industrial computers that control machine and other applications.  PLC have.
Residential Cabling Technologies Copyright © 2005 Heathkit Company, Inc. All Rights Reserved Electrical Measurements.
Digital Multimeter.
DVOM Not-So Basics.
THREE PHASE FAULT ANALYSIS WITH AUTO RESET ON TEMPORARY FAULT AND PERMANENT TRIP OTHERWISE Submitted by:
OBJECTIVES Explain the ABS diagnostic procedure and the brake warning lamp operation. Explain how to retrieve ABS diagnostic trouble codes. Explain how.
INDUCTION MOTOR PROTECTION FOR SINGLE PHASING, OVERVOLTAGE AND OVER TEMPERATURE Submitted by:
FEEDER PROTECTION UNIT
The D.C. Scout Battery Distribution System Ground Locator
Model Output Current Battery Life BATPSU VDC 2A 1.2Ah BATPSU VDC 2.3Ah
ACOE347 – Data Acquisition and Automation Systems
A. Touching both terminals with the hands can cause electrical shock
22 Chapter Basic Electrical Tests. 22 Chapter Basic Electrical Tests.
Electrical components and systems
Presentation transcript:

Basic Troubleshooting FC 100/200/300

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 2 Main Session Topics Required Tools and Material Physical Inspection Basic Troubleshooting Logic Testing Procedures Diagnostic Information Available from the Drive

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 3 Touching the electrical parts of the VLT may be fatal. The largest models can require a significant amount of time to discharge it’s internal circuitry to a safe level after being disconnected from the incoming AC line power. Check Instruction Manual for further warnings. Warning

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 4

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 5 Required Reference Material Instruction Manual Service Manual Customer Connection Diagram

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 6 Required Tools Screwdrivers, Standard & Phillips Torx drivers T10 to T50 Metric socket set, 7 – 17 mm long extension (must be able to clear 20”) Torque wrench, 4 – 170 in./lbs. Magnet Nut starter

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 7 Required Equipment DVM PWM compatible voltmeter Clamp-on ammeter

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 8 Many Digital Meters will give erroneous readings due to PWM waveform. PWM Compatible Meter Use an Analog meter or Digital meter designed for PWM compatibility to measure output voltage.

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 9 Possibly Useful Tools 1000 Volt Megger Cell phone Laptop computer with Drive Software, RS-485 converter Oscilloscope

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 10 What Is Troubleshooting? Troubleshooting is nothing more than a logical approach to determine the answer to the question: Why is this SYSTEM not working?

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 11 The Logical Approach Assess The Situation Perform Physical Inspection Divide and Conquer Zero in on Malfunction

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 12 Physical Inspection Is the Display Lit? Warning or Alarm Message Displayed? Programmed Correctly?

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 13 Try a different setup Try downloading the parameters from the LCP Try downloading parameters from another drive in the same application Use MCT-10 to download the parameters Study them yourself them to the factory Is The Drive Programmed Correctly?

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 14 Physical Inspection Unit Installed Correctly? Are the connections tight? Environmental Conditions OK?

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 15 Physical Inspection Carbon Deposits Inside Drive? Burnt or Damaged Components? Blown Fuses? NOTE: Do not apply power to test the drive until Static Test has been performed!!!

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 16 If the Drive Blows Power Fuses Before plugging in another fuse...with power off, use the ohmmeter to check for input AND output shorts Line-to-bus and motor-to-bus, is desirable. Line-to-line if the bus connections aren’t readily available

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 17 Static Test Set the ohm meter on either the diode check scale or the 2K scale. Connect the + meter lead to the + DC Bus. Connect the – meter lead to L1, L2, L3 in turn. All readings should be open or capacitor charging effect.

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 18 Now reverse the ohm meter leads and repeat the process. The meter readings should be with in the range of 0.3 to 0.7 K ohms. Static Test

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 19 Repeat the process connecting the meter between the DC Bus and the output terminals. Similar reading should be obtained with these devices. Static Test

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 20 Drive Fault Indicators Drive fault displays and warnings Resetting alarms Sample alarms Alarm history

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 21 Drive fault displays and warnings What is the LCP’s display telling you? Alarms Warnings Status If you contact the factory, be sure to have the exact wording of the display!

