Presentation is loading. Please wait.

Presentation is loading. Please wait.

Chapter 18 Ventilation.

Similar presentations


Presentation on theme: "Chapter 18 Ventilation."— Presentation transcript:

1 Chapter 18 Ventilation

2 Introduction Ventilation: planned, methodical, systematic removal of pressure, heat, smoke, gases, and flame Essential part of tactical and strategic objectives Late application of proper ventilation subjects firefighters to extreme circumstances Very complex subject area with many facets

3 Principles, Advantages, and Effects of Ventilation
Ventilation: relief of products of combustion Essential to fire suppression Benefits of ventilation: Deprives fire of ability to heat up structure Ventilation channels smoke out of the structure Removal of smoke, heat, and toxic gases add survival time to a potential victim

4 Heat, Smoke, and Toxic Gases
When fire burns, air heats, expands, and rises Exerts pressure on anything that surrounds it Fire spreads by convection and radiation with rising of heated air Fire can spread by pressure Structures built today outfitted with heavy insulation and tight weatherproof seams Many buildings have unopenable windows Ventilation important in these structures

5 Table 18-1 Gases Produced by Fire

6 Considerations for Proper Ventilation
Heat tends to rise, bringing smoke with it Smoke collects under vertical obstructions Mushrooms in all directions when it meets obstruction Gradually fills the structure from highest point Vertical ventilation: removal of gases and smoke through vertical channels Horizontal ventilation: channeling of smoke and heat through horizontal openings

7 Figure Heat, smoke, and fire will follow the path of least resistance and find their way through any available opening.

8 Figure 18-4 Air movement is created by water application
Figure Air movement is created by water application. Openings in back of the nozzle team will create airflow from behind in the direction of the hose team. It can be a source of fresh cool air, or it can pull fire to the nozzle from behind. Indiscriminate ventilation can be a liability. Careful assessment and proper timing are important.

9 Fire and Its By-Products
During combustion, energy is released from exothermic reaction as heat and light Ventilation removes harmful agents Carbon dioxide accelerates respiration Increases the rate of toxin absorption Ventilation prevents: Flashover and backdraft Smoke explosion Rollover/flameover

10 Flashover As trapped heat accumulates at the ceiling, temperature increases When temperature reaches ignition point of any substance in the room, new combustion occurs Forms a chain reaction that causes the entire room and all contents to burn Very rapid fire spread

11 Backdraft (Smoke Explosion)
Rapid ignition of smoke and unburned products of combustion Result of introduction of oxygen into environment With the heat, pressure builds in the confined space When an opening is made a billow of smoke escapes Tunnel of fresh air finds its way to the fire Ignition from seat of the fire burns back to opening along air tunnel

12 Signs of a Potential Backdraft
Short distance to opening Backdraft unspectacular Appears as if fire is flaring up Long distance to opening Amount of proper concentration from opening to seat is greater Ignition travels greater distance and amasses greater force Almost instantaneous reaction like an explosion

13 Rollover/Flameover Heat brings products of combustion to higher levels
Usually accumulate near the ceiling Accumulated heat reaches ignition point Spread across room at ceiling level Fingers of flame reach across the room, followed by a wall of flame Advancing hoseline disrupts the upper thermal layer Disrupts the rollover phenomenon

14 What Needs to be Vented? Without ventilation, expanding heated steam and smoke will roll over the wall of water Drop down behind the hose team Long before entire building requires venting, smaller voids and compartments need to vent Exhaust increasing pressure and intensifying heat If done in a timely manner, involvement of entire building might be avoided

15 (A) Figure (A) Applying water to the upper levels of a thermal layer will cool and disrupt the rollover effect that is apt to occur with the proper conditions. Ventilation is critical when this is done.

16 (B) Figure 18-9 (cont’d.) (B) As a hose team advances into the fire and sprays water in droplet form, it creates a wall of water and disrupts the high-heat thermal layer and cools the upper levels of the compartment. Water absorbs heat as it turns to steam, expanding 1,700 times as it does. If there is no path for the expanding water/steam conversion, it will take the path of least resistance, in this case over the wall of water and the nozzle team. The water movement will then pull any heat from the back of the nozzle team and roll over on top of it. 18.16 16

17 Voids and Compartments
All compartments treated with same understanding Residential building is a large compartment with many sub-compartments Example: apartments Each sub-compartment can be subdivided Example: rooms Each sub-compartment can be further subdivided Example: closets Building might have eaves, peaks, gables, etc.

