1 1 1 KPS Leak Detection No maintenance and perfect for retro-fit

2 2 KPS Leak Detection – KP 315  What is the worst enemy of service stations ? Leakages Water entry in tanks  What is the best solution against these threats : Leak detection system

3 3 KPS Leak Detection – KP 315 How it works : with double wall piping installation

4 4 Connections to the piping  The leak detection unit is placed at the lowest point of the piping system, one in each tank sump  Polyamide tubing connects from secondary containment of the piping to the leak detection unit  The manifold is used to connect to multiple pipes  If primary pipe is leaking, fuel will flow by gravity down to the leak detection unit

5 5 The Leak Detection Unit  A sensor inside the unit reacts to the presence of fluids Fuel of any sort = leakage from primary pipe to secondary Water = leaking secondary containment Proximity Capacitive sensor

6 6 KPS Leak Detection – KP 315  Non-maintenance  No pressure/vaccum  Easy integration with tank gauging systems

7 7 The Leak Detection Unit Example of installed leak detection box : retrofit

8 8 The Alarm Unit Test buttons Status LED Power supply Alarm Mute Sensors connections Module : Isolated switch amplifiers Intrinsic safely EExi Power supply Fuses, and relay

9 9 Applications: Stand-alone  Local installation with audio and visual alarm  Up to 5 pipes connected to each leak detection unit To monitor up to 9 pipes, add an extra manifold  Up to 6 sumps monitored by one alarm unit. For more, a extra unit can be added

10 10 Applications: Telematic Surveillance  The alarm unit is prepared for GSM connection GSM module Backoffice server Filling station leak detection Notification and surveillance

11 11 Applications: Connected to ATG systems  Connect to tank gauging systems or other external monitoring systems via the outgoing signal relay  NO/NC – potential free switch with breaking or closing function : STOP the submerged pumps system for instance

12 12 Advantages of KP 315 Leak Detection System  Immediate alarm as soon as liquid reaches the sensor - No minimum leak rate or volume  Any leakage is contained by the system and will not contaminate the sump (compare with Veeder-Root containment sump sensors)  No restrictions on pipe volume  Works for all secondary contained pipes (steel, fibreglass, flexible)  Quick reset in case of alarm Disconnect the tubing, empty the container and connect tubing again Ready to go! No drying times or recalibration of systems.  Easy to install One cable from the sump to the alarm unit/building Suitable for retro-fit applications

13 13 Approval  Approved to EN 13160 – Leak Detection Systems

14 14 Suggested Positioning  As an add-on to OPW SiteSentinel  As an add-on to existing Veeder-Root systems  For retro-fit where leak detection is missing  Stand-alone as a low investment solution  Where low/no maintenance costs are required