Presentation is loading. Please wait.

Presentation is loading. Please wait.

Construct Wall Framing

Similar presentations


Presentation on theme: "Construct Wall Framing"— Presentation transcript:

1 Construct Wall Framing
BCGCA3004B Construct Wall Framing

2

3 Wall Framing National Construction Code states that

4 What does this mean NSW law has adopted the National Construction Code (NCC) as “Building Law” The “Building Law” says that the methods outline in AS will comply with this law. So if you follow the methods outlined in AS , unless otherwise stated you do not need any other design assistance e.g. Engineer etc.

5 AS Scope Page 9 Section 1.1

6 AS Scope Page 9 Section 1.1 This means that this standard only applies the Residential Buildings (Class 1) or Garages & Carports (Class 10).

7 Wall Frame Members Parts of a frame perform specific functions - supporting live & dead loads - resist Racking Forces - resist Overturning Forces - resist Sliding Forces - resist Uplift Forces -Most members provide a face to accept linings (this means that member sizes may be limited)

8 Live Load

9 Dead Load

10 Racking Forces Wind

11 Overturning Forces Wind

12 Sliding Forces Wind

13 Uplift Forces Wind

14 What is a Timber Frame Structurally Connected Timber Members
Resist Forces Forming a Wall Frame to meet requirements Height Load Roof, Upper Levels etc Openings

15 Timbers Generally Used
Radiata Pine F5 MGP 10 Higher Grades for Lintels etc. Oregon Hardwood Generally only used for Lintels etc. Engineered Timbers

16 Basic Frame Components
Refer page 2 TAFE Guide

17 Common Stud Main Vertical component of the wall
Transfer Loads from Top Plate to Bottom Plate Accept wall finishes Straightness will affect the quality Accept fittings & Fixtures Driers, Shelving etc.

18 Common Studs Vertical members placed between the plates
The set the wall height Studs in external frames resist Wind Loads Generally Stud sizes are 90mm or 70mm wide by 45mm or 35mm in seasoned timbers and 75mm or 100mm wide by 50mm or 38mm in seasoned timbers. Required Stud sizes can be found in AS Supplements (which we will look at Shortly)

19 Common Studs May be Straightened to provide acceptable wall
Only 20% of Studs may be Straightened Studs at sides of Openings & Supporting Concentrated Loads shall not be Crippled

20 Straightening Refer to Page 59 of AS 1684.2

21 Confirmation of Learning
On A4 page supplied draw & label an Isometric view showing the method of Crippling Studs

22 Frame Components Common Studs What Consideration For Selection
Determine Required Grade – Cost v Size, Usually MGP10 Level – Upper/Single or Lower Select Correct Table – For member Upper Floor Joist Spacing – Applicable to Double Storey Only Upper Floor Load Width – Applicable to Double Storey Only Roof Material – Tile/Metal Rafter/Truss Spacing – Roof Panel Width Stud Spacing – How much of Roof Panel does it carry Stud Height – The Taller a stud the less load it can carry Roof Load Width – Roof Panel Length Span Tables supplied – Identify Part

23 Worked Example Determining Studs
Refer to Supplied Plans Determine minimum sizes of Studs External Walls at rear (Single Storey Section) At Point marked 1 External Walls at front (Two Storey Section) At Point marked 2 (Lower Level) At Point marked 3 (Upper Level) Present this to your trainer for confirmation of Understanding and recording of completion of the task

24 Select Stud

25 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Select Correct Table – Upper Floor Joist Spacing – Upper Floor Load Width – Roof Material – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

26

27 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Upper Floor Joist Spacing – Upper Floor Load Width – Roof Material – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

28

29 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing – Upper Floor Load Width – Roof Material – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

30

31 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing –N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

32

33 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing –N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – 600mm Stud Spacing – Stud Height – Roof Load Width -

34

35 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing –N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – 600mm Stud Spacing – 600mm Stud Height – Roof Load Width -

36

37 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing –N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – 600mm Stud Spacing – 600mm Stud Height – 2700 Roof Load Width -

38 3 Options

39 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Level Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing – N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – 600mm Stud Spacing – 600mm Stud Height Roof Load Width

40 Select the best For the Situation 70 x 35 Most Suitable 75mm

41

42 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Select Correct Table – Roof Material – Upper Floor Joist Spacing – Upper Floor Load Width – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

43

44 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Lower Level Select Correct Table – Roof Material – Upper Floor Joist Spacing – Upper Floor Load Width – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

45

46 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 36 Studs Not Notched Roof Material – Upper Floor Joist Spacing – Upper Floor Load Width – Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

47

48 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing –N/A Upper Floor Load Width – N/A Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

49

50 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing – 600mm Upper Floor Load Width – N/A Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

51

52 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing – 600mm Upper Floor Load Width – 3000mm Rafter/Truss Spacing – Stud Spacing – Stud Height – Roof Load Width -

53

54 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing – 600mm Upper Floor Load Width – 3000mm Rafter/Truss Spacing – N/A Stud Spacing – Stud Height – Roof Load Width -