18 Cocklofts Cockloft: space between ceiling of top floor and bottom of roof Major attack point for ventilation crew Especially in a top-floor fire or fire that has extended into that space

19 Horizontal and Vertical Voids
All heat follows the path of least resistance Unobstructed channel in form of horizontal or vertical void Heat and fire extend without being seen Following pipe chases or electrical wire pathways Ventilating these by opening at highest points exposes extending fire for extinguishment Trapped heat diffused into unheated spaces Minimizes risk of heating up a new portion

20 Figure 18-10 Voids in a typical structure that can trap heat and permit fire extension.

21 Figure 18-10 (cont’d.) Voids in a typical structure that can trap heat and permit fire extension.
18.21

22 Air Movement Convection Conduction Radiation
Venting carries heat out to atmosphere Conduction Venting prevents heat from traveling to uninvolved areas of the structure Radiation Venting delays or prevents exposed material from reaching its ignition temperature

23 Types of Ventilation Several methods used individually or in combination Natural ventilation: open windows and doors Mechanical ventilation: use smoke fans and water to create air movement

24 Natural Opening windows and doors provides natural ventilation
When time not essential; slower venting operation Appropriate for light smoke condition where incident is under control Method of choice for residual smoke removal Cut a hole in the roof or break out windows when greater volumes of smoke need to be removed

25 Figure Smoke will be carried throughout the building to upper floors by normal air currents mixed in with the heat.

26 Mechanical HVAC systems can be used for ventilation in climate-controlled buildings Smoke fans are placed in opening to suck out smoke and heat Establish unobstructed path of airflow from outside opposite the fan Disadvantage: fire crew exposed to smoke and heat Air introduced via PPV fans or blowers Hydraulic ventilation: water creates air movement

27 Figure A smoke ejector exhaust fan placed in an opening will pull air through the fan as it ejects air out of the structure.

28 Figure Positive pressure literally pressurizes the structure and forces smoke out any path of least resistance. Almost the same effect would occur if a light breeze were blowing directly into the structure from one side and venting out the other side.

29 Mechanics of Ventilation
Entire ventilation process is the movement of air from high-pressure location to lower pressure Natural tendency of air is to move from high pressure to lower pressure Assists the firefighter in ventilation

30 Vertical Ventilation Based on the “heat rises” rule of physics
Heat collects at upper levels and spreads fire to those levels Opening vertical arteries releases pent-up gases Reduces chance of fire spreading Heated air replaced with cooler air at lower levels Improved conditions help crew in locating the fire and searching for victims

31 Horizontal Ventilation
Conforms to same rules of vertical ventilation Both are a form of diffusion Molecules spill excess levels of high concentrations into areas of low concentrations Molecules move laterally as well as vertically Molecules bounce off walls and move through openings Openings are made Smoke and heat are channeled out

32 Figure Heated air has more agitation in its molecules, causing internal pressure in a compartment. This will, in turn, create greater velocity when air exits an opening. Normal diffusion takes much longer to occur when only natural air movement and currents are employed.

33 Ventilation Techniques
Many techniques used to effect ventilation Some are simple and require no tools Others are more complex and dangerous to implement, and require sophisticated tools

34 Break Glass Quickest way to open a building is to break glass
Best investment of time for results if done properly Many windows can be broken in time it takes to force one locked door Glass can penetrate skin deep enough to sever arteries and veins Wear protective equipment

35 Open Doors Opening a door will usually exhaust huge volumes of smoke and heat built up Keeping door on its hinges is a good practice May need to close the door to limit fire extension

36 Effects of Glass Panes Many windows have several panes of glass separated by wood or aluminum dividers Entire window should be removed Remove sash, cross members, etc. Remove all glass Sweep around perimeter with a tool Remove glass with a tool: two steps Break through glass from upper to lower sashes Sweep perimeter to remove remaining glass

37 Rope and a Tool When operating off a flat roof beyond reach of a ladder Rope secured to the tool Turn of rope taken around firefighters hand Toss tool out as far as possible from building in horizontal direction This technique leaves shards of glass in place Does not remove screens, window shades or curtains Effective when no other approach easily made

38 Hook or Pike Pole Length of pole keeps firefighter a safe distance from falling glass Longer hook enables access to out-of-reach windows Hook can also be used to extend reach of firefighter attempting to open or close a door Pry tool to remove roof material Used for other purposes that extend the reach or remove firefighter from dangerous positions

39 (A) (B) Figure Making a ventilation hole requires some preplanning. (A) Firefighters should make the hole so that heat, smoke, and possibly flame do not envelop them. (B) When working off a ladder, the same general precautions are necessary. Firefighters must be secured to the ladder before performing any action.