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 22 Resetting Alarms TRIP (Red LED Flashing) TRIPLOCK (Red & Yellow LED’s On) Press the RESET key to restart Disconnect power to restart the drive

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 23 Warning / Alarm Messages ALARM 9 INVERTER TIME ALARM 10 MOTOR TIME WARNING/ALARM 12 CURRENT LIMIT Ensure drive is sized and programmed correctly Check for bad bearings Check motor parameters Check Para 1-90 Check mechanical load This is caused by motor overload conditions. Check motor parameters Check mechanical load Check Para

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 24 ALARM 13 OVER CURRENT ALARM 14 EARTH FAULT ALARM 16 CURR. SHORT CIRCUIT Drive has exceeded 200% current surge Check application for problems There is a short to ground in the motor or the motor wiring There is a line-to-line short circuit in the motor or the motor wiring Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 25 Checking Current Sensors Disconnect Motor From Drive Observe Current In Display Current Should Be Zero >1 Amp Indicates Defective Current Sensor <1 Amp, Check Motor and Wiring

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 26 ALARM 29, 65, 66 DRIVE OVER TEMP. ALARM 30, 31, & 32 MISSING MOTOR PHASE U, V, W Is something (like an instruction manual) blocking the air flow? Check wiring between the drive and motor. This alarm doesn’t show up when the drive is starting Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 27 ALARM 4 MAINS PHASE LOSS Measure the input voltage phase to phase while the motor is running at high speed Measure the input current in each phase Both should be balanced Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 28 Alarm 7 DC Link Overvoltage Alarm 8 DC Link Undervoltage The DC Link Voltage is too high -Overhauling Load -High input voltage The DC Link Voltage is too low. Power outage Drive failure in the pre- charge circuit Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 29 ALARM 2 LIVE ZERO ERROR ALARM 17 STD BUS TIMEOUT An input 4-20 mA or 2-10 V control signal is missing The connection to the serial communication port has been lost Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 30 Warning 1 10 volt supply problem Alarm 15 Hardware Mismatch 10 Volt power supply is being over loaded. Reduce the load (min res 590ohm) Non-compatible Option Installed Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 31 ALARM AMA FAILURE ALARM 80 DRIVE INITIALIZED AMA procedure could not be carried out All parameters in the drive have been reset to their default values. Warning / Alarm Messages

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 32 Alarm Log Last 5 Alarms Previous 5 Available in Para Status Info for ea. Alarm Time, Value, Reference, Frequency, Current, Output Voltage, DC Voltage Graphic Displays

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 33 DIVIDE AND CONQUER 3 Phase AC Line Voltage Control Logic Motor

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 34 3 Phase AC Line Voltage Control Logic Motor Input Power

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 35 Checking Line Voltage Measure Phase to Phase AC Line Voltage L1 - L2 L1 - L3 L2 - L3 L1 L2 L3

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 36 Control Logic 3 Phase AC Line Voltage Control Logic Motor

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 37 Press “+” or “-” Keys, (or Set Parameter 0-23) to Display Digital Inputs Binary # Corresponding to Digital Inputs MSB = Term. 18 LSB = Term. 33 Digital Inputs

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 38 Digital Inputs If Input State is not Displayed Correctly, Measure Voltage at Terminal. Reference Meter on Terminal 20. Digital Inputs Must be 10-28VDC to be High (Logic 1)

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 39 Analog Inputs The Same Procedure can be Used to Check Analog Inputs

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 40 Analog Inputs Reference Meter (-) to Term Lead to Term. 53 or 54 for Voltage 0-10VDC for Current 1-5VDC Observe Polarity

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 41 Output Circuit 3 Phase AC Line Voltage Control Logic Motor

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 42 Measuring Output Current

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 43 Drive 3 Phase AC Line Voltage Control Logic Motor

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 44 Measuring Output Voltage Motor

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 45 Drive or Motor? Voltage is Balanced But Current is not. Drive is Good Problem in Motor or Wiring Voltage is Unbalanced. Drive is Bad Not all IGBT’s Switching Correctly. Check Gate Signals

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 46 Before Calling the Factory, Be Able to: Describe the problem Exactly what does the LCP show? What does (or doesn’t) happen? When does the problem occur? What time of day? What is the drive doing at the time? What else is happening at the time? What have you tried?

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 47 Describe the problem Describe the drive Serial number MATERIAL # 178B0300 (PLUS) SERIAL # H336(all of it!) Model number (FC202) Revision levels Parameter 15-43SOFTWARE VERSION Does the drive have bypass? Before Calling the Factory, Be Able to:

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 48 Describe the job site Call from the job site If they want a Service Station to look at the drive and the problem might be non-warranty then get a purchase order Before Calling the Factory, Be Able to:

| Confidential/Property of Danfoss Drives A/S | Sunday, 12 June 2016 | 49 This concludes this training module. Please proceed to the next installation module which covers applications in more detail. If you have any comments or questions, please contact: Technical Support Danfoss Drives 4401 N. Bell School Rd Loves Park, Illinois USA phone: (800) or (815)