Presentation is loading. Please wait.

Presentation is loading. Please wait.

E5CN-U to E5CC-U Conversion

Similar presentations


Presentation on theme: "E5CN-U to E5CC-U Conversion"— Presentation transcript:

1 E5CN-U to E5CC-U Conversion
March 2014

2 E5CN-U

3 E5CN-U Input Voltage VAC 24 VAC/VDC Input Type Thermocouple (K,J, T, L, E, U, N, R, S,B, W, PII) RTD (Pt100, JPt100) Analog (Based select on models) Alarms 1 or 2 (Based select on models)

4 E5CN-U Output Relay (SPDT, 250VAC) Current (4 to 20mA/0 to 20mA) Voltage (12VDC) Sampling Period 250 ms Control ON/OFF 2-PID

5 E5CC-U

6 Features 1/16 DIN Plug-in 58.6 mm depth Standard E5CC display Standard E5CC parameters

7 Features Programmable via CX-Thermo E58-CIFQ2 cable programming cable Version 4.61 or higher Sampling Period 50 ms Aux Output 1 to 2 (Based on select model)

8 Features Universal Input Thermocouple (K,J,T,E,L,U,N,R,S,B,W, or PLII) RTD (Pt100 & JPt100)

9 Features Outputs Relay (SPDT, 250 3A) Voltage (12VDC) Analog (Current: 4 to 20mA or 0 to 20mA) (Voltage: 1 to 5V, 0 to 5V, or 0 to 10V)

10 Specifications SIZE (MM) Front :48 x 48 Depth: : 58.6 Visibility
Heights of Character PV:15.2mm SV:7.1mm User-friendliness Operation Key 5 keys USB bus power YES Port for setting tools Front Functions/ Performance/ Control output Control Output Relay output, Voltage output (for driving SSR), Linear current output( no simple transfer output) Auxiliary Output 0 or 1 or 2 (depends on models) Power Supply Voltage AC V, AC/DC24V (depends on models) Terminal Type Socket Type 11 pin plug Input type Sensor Input Fully universal input( Thermocouple, PT and Analog input are switchable) Indication Accuracy Thermocouple: 1% PT/Analog input: 0.2% Input Sampling Period 50ms Options Event Input Not available Remote SP input Transfer output HB alarm and HS alarm Communications Approvals cULus

11 Comparison

12 E5CN-U E5CC-U Universal Input Yes Output (Relay, Voltage, Current)
Sampling Period 250 ms 50 ms Aux Output 1 or 2 Event Input No Heater Burnout/ SSR Detection Display Size (PV) 11 mm 16 mm CX-Thermo Programming

13 Dimensions E5CC-U: 58.6mm E5CN-U: 70.5mm Space savings of: 11mm E5CN-U

14 E5CC-U has the same terminal arrangement of E5CN-U

15 Mounting Sockets Front Mounting (P2CF-11) Back-connecting (P3GA-11)

16 E5CN-U to E5CC-U Cross Supply Voltage Number of Alarms Output
E5CN-U Model E5CC-U Model 100 to 240 VAC Relay E5CN-RTU E5CC-RW0AUM-000 Voltage E5CN-QTU E5CC-QX0AUM-000 1 E5CNR1TU E5CC-RW1AUM-000 E5CN-Q1TU E5CC-QX1AUM-000 2 E5CN-R2TU E5CC-RW2AUM-000 E5CN-Q2TU E5CC-QX2AUM-000 24 VAC/VDC E5CC-RW0DUM-000 E5CC-QX0DUM-000 E5CC-RW1DUM-000 E5CC-QX1DUM-000 E5CC-RWDAUM-000 E5CC-QX2DUM-000

17 (Thermocouple 500C or less)
Competition E5CC-U Yamatake:SDC15 RKC: SA100 Sampling period 50ms 500ms 250ms Input type Fully universal input Depends on models Indication accuracy ±1% or ±2C ±0.5%FS±1 digit or less ±1C±1digit (Thermocouple 500C or less) Depth 60mm 70mm The number of auxiliary output 2 at max 3 at max The number of pins 11

18 Questions Plan questions to ask the audience if there aren’t any raised…. How they would apply what they just learned? Are we addressing their needs or pain points? What would prevent them from moving forward?


Download ppt "E5CN-U to E5CC-U Conversion"

Similar presentations


Ads by Google