40 (C) (D) Figure (cont’d.) (C) When venting from above, firefighters use the wind to their advantage and stand off to one side so that they are not standing in the path of any initial billow of heat. (D) When pulling off roof boards, firefighters should work in the clear air with the wind blowing smoke away, and be careful with roof debris. It will most likely be hidden in the smoke. 18.40

41 (E) (F) Figure (cont’d.) (E) When removing a skylight, firefighters work with the wind at their backs. It is sometimes less work to lift off the entire housing than to break out each individual pane of glass. (F) When using an ax to remove window glass, the flat side of the ax head should be used, not the point or the striking surface.

42 Iron or Halligan Iron or Halligan tool brought down diagonally through the glass Start at the upper corner Tool sweeps around the perimeter to clean out any large shards Short length a disadvantage Places firefighter near flying glass Places firefighter in path of heat and smoke Plan carefully to minimize risk

43 Ax Ax affords limited reach and places firefighter in hazardous location Use an ax for venting glass Side of ax breaks the glass Do not use blade portion Use of striking head might cause firefighter to lose grip on the handle This technique will not break tempered glass Sharp pointed tool required

44 Portable Ladder Check for overhead obstructions
Place ladder to side of window against side of house Measure the base so that the tip will fall into the glass at about 2/3 the height of the window Reposition the ladder in front of the window Perpendicular to the ground Shove the ladder into the building Tip of ladder crashes through upper pane

45 Negative Pressure Ventilation
Negative pressure created on back side of fan blade Place a fan in a window facing the outward flow Heat and smoke trapped in the compartment forced out Barrier must be created to separate positively charged air from negatively charged air Effective in limited access compartments Do not use during the attack

46 (A) (B) Figure (A) When using an exhaust fan, it is important to cover the openings around the unit. (B) When covering any opening around the exhaust fan, the vacuum necessary to operate efficiently will be created and the exhausted air will not be sucked back around the fan.

47 (C) (D) Figure (cont’d.) (C) When using an exhaust fan in a door, the air will circulate from the exhaust side into the intake side if no provision is made to block that flow. (D) Through the use of plastic, tarps, or even a piece of plywood, the air is prevented from being pulled back into the intake side of the fan. 18.47

48 Positive Pressure Ventilation
Injects air into compartment and pressurizes it Smoke and heat carried into areas of lower pressure outside the structure Fans can be set up to augment one another For every cubic foot of air injected into a compartment, a cubic foot of air must be ejected Most efficient when exhaust opening is ¾ to 1½ times the size of the entrance opening

49 Figure With positive pressure ventilation, the theory is to actually pressurize the compartment and then the smoke and heat will actually be pushed out another opening. To be effective, certain actions must be taken. (1) The blower or fan must be placed a short distance from the opening so that a “cone of air” is created that just barely exceeds the opening being used. (2) The exhaust opening should be smaller than the introduction opening for maximum efficiency. That opening size depends on the number of blowers and their capacity. There are many variations where this practice can be effective.

50 Roof Ventilation Use penthouse doors, skylights, and ventilation shafts for vertical ventilation Two types of vertical openings: Offensive Defensive Place offensive openings into structure and evaluate need for defensive ventilation Directly over the fire, if possible Strip cut (trench cut) is an example of defensive ventilation

51 Expandable Cut Most efficient for time expended
Produces as large a hole as needed Plan the cut so wind will blow smoke away from work area Prevent damage to support rafters or cross members One large opening produces more airflow than several smaller holes Produces debris

52 Figure The initial hole was cut and the “lid” lifted off in one piece. In the foreground, the cuts of the second hole can be seen along the right side of the hole. This type of roof, called an inverted roof, consists of a flimsy under-roof support system while the actual weight-carrying members exist at the occupancy ceiling level. This photo illustrates how little support is available.

