1 Control of Bioaerosols

2 Concentrations in Air Concentrations of indoor bacteria range from <100-1500 cfu/m 3 ; avg 0-500 –heated dwellings lower Avg concentrations of outdoor bacteria 200-1000 Avg concentrations of indoor Fungi range from 10-500 Avg concentrations of Outdoor Fungi range from 100-1000

3

4

5

6

7 Air Filtration Part of most HVAC systems Hospitals have very intricate systems No universal standard method for evaluating filter performance –Thus advertised efficiencies may be misleading Most difficult range of particles to filter 0.2 to 0.3 micron; generally particles categorized as > 0.5 or < 0.5 microns Peak Particle Removal with 12-15 ACH

8 Types of Filters Fiberglass- typical household filter 5-7% effective Electronic- lose filtering 50% capacity in first week HEPA- High Efficiency Particulate Air, 99.97% of pollutants at 0.3 microns ULPA- Ultra Low Penetration Air, 99.9997% of particles as 0.1 micron Electrostatic- “static charged”, 95%

9

10

11

12

13

14

15

16

17

18 Other Air Treatments Ionizer- negative ion generation Ozone- good disinfectant, safety risk UV- good disinfectant, 253.7nm, long exposure times?

19

20

21 Cundith et al., Meat Processing Plant Deployed EP filters with scanning UV Three Rooms (100% recirculation) –Processing- 10ºC, 110m 3, 3 m/min –Chill Cooler- 0-2ºC, 130m 3, 21 m/min –Aging Cooler- 0-2ºC, 360m 3, 8m/min

22

23

24

25

26 Kujundzic E, et al.. Effects of ceiling-mounted HEPA-UV air filters on airborne bacteria concentrations in an indoor therapy pool building. J Air Waste Manag Assoc. 2005 Feb;55(2):210-8. – The purpose of this study was to assess the effectiveness of a new generation of high-volume, ceiling-mounted high-efficiency particulate air (HEPA)-ultraviolet (UV) air filters (HUVAFs) for their ability to remove or inactivate bacterial aerosol. In an environmentally controlled full-scale laboratory chamber (87 m3), and an indoor therapy pool building, the mitigation ability of air filters was assessed by comparing concentrations of total bacteria, culturable bacteria, and airborne endotoxin with and without the air filters operating under otherwise similar conditions. Controlled chamber tests with pure cultures of aerosolized Mycobacterium parafortuitum cells showed that the HUVAF unit tested provided an equivalent air-exchange rate of 11 hr(-1). Using this equivalent air-exchange rate as a design basis, three HUVAFs were installed in an indoor therapy pool building for bioaerosol mitigation, and their effectiveness was studied over a 2- year period. The HUVAFs reduced concentrations of culturable bacteria by 69 and 80% during monitoring periods executed in respective years. The HUVAFs reduced concentrations of total bacteria by 12 and 76% during the same monitoring period, respectively. Airborne endotoxin concentrations were not affected by the HUVAF operation.

27 Cundith et al. Console filtration

28 Laboratory Control BSCs Centrifuge containment HVAC

29 Class I Personnel and Environmental Protection No Product Protection Similar to fume hood with HEPA exhaust 75 LPM Hard-ducted to BLDG exhaust 0.5 inches water

30 Class I Some have integral blower Must be turned off in case of BLDG exhaust failure Good design to surround all positive pressure plenums with vacuum

31 Class IIA/B3 (Now Class II A2) 30/70 exhaust/recirculation HEPA filtered on exhaust and recirculation 75 LPM Hard-ducting not recommended Not rated for volatiles or toxics

32 Class IIB1 Originated with NCI designed cabinet 70/30 exhaust/recirculation HEPA filtered on exhaust, recirculation and inflow Personnel, environment and product protection 100 LPM 70% downflow through rear grill; 30% front grill Hard-ducted; preferably dedicated

33 Class IIB2 Total exhaust Personnel, environment and product protection HEPA filtered on inflow and exhaust 100 LPM Hard-ducted;1.5 inches water; must be interlocked; ideally dedicated With internal blower may not be hard-ducted

34 Class III Designed for work with BSL 4 agents Interchange box Heavy duty rubber gloves HEPA filtered on supply and exhaust (double or incinerator) Hard-ducted; dedicated exhaust 0.5 inches water

35 BAG-IN BAG-OUT (BIBO) Additional layer of protection Between BSC and BLDG exhaust HEPA Required for BSL3/BSL4 laboratories