55 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing – 600mm Upper Floor Load Width – 3000mm Rafter/Truss Spacing – N/A Stud Spacing – 600mm Stud Height – Roof Load Width -

56

57 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 7 Studs Not Notched Roof Material – Tile Roof Upper Floor Joist Spacing – 600mm Upper Floor Load Width – 3000mm Rafter/Truss Spacing – N/A Stud Spacing – 600mm Stud Height – 2700mm Roof Load Width -

58

59 To Determine Studs – Answer the Questions
Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Level Select Correct Table – Table 7 Studs Not Notched Upper Floor Joist Spacing – N/A Upper Floor Load Width – N/A Roof Material – Tile Roof Rafter/Truss Spacing – 600mm Stud Spacing – 600mm Stud Height Roof Load Width

60 Most Suitable 75mm Most Suitable 90mm

61 Confirmation of Learning
Refer to Supplied Plans Trainer to Provide Rafter/Truss Spacing Stud Spacing Roof Load Width = ½ Span ÷ Cos (Pitch°) Determine minimum sizes of Studs External Walls at rear (Single Storey Section) At Point marked 1 External Walls at front (Two Storey Section) At Point marked 2 (Lower Level) At Point marked 3 (Upper Level)

62 Basic Frame Components
Refer page 2 TAFE Guide

63 Jamb Studs Additional Studs placed at sides of Openings in walls carrying structural loads Accommodate extra loads imposed by Lintels

64 Jamb Studs - Notching

65 Jamb Studs - Housing Why Bother 2/75 x 3.8mm is more than enough
Housings not allowed in Load Bearing Walls

66 Frame Components Jamb Studs What Consideration For Selection
Determine Required Grade – Cost v Size. Upper or Single Level) or Lower Level – Is it taking 1st Floor Load. Select Correct Table – Common, Jamb or Concentrated Loads Studs. Upper Floor Load Width – Floor Load Panel Length (Only Applies to 2 Storey). Roof Material – Tile or Metal Roof Roof Load Width – Roof Load Panel Length Lintel Span – Opening being Spanned Stud Height – Taller Stud has less ability to carry load. Span Tables supplied – Identify Part

67

68 Frame Components Jamb Studs What Consideration For Selection
Determine Required Grade – MGP10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 11 Upper Floor Load Width – N/A Roof Material – Tile Roof Load Width – Lintel Span – Stud Height – Span Tables supplied – Identify Part

69

70 Frame Components Jamb Studs What Consideration For Selection
Determine Required Grade – MGP10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 11 Upper Floor Load Width – N/A Roof Material – Tile Roof Load Width – 5400 Lintel Span – Stud Height – Span Tables supplied – Identify Part

71

72 Frame Components Jamb Studs What Consideration For Selection
Determine Required Grade – MGP10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 11 Upper Floor Load Width – N/A Roof Material – Tile Roof Load Width – 5400 Stud Height – 2700 Lintel Span – Span Tables supplied – Identify Part

73

74 Frame Components Jamb Studs What Consideration For Selection
Determine Required Grade – MGP10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 11 Upper Floor Load Width – N/A Roof Material – Tile Roof Load Width – 5400 Stud Height – 2700 Lintel Span – 1900 Span Tables supplied – Identify Part

75 Most Suitable for 75mm Most Suitable for 90mm

76 Studs for Concentrated Loads

77 Studs for Concentrated Loads See Page 67 - AS 1684.2 - 2006
Point Load from Beam etc. that gathers load from other structural members

78 Studs for Concentrated Loads See Page 67 - AS 1684.2 - 2006
Point Load from Beam etc. that gathers load from other structural members Beams etc. > 3000mm that take loads from Strutting Beams Roof Struts Girder Trusses or Hanging Beams

79

80 Frame Components Studs Supporting Concentrated Loads`
What Consideration For Selection Determine Required Grade – Cost v Size. Upper or Single Level) or Lower Level – Is it taking 1st Floor Load. Select Correct Table – Common, Jamb or Concentrated Loads Studs. Upper Floor Load Width – Floor Load Panel Length (Only Applies to 2 Storey). Roof Material – Tile or Metal Roof Stud Height – Taller Stud has less ability to carry load. Roof Area Supported – Roof Load Imposed Span Tables supplied – Identify Part

81

82 Frame Components Studs Supporting Concentrated Loads`
What Consideration For Selection Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 9 Upper Floor Load Width – N/A Roof Material – Tile Stud Height – Roof Area Supported – Span Tables supplied – Identify Part

83

84 Frame Components Studs Supporting Concentrated Loads`
What Consideration For Selection Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 9 Upper Floor Load Width – N/A Roof Material – Tile Stud Height – 2700 Roof Area Supported – Span Tables supplied – Identify Part

85

86 Frame Components Studs Supporting Concentrated Loads`
What Consideration For Selection Determine Required Grade – MGP 10 Upper or Single Level) or Lower Level – Single Select Correct Table – Table 9 Upper Floor Load Width – N/A Roof Material – Tile Stud Height – 2700 Roof Area Supported – (4.150 x 5.400) ÷ 4 = 5.6m2 = 4.150 = 5.400 Note – Dimensions are in metres

87 Therefore a 70 x 45 is sufficient

88 Studs supporting concentrated Loads
It is important that you develop the ability to recognise the location of Concentrated Loads This will allow you to install the required studs while manufacturing the frames

89 Discuss Concept of Pattern Stud
Common Studs Lintel Positions Trimmers

90 Basic Frame Components
Refer page 2 TAFE Guide

91 Frame Components Bottom Plate
Horizontal member that form the bottom of the frame. Bottom plate must run full length of wall, except at openings (cl 6.2.2) Bottom plates are joined with butt joints with fixing near the joint Joints must be fully supported

92 Frame Components Bottom Plate
Horizontal member that form the bottom of the frame. Bottom plate must run full length of wall, except at openings (cl 6.2.2) Bottom plates are joined with butt joints with fixing near the joint Joints must be fully supported Where the Bottom Plate Supports a concentrated Load or Jamb Studs to openings > 1200, the bottom plate must be fully supported

93 Frame Components Bottom Plate Sizing
Bottom plate sizing is dependent on its span If it is fully supported (e.g. Concrete Slab) only nominal 35mm thickness required for any structural grade (cl 6.3.3) Items to consider when determining the size of Bottom Plate are listed in the span tables where you make the selections. (page 1 & 2 of Handout) Timber Grade – Strength of Timber Joist Spacing – Means greater span Loading – Load that is to be disturbed through structure Is it a tiled roof, Is it the lower level of a 2 storey building Rafter/Joist Spacing – More load concentrated at studs once distributed. Span Tables supplied – Identify Part

94 Design Parameters for Bottom Plate

95 Worked Example Roof Material Sheet Roof Rafter / Truss Spacing 600mm
Joist Spacing 450mm Roof Load Width 6000mm

96 Worked Example Roof Material Sheet Roof Rafter / Truss Spacing 600mm
Joist Spacing 450mm Roof Load Width 6000mm

97

98 Worked Example Roof Material Sheet Roof Rafter / Truss Spacing 600mm
Joist Spacing 450mm Roof Load Width 6000mm

99

100 Worked Example Roof Material Sheet Roof Rafter / Truss Spacing 600mm
Joist Spacing 450mm Roof Load Width 6000mm

101 Select most Suitable

102 Worked Example Roof Material Sheet Roof Rafter / Truss Spacing 600mm
Joist Spacing 450mm Roof Load Width 6000mm

103 v 70 x 45 Or 90 x 45

104 Confirmation of Learning
Determine Minimum Member Size Based on Following Data (Conventional Floor System) Roof Load Width 4100mm Truss Spacing 600mm Joist Spacing 450mm Stud 90mm Wide Roof Material Tile Minimum Size ______________________ (Concrete Slab) Joist Spacing N/A Stud 70mm Wide

105 Confirmation of Learning - Answer
Determine Minimum Member Size Based on Following Data (Conventional Floor System) Roof Load Width 4100mm Truss Spacing 600mm Joist Spacing 600mm Stud 90mm Wide Roof Material Tile Minimum Size 2/ 70 x 45 (Concrete Slab) Joist Spacing N/A Stud 70mm Wide Minimum Size 70 x 35 (Nominal as Fully Supported)

106 Basic Frame Components
Refer page 2 TAFE Guide

107 Top Plate An Important Structural Member
Provides Lateral tie to the Building

108 Top Plate An Important Structural Member
Provides Lateral tie to the Building Provides a transition point for the connection of Roofing Members and distribution of loads A Component of the Bracing System

109 Top Plate An Important Structural Member
Provides Lateral tie to the Building Provides a transition point for the connection of Roofing Members and distribution of loads A Component of the Bracing System A component of the uplift restraint system

110 Top Plate To Plates must run full length of the wall
Top Plate must run over openings Concentrated Loads must be Fully Supported

111 Frame Components To Plate Sizing
Top plate sizing is dependent (See pages 3 to 6 of Handout) Positioning of Rafter/Truss (See next Slide) Upper or Lower Level (Pages 3 & 4 v Pages 5 & 6) Timber Grade – Strength of Timber Roof Material – Tile v Metal Rafter/Truss Spacing – How & Where the Load is applied Stud Spacing – How much bending will be caused by Rafters Roof Load Width - How wide is the Building (see next slide) Span Tables supplied – Identify Part

112 Frame Components To Plate Sizing
Top plate sizing is dependent (See pages 3 to 6 of Handout) (Pages 3 & 4 v Pages 5 & 6) Timber Grade – Strength of Timber Location – Single Level , Upper Level or Lower of 2 Storey Roof Material – Tile v Metal Rafter/Truss Spacing – How & Where the Load is applied Tie Down Spacing – Bending imposed on Top Plate by Uplift Stud Spacing – How much bending will be caused by Rafters Roof Load Width - How wide is the Building (see next slide)

113 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 600mm Stud Spacing 450mm Roof Load Width 6000mm

114 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 600mm Stud Spacing 450mm Roof Load Width 6000mm

115

116 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 600mm Stud Spacing 450mm Roof Load Width 6000mm

117

118 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 600mm Stud Spacing 450mm Roof Load Width 6000mm

119

120 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 600mm Stud Spacing 450mm Roof Load Width 6000mm

121

122 Worked Example Roof Material Sheet Roof Location Single Storey
Rafter / Truss Spacing 600mm Tie Down Spacing 0 Stud Spacing 450mm Roof Load Width 6000mm

123 70 x 45 90 x 45

124 Confirmation of Learning
Determine Minimum Member Size Based on Following Data Roof Material Sheet Roof Location Single Storey Rafter / Truss Spacing 600mm Tie Down Spacing 0 Stud Spacing 600mm Roof Load Width 5500mm Wall Frame Width 70mm Minimum Size ______________________

125 Confirmation of Learning - Answer
Determine Minimum Member Size Based on Following Data Roof Material Sheet Roof Location Single Storey Rafter / Truss Spacing 600mm Tie Down Spacing 0 Stud Spacing 600mm Roof Load Width 5500mm Wall Frame Width 70mm Minimum Size 70 x 45

126 Undersize Top Plate

127 Undersize Top Plate

128 Plates Seasoned timbers are dressed therefore trenching not required
Rough Sawn Timbers such as Oregon, Hardwood require trenching. Housing of plates for studs provides a constant thickness Trenching keeps Top & Bottom plates parallel Restrains Unseasoned Studs from twisting

129 Trenching usually appox 10 mm
Trenching depth is not critical but what is left on is. Top Plates fully supported on masonary walls will be sized based on a 300mm spacing

130 Joining of Plates Where plates are butt jointed they may be joined using a connector plate.

131 Joining of Plates Plates may be Scarfed or Lapped jointed.
Theses are time consuming and rarely used

132 Calculate Plate Lengths
During Fabrication Top & Bottom Plates are the same length Plates should be as long as possible Consider manpower available to stand frames Remember Top Plate must be continuous

133 Roof Load Width AS Definition

134 Roof Load Width Why is it an Important Consideration?

135 Roof Load Width Why is it an Important Consideration?
Compare if Y= 5m & b = 0.6m

136 Roof Load Width Why is it an Important Consideration?
The Top Plate in the Top example is taking more load B = 2 = 5.6m Compare if Y= 5m & b = 0.6m B = 6 = 1.433m

137 Uplift Uplift is a complex item and dealt with at Cert IV level
Generally in Sydney for a Tile Roof it is not a consideration (See next slide) except for; Ocean Front Top of a Hill Isolated Buildings with no wind shielding

138

139 Basic Frame Components
Refer page 2 TAFE Guide

140 Lintels Also referred to as a Head when it is not supporting Structural Loads Horizontal Load Bearing Member between Studs Purpose is to transfer structural loads that are above an opening to load bearing studs May be made of many materials - Timber - Engineered Timbers - LVL’s, I Beams - Structural Steel or Cold Rolled Steel Sections

141 Lintels – Installation Requirements
AS 1684 Figure 6.9 page 64

142 Lintels – Installation Requirements
AS 1684 Figure 6.9 page 64

143 Lintels – Installation Requirements
AS 1684 Figure 6.9 page 64

144 Lintels – Installation Requirements
AS 1684 Figure 6.9 page 64

145 From experience this is my preferred method as if there is
A change in size or height, it does not require a major alteration It is a simple change of the infill head.

146 Lintels – Requirement for Top Plate
Top Plate must be Continuous The Top Plate CANNOT be cut To fit a Lintel

147 Frame Components Lintel Sizing
Lintel sizing is dependent (See pages 9 & 10 of Handout) Timber Grade – Strength of Timber Roof Material – Tile v Metal Location – Upper,Single or Lower Level of 2 Storey Floor Load Width– Applicable to Lowers Storey of 2 Storey Only Roof Load Width - How wide is the Building Rafter Truss Spacing – Loading on Beam Lintel Span – Required Span Span Tables supplied – Identify Part

148 Worked Example

149 Worked Example Timber Grade – MGP10 Roof Material – Tile
Location – Single Level Floor Load Width– Roof Load Width – Rafter Truss Spacing – Lintel Span –

150

151 Worked Example Timber Grade – MGP10 Roof Material – Tile
Location – Single Level Floor Load Width – N/A Roof Load Width – 3500mm Rafter Truss Spacing – Lintel Span –

152

153 Worked Example Timber Grade – MGP10 Roof Material – Tile
Location – Single Level Floor Load Width – N/A Roof Load Width – 3500mm Rafter Truss Spacing – 600mm Lintel Span –

154

155 Worked Example Timber Grade – MGP10 Roof Material – Tile
Location – Single Level Floor Load Width – N/A Roof Load Width – 3500mm Rafter Truss Spacing – 600mm Lintel Span – 2100mm

156

157 6. Noggins

158 6. Noggins Stop Studs from Twisting, Cupping etc
Assist Studs to take load – prevent buckling under load Form Part of Bracing System

159 6.Noggins Walls > 1350mm in height must have noggins
Max Spacing between rows = 1350mm No Stress grading required Min 25mm Thick Noggins may be offset 2 x Thickness to allow for ease of Installation Min width = Wall Thickness – 25mm

160 Confirmation of Learning
How many Rows of Noggins are required for following wall heights. 2550 3000 3800 Is a 70 x 35 Noggin suitable for a 90mm Wall Frame

161 Bracing

162 6. Bracing Member that prevents distortion of frame by Racking Forces
You must determine Wind load on Building

163 Bracing There are many materials that can be used to Brace a wall frame. These generally form part of a system. See page 4 of TAFE Notes

164 Diagonal Timber Bracing
Rarely Used Today.

165 Diamond Bracing Not Mentioned in AS 1684.2.
Must be Considered an Alternative Solution. Would require an Engineer to Certify.

166 Perforated Metal Angle
Where there a 2 in a wall, They should oppose each other

167 Hoop Iron Cross Bracing
A very good and efficient method and should be 1st choice

168 Hoop Iron Cross Bracing
Tensioning should be done during the hottest part of the day

169 Hoop Iron Cross Bracing
Final Nailing off should be done as late as possible Leave temporary bracing as long as possible

170 Sheet Bracing Plywood or Hardboard (Masonite)

171 6. Bracing Member that prevents distortion of frame by Racking Forces
Section 8 of Standard

172

173 (a) Determine Wind Classification

174 Limitations of Classification

175 Same Limitations AS

176 (a) Determine Wind Classification
AS 4055 Outline the Process to Determine Geographic Wind Speed Terrain Category Topographic Class Shielding

177 (a) Determine Wind Classification
AS 4055 Outline the Process to Determine Geographic Wind Region Terrain Category Topographic Class Shielding

178 1.Geographic Wind Region

179 Exercise What Region are the following Cities or towns located in
Sydney ______________ Brisbane ______________ Melbourne ______________ Darwin ______________ Perth ______________ Grafton (NSW) ______________ Townsville (Qld) ______________ Alice Springs (NT) ______________ Perisher Valley (NSW) ______________ Launceston (TAS) ______________ Port Hedland (WA) ______________

180 Exercise - Answer What Region are the following Cities or towns located in Sydney A Brisbane B Melbourne A Darwin C Perth A Grafton (NSW) B Townsville (Qld) C Alice Springs (NT) A Perisher Valley (NSW) A Launceston (TAS) A Port Hedland (WA) D

181 (a) Determine Wind Classification
AS 4055 Outline the Process to Determine Geographic Wind Speed Terrain Category Topographic Class Shielding

182 2.Terain Category

183 2.Terain Category

184 Exercise Determine The Follow Terrain Categories
An Isolated House at Woomera with no significant Topographical features for 15km in all directions. Classification _________________ A House at Bronte located on the Ocean Front. Classification _________________ House Build adjacent to Richmond Air force Base A house in Alexandria (NSW)

185 Exercise - Answer Determine The Follow Terrain Categories
An Isolated House at Woomera with no significant Topographical features for 15km in all directions. Classification TC1 A House at Bronte located on the Ocean Front. Classification TC2 House Build adjacent to Richmond Air force Base A house in Alexandria (NSW) Classification TC3

186 (a) Determine Wind Classification
AS 4055 Outline the Process to Determine Geographic Wind Speed Terrain Category Topographic Class Shielding

187 3. Topographic Class Topographic class determines the effect of wind on a house considering its location on a, hill, ridge or escarpment and the height and average slope of the hill, ridge or escarpment.

188 3. Topographic Class Where average slope is
Greater than 1 in 20 is the Start of the “Hill” .

189 3. Topographic Class Height of Hill.

190 3. Topographic Class Height of Hill. Note Parameter for Escarpment

191 3.Topographic Class AS

192 Topography for Hills Explained

193 Determine Average Slope
The average slope of a hill, ridge or escarpment (φa) shall be the slope measured by averaging the steepest slope and the least slope through the top half of the hill, ridge or escarpment.

194 AS 4055 - Table 2.3 Row 1 Average Slope < 1 in 10 T1 All Heights T1

195 AS 4055 - Table 2.3 Row 2 Average Slope < 1 in 10 & > 1 in 7.5
*Less than 20m all T1

196 AS 4055 - Table 2.3 Row 3 Average Slope < 1 in 7.5 & > 1 in 5
*H > 30 T3 *H ≤ 30 T2 T1 T1 *Less than 9m all T1

197 AS 4055 - Table 2.3 Row 4 Average Slope < 1 in 5 & > 1 in 3
H > 30 T4 H ≤ 30 T3 T2 H T1

198 AS 4055 - Table 2.3 Row 5 Average Slope > 1 in 3 H > 30 T5

199 Topography for Escarpments Explained

200 3.Topographic Class AS

201 Determine Average Slope
The average slope of a hill, ridge or escarpment (φa) shall be the slope measured by averaging the steepest slope and the least slope through the top half of the hill, ridge or escarpment.

202 AS 4055 - Table 2.3 Row 1 Average Slope < 1 in 10 T1 T1 T1
All Heights T1

203 AS 4055 - Table 2.3 Row 2 Average Slope < 1 in 10 & > 1 in 7.5
*Less than 20m all T1

204 AS 4055 - Table 2.3 Row 3 Average Slope < 1 in 7.5 & > 1 in 5
*H > 30 T3 *H ≤ 30 T2 T1 T1 T1 *Less than 9m all T1

205 AS 4055 - Table 2.3 Row 4 Average Slope < 1 in 5 & > 1 in 3
H > 30 T4 H ≤ 30 T3 T2 T2 H T1

206 AS 4055 - Table 2.3 Row 5 Average Slope > 1 in 3 H > 30 T5

207 Worked Example For Our Purposes in this course we will always use T1
You will go into more detail in the CERT IV Course

208 (a) Determine Wind Classification
AS 4055 Outline the Process to Determine Geographic Wind Speed Terrain Category Topographic Class Shielding

209 4.Shielding The affect of local obstructions on wind flow
The 5 year likely impact must be considered Growth of Trees etc. Proposed Developments etc. Classes Full Shielding (FS) Partial Shielding (PS) No Shielding (NS)

210 Full Shielding (FS) Surrounded by 2 Rows of Houses
Heavily Wooded Areas (Zones A & B Only) Typical Suburb consisting of 10 houses per Ha Roads or Parks less than 100m wide are ignored

211 Partial Shielding (PS)
2.5 Houses, Trees, Sheds etc. per Ha In Regions C & D heavily wooded areas

212 No Shielding (NS) No Permanent Obstructions
Less than 2.5 obstructions per Ha First 2 Rows abutting Open Parkland, Open Water, Airfield etc.

213 Worked Examples

214

215 Wind Classification

216 Worked Example TAFE UNI Randwick Town Centre

217 Worked Example Geographic Wind Region Region A

218 Worked Example Geographic Wind Region Region A Topography T1
House is not On a hill

219 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Shielded by 2 Rows of Houses

220 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Terrain Category TC 3

221 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Terrain Category TC 3

222 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Terrain Category TC 3

223 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Terrain Category TC 3

224 Worked Example Geographic Wind Region Region A Topography T1
Shielding FS Terrain Category TC 3 Wind Category is N1

225 Worked Example Bronte Ocean Front

226 Worked Example Geographic Wind Region Region A

227 Worked Example Geographic Wind Region Region A Topography T5
House is located on top Of 30m escarpment

228 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS No Shielding on Ocean Side – You must always use worst case example

229 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS Terrain Category TC1

230 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS Terrain Category TC1

231 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS Terrain Category TC1

232 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS Terrain Category TC1

233 Worked Example Geographic Wind Region Region A Topography T5
Shielding NS Terrain Category TC1 Wind Category = N5

234

235 Determine Wind Pressure
Determined by; Wind Classification Tables 8.1 to 8.5 AS Is dependant on the shape of the Building Is it a Gable or Hip or a more Complex shape? – Explained in Next Slides

236

237

238

239

240

241

242 Area of Elevation Table 8.2 h = ½ height of the wall (half of the floor to ceiling height). For wind direction 2, the pressure on the gable end is determined from Table 8.1 pressure on the hip section of the elevation is determined from Table 8.2. The total of racking forces is the sum of the forces calculated for each section. Eaves < 1m2 can be ignored. Table 8.1 Table 8.2 Table 8.2 Table 8.2

243 Area of Elevation You must determine Area of each part of the
11000 You must determine Area of each part of the elevation Of the Building. 7000 15000 6000 8000 5000

244 Area of Elevation Wind Direction 1 has 2 Shapes 1.1 = 14m2 1.2 = 16m2

245

246 (d) Calculating Racking Force
Formula Area of Elevation x Wind Pressure Required Data Pitch = 30°

247 (d) Calculating Racking Force
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x Wind Pressure ? 1.2 = 16m2 2 1 6000 5000 Wind Direction 2 has 2 Shapes 1.1 = 14m2 1.2 = 14m2 2 1

248 Wind Pressure Direction 1.1

249 (d) Calculating Racking Force
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x 0.75 = 10.5 1.2 = 16m2 x Wind Pressure ? 2 1 6000 5000 Wind Direction 2 has 2 Shapes 1.1 = 14m2 1.2 = 14m2 2 1

250 Wind Pressure Direction 1.2

251 (d) Calculating Racking Force
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x 0.75 = 10.5 1.2 = 16m2 x 0.74 = 11.84 Total Racking Force = 22.34 2 1 6000 5000 Wind Direction 2 has 2 Shapes 1.1 = 14m2 x Wind Pressure ? 1.2 = 14m2 2 1 8000 7000

252 Important Note Which Wind Pressure to Use ? Wind N2
8 000 Pitch 25° 15 000 As shape is the same from both directions We use the same Table (8.2)

253 Pressure = 0.73 in Both Directions

254 Important Note Which Wind Pressure to Use ? Wind N2
8 000 Pitch 25° Table 8.1 Table 8.2 15 000 As shape is different in each elevation we must determine individually for each direction And use WORST case.