53 Two-Panel Louver Operation
Used as an offensive heat hole Often on building construction that uses plywood sheeting under paper as roof cover Based on a series of cuts beginning with an outside cut Opening should be evaluated for effectiveness If expansion needed, repeat steps for cut Last step: push in roofing pieces creating louvers along the cut

54 Louver in Lieu Typically an offensive heat hole operation placed into a panelized roof Performed by a minimum of three people Minimum of two saws, one rubbish or roof hook Placed in area of greatest smoke pressurization While members are standing on purlins Members split into two teams Company Officer closest to means of access and egress

55 Triangular Cut Roof supported by open web bar joist with Q-decking is the best candidate for this type of cut Span of web bar joist often exceeds 24 inches Opening can become a funnel if opened using conventional square cuts Triangular cut will help support underlying Q-decking because it is interlocked Tendency to sag reduced Holes will be relatively small

56 Strip Cut or Trench Cut Ventilates the cockloft area or open attic space Offensive heat hole opening made Gases expanding under the roof are vented to the atmosphere Not permitted to pass a chosen defensive line Building on fire side of the cut unsavable Hoseline positioned below the cut with ceilings pulled down to expose the opening Hoseline should not be operated from roof side

57 Figure 18-33 A trench cut is a defensive move
Figure A trench cut is a defensive move. Ceilings should be pulled below the cut to promote vertical airflow through the trench. Additionally, a hand-line should be in place below the opening to cut off any horizontal extension.

58 Inspection Cut First operation to be accomplished on a flat roof
Determines: Roof covering and depth of covering Roof sheeting material Rafter direction Conditions directly below firefighters Types of operations to be done by ventilation crew First cut made at 45 degrees to a bearing wall Followed by a cut opposite the first Triangular inspection completed with another cut

59 Smoke Indicator Hole Only opening that will adequately determine conditions directly below firefighters Small triangular opening large enough to push D-handle of a roof hook through Small enough that a firefighter will not put a foot through Placed in path of access and egress every 15 to 20 feet of travel

60 Safety Considerations
When considering placement of a hole, consider benefit gained against liability created In some cases, it is best not to vent at that location Example: do not vent if venting would expose a victim and rescuer on a ladder to danger

61 Will Ventilation Permit the Fire to Extend?
No justification for permitting a fire to extend in order to complete a task Order may be given without full understanding of the consequences Report to incident commander for reevaluation if conditions are changing out of sight Most incident commanders gladly countermand in presence of new information

62 Will the Escape Route Be Cut Off?
Individual safety of paramount importance When ventilating, keep an eye toward escape When venting a series of windows, firefighter must work toward the escape point Should always be two easily recognizable ways off a roof Escape routes should be lighted at night if possible Rooftop LCES primary responsibility of person assigned to Roof Division or Ventilation Group

63 Figure 18-35 Ventilate in the direction of the escape route so escape is not cut off.

64 Will Ventilation Endanger Others?
Activity of one firefighter performing a venting task must never endanger position of another When opening a roof, advise everyone else where the holes are Easy to fall into the fire Torn-up roofing material should be cleared away as soon as possible to remove tripping hazards Pile roofing in one place Think ahead of possible safety problems

65 Work in Teams Firefighter should never work alone
Difficult for one person to be aware of everything Affords opportunity for discussion Team member might make the difference between being located in a collapse Team member may make it possible to remove a heavy obstruction

66 Proper Supervision There should be a person on the scene to make decisions when conflicting options presented Presence of supervision ensures effort is unified Supervision brings experience to an activity Prevents team members from becoming too focused on mission

67 Obstacles to Ventilation
Importance of ventilation cannot be overstated Fire operations are unpredictable Firefighters confronted with unforeseen circumstances that delay ventilation activities

68 Access Access is an initial size-up consideration
First assess the needs of the ventilation objective Determine the route to be employed to reach location of job performance task Example: adjoining building Access to rear yard might be impeded by fences or dogs Alternative methods must be employed Map out access strategy for particular building

69 Security Devices Security devices can impede ventilation in access and timing Examples: Gates, screens, steel doors, and closed-up windows Window openings may have been sealed Skylights may have been replaced with plywood attached to inferior support No longer discernible Cause of firefighter deaths

70 Height Be alert to structure’s ventilation needs
Sometimes necessary to cut a hole in an area out of reach Need for reach part of initial size-up Assume reach will be a problem Think proactively not reactively

71 Poor Planning Planning is an obstacle to ventilation that can be addressed Time is not a luxury Planning must occur without delay Quick size-up and implementation of a plan essential for timely ventilation If ventilation delayed, interior team will suffer Backdraft, rollover, diminished survival time, and arduous working conditions

72 Personnel Assignment Task assigned to shorthanded or inexperienced crew will delay ventilation Safety an overriding concern Firefighter may be able to affect ventilation while waiting for reinforcements Roof operation: two-person team can open many openings quickly Structural components can be easily opened or removed by individuals working together

73 Unfamiliar Building Layout
Floor layout can be confusing to the firefighter Building layout can be an obstacle to firefighter attempting to reach the rear Building wings, fences, lower floor extensions Buildings can have multiple doors on same floor but serve three different levels Conduct “walkthroughs” and inspections Often same floor plan exists throughout multistory building

74 Ventilation Timing Ventilation too early can lead to fire extension
Ventilation too late causes unnecessary punishment to the interior forces Can prevent forward progress Vertical ventilation of firefighter access holes is paramount Ventilation may have to be delayed if occupants/firefighters are using stairs

75 Cut a Roof – Open a Roof Cutting a roof and opening a roof are different operations Cutting a roof makes necessary cuts to perform ventilation Once cuts made, roof can be opened Opening refers to removal of roof material Cuts may be made, and opening time delayed

76 Factors Affecting Ventilation
Several factors affect proper ventilation, including the following: Partial openings Screens Type of roof material Wind direction Weather Building size Construction features

77 Partial Openings Single opening has greater ventilation capacity than multiple openings of equivalent area Example: chimneys Greater the circumference of the vessel, the less friction on the sides and the greater the flow Many small holes have greater overall length of perimeters The greater the perimeter, the more opportunity to slow airflow

78 Figure 18-38 Airflow is reduced by friction.

79 Partially Broken Windows
Windowpane that is broken and many shards of glass left in place: Area of opening reduced Presence of shards creates more perimeter opening distance

80 Figure Airflow is greatest through a window where glass is fully removed. Screens, shades, curtains, and window cross members should also be removed.

81 Screens Presence of insect screens in a window that has been broken out is magnified Screen is like a solid panel with hundreds of holes Failure to remove a screen is like opening 100 windows and letting the shutter close on 44 of them Removal of window treatments also important Any obstruction reduces airflow

82 Roof Material Roof material may be several layers thick
Kerf cut of the saw usually permits thin line of smoke to vent When removing several layers of roofing, cut should not penetrate the under-roof area Corrugated metal roof: Kerf cut supplies oxygen Roof erupts into fire where roof weakened by cuts

83 Dropped or Hanging Ceilings
Dropped ceilings create impediments to ventilation process Trapped air pockets conceal fire and smoke Raging fire will not vent through roof opening Several hanging ceilings may be in place Space between ceilings collects gases Dropped ceiling are hazardous because they are: Not always obvious Out of reach of roof firefighter Difficult to open

84 Building Size Building size affects ventilation
In tall buildings, a neutral plane can occur Location where smoke collects instead of rising Factors that affect development of neutral plane: Presence or absence of HVAC systems and ducts Wind direction Presence of other buildings, and their height Outside temperature Presence or absence of smoke shafts

85 Weather On cool dry days, structures vent quickly
On rainy humid days, smoke lifts slowly Snow impedes vertical venting Horizontal venting is not affected the same way Use positive pressure ventilation

86 Opening Windows Simplest way to open a compartment
One full sash opening better than two equal in area Better in general to open top sash fully If smoke condition from door opening will make room conditions worse, close door and open window If two windows, open one at upper sash and other at bottom sash

87 Lessons Learned Ventilation is a tool used in firefighting
Must be understood and manipulated Proper use makes the difference between extinguishing a fire and creating conflagration Ventilation enables firefighter to make a rescue Heat rises and cold air drops Heated air expands; cooled air contracts Airflow follows path of least resistance Can be artificially generated by mechanical means


Download ppt "Chapter 18 Ventilation."

Similar presentations


Ads by Google