255 Pressure = 0.92

256 Pressure = 0.71

257 Important Note Which Wind Pressure to Use ? Wind N2
The Gable End will ALWAYS have the highest pressure 8 000 Pitch 25° Table 8.2 = 0.71 Table 8.1 = 0.92 15 000 As the worst case is the Gable End, we must use the wind Pressure from Table 8.1 = 0.92

258 Pressure = 0.71

259 (d) Calculating Racking Force - Revisited
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x 0.75 = 10.5 1.2 = 16m2 x 0.74 = 11.84 Total Racking Force = 22.34 2 1 6000 5000 Wind Direction 2 has 2 Shapes 1.1 = 14m2 x Wind Pressure ? 1.2 = 14m2 2 1

260 Wind Pressure Direction 1.2
You must use this table as it is a Gable End

261 (d) Calculating Racking Force
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x 0.75 = 10.5 1.2 = 16m2 x 0.74 = 11.84 Total Racking Force = 22.34 2 1 6000 5000 Wind Direction 2 has 2 Shapes 2.1 = 14m2 x 0.92 = 12.88 2.2 = 14m2 x Wind Pressure ? 2 1 8000 7000

262 Wind Pressure Direction 2.2

263 (d) Calculating Racking Force
Racking Force = Area x Wind Pressue Wind Direction 1 has 2 Shapes 1.1 = 14m2 x 0.75 = 10.5 1.2 = 16m2 x 0.74 = 11.84 Total Racking Force = 22.34 2 1 6000 5000 Wind Direction 2 has 2 Shapes 2.1 = 14m2 x 0.92 = 12.88 2.2 = 14m2 x 0.72 = 10.08 Total Racking Force = 22.96 2 1 8000 7000

264 Before we do this lets see what (f) says

265 Before we do this lets see what (f) says

266 Clause 8.3.6.6 We must start placing Bracing at, External Walls &
At Corners

267 Before we do this lets see what (f) says

268 Clause 8.3.6.7 Single or Upper Level Bracing
Max Spacing is 9m for N2 & N2 Wind Classification For N3 & above refer Tables

269

270

271 Before we do this lets see what (f) says

272 Table 8.18 List Types of Bracing Systems that are “Deemed to Satisfy”
Gives a value per/m length of Bracing Panel Theses values are used to counteract the Racking Forces calculated.

273

274

275

276

277

278

279

280

281

282

283

284

285

286 Before we do this lets see what (f) says

287 Clause &Table 8.19

288 Lets Design

289 Design Wind Direction 1.1 Racking Force = 10.5 Wind Direction 1.2
3500 Wind Direction 2.1 Racking Force = 12.88 7000 3500 4500 6000 3000 Wind Direction 2.2 Racking Force = 10.08 8000 3000 5000

290 Nominal Wall Bracing

291 Design – Area 1.1 Wind Direction 1.1 Racking Force = 10.5 3500 7000
4500 6000 3000 8000 3000 5000

292 Design – Area 1.1 Wind Direction 1.1 Racking Force = 10.5
Metal Cross Strapping to Corners As per Table 8.14 (b) 3500 7000 3500 4500 6000 3000 Note you must do all corners Regardless of Overkill 8000 3000 5000

293 Design – Area 1.1 Wind Direction 1.1 Racking Force = 10.5
Metal Cross Strapping to Corners As per Table 8.14 (b) 3500 7000 3500 4500 6000 3000 You Still would place Bracing on Internal Walls To assist During Constructions Using any Method (a) is easiest 8000 3000 5000

294 Design – Area 1.1 Wind Direction 1.1 Racking Force = 10.5
Metal Cross Strapping to Corners As per Table 8.14 (b) 3500 7000 3500 4500 6000 3000 You Still would place Bracing on Internal Walls To assist During Constructions Using any Method (a) is easiest 8000 3000 5000

295 Design – Area 1.2 Wind Direction 1.2 Racking Force = 11.84 3500 7000
4500 6000 3000 8000 3000 5000

296 Design – Area 1.2 Wind Direction 1.2 Racking Force = 11.84
3500 7000 3500 4500 6000 3000 8000 Metal Cross Strapping to Corners As per Table 8.14 (b) 3000 5000

297 Design – Area 1.2 Wind Direction 1.2 Racking Force = 11.84
3500 7000 3500 4500 6000 3000 Bracing to Internal Walls to Spread Bracing thru Structure Assist During Construction 8000 3000 5000

298 Design – Area 2.1 Wind Direction 2.1 Racking Force = 12.88 3500 7000
4500 6000 3000 8000 3000 5000

299 Design – Area 2.1 Wind Direction 2.1 Racking Force = 12.88
3500 Wind Direction 2.1 Racking Force = 12.88 7000 3500 4500 6000 3000 8000 Metal Cross Strapping to Corners As per Table 8.14 (b) 3000 5000

300 Design – Area 2.1 Wind Direction 2.1 Racking Force = 12.88
3500 Wind Direction 2.1 Racking Force = 12.88 7000 3500 4500 6000 3000 8000 Bracing to Internal Walls to Spread Bracing thru Structure Assist During Construction 3000 5000

301 Design – Area 2.2 Wind Direction 2.2 Racking Force = 10.08 3500 7000
4500 6000 3000 Wind Direction 2.2 Racking Force = 10.08 8000 3000 5000

302 Design – Area 2.2 Wind Direction 2.2 Racking Force = 10.08 3500 7000
4500 6000 3000 Wind Direction 2.2 Racking Force = 10.08 8000 3000 5000

303 Design – Area 2.2 Bracing to Internal Walls to
3500 7000 3500 4500 6000 3000 8000 Bracing to Internal Walls to Spread Bracing thru Structure Assist During Construction 3000 5000

304 Lets Design

305 Clause Top of INTERNAL Bracing Walls must be fixed to Ceiling or Upper Floor Structure with equivalent Shear Capacity as to its Bracing Capacity

306 See Next Slide for Explanation

307 Confirmation Learning
Complete Exercise 42 of your workbook

308 Connection of Internal Brace Walls
In our Exercise we use Crossed Hoop Iron 3500 7000 3500 4500 6000 3000 Bracing Value = 1.5 Bracing Panel Length = 2.7 Total Force = 1.5 x 2.7 = 4.05kN 8000 3000 5000

309 Total Force = 4.05kN Seasoned Radiata Pine = JD4 1 Fixing at each end of Bracing Panel = 2 x 2.1kN = 4.2 (Sufficient)

310

311 Wall Frames Frames are classified into 2 categories
Load Bearing – They are structural frames, they transfer loads from roof or upper floor to the supporting floor frame. They can be either external or internal walls. Non Load Bearing – - do not support any structural loads. - They support their own weight - Non structural loads doors and frame, kitchen cupboards, driers etc. - support some live loads eg Doors closing. Therefore there are some minimum requirements for these AS cl 6.3.5

312 AS cl 6.3.5

313 Wall Components

314 Trimmers Horizontal members fixed between window studs and door studs.
Referred to as Sill or Head trimmers Usually of the same section size bottom plates Openings wider than 1800mm require trimmers as specified in AS cl & table 6.3

315 Trimmers Refer Table 6.3 of your Australian Standard

316 Trimming Studs Run from Trimmers to Plates – Use same Timber Size
Used to block out Narrow Lintel Where use in conjunction with Lintel they may take structural loads Must be same depth as wall frame to accept finishes May also be referred to as “Jack”, “Soldier”, or “Short” studs

317 Wall Intersections Blocking
Placed at intersections of wall frames Normally 3 Blocks per intersection

318 Blocking AS1684.2

319 What is a Concentrated Load ?
>3000

320

321

322 Stress Grading Refers to the Timbers Strength
Timber must be able to withstand stress loads placed on them. Overloading may cause straining or failure 3 types of stress Compressive Tensile Shear Note Torsional Stress is not discussed

323

324

325 Stress Grading Members Sizes will be determined for span tables
Generally for Residential Construction sizes will not be specified by designers Why? Architect will not want to take responsibility Engineer will want to charge extra to do this and Why would a client want to pay for something that he can get done for nothing

326 Stress Grading Why are members generally specified on Commercial projects AS Residential Timber Framed Construction Guide

327

328 AS Limitations 1.4.4 The Maximum number of storey's of timber shall not exceed 2 1.4.5 The maximum width of a building shall mm, Note, if you use AS simplified max width = mm The maximum wall height shall be 3000mm excluding gable ends 1.4.7 The maximum roof pitch shall be 35 degrees

329

330 Ordering Timber Timber is ordered in lineal meters may be priced in cubic meters Increments of 300mm Timber should be ordered as required - avoid unnecessary exposure to weather - affecting cash flows - theft - storage

331 Material Storage Timber should be stored on gluts
This allows for airflow Care should be taken in stack sizes Stacks can be strapped for safety

332 Storage of Materials Timber should be stored as close as possible to work area

333

334

335

336

337

338

339

340 Stud Spacing – Other Consideration
Stud Spacing may also be determined by sheeting

341 Studs Not all external sheeting require critical stud placement
Check with LATEST manufactures manual as to requirements

342

343 Harditek (Blue Board) For Sheet Products Stud Placement is Important

344 Calculating Stud Lengths
Finished Floor to Ceiling govern stud length Minimum Habitable Room is 2400mm Clear Floor Finishes 1. Carpet 20mm 2. Timber Flooring 40mm (Depending on Batten) Ceilings 1. 10mm Plasterboard 2. 13mm Plasterboard

345 Calculating Stud Length
Double Storey building may have FFL (Finished Floor Level). Allowance must be made for structural members Most Importantly Determine if there are any height restrictions Type of Roof Will affect Stud Heights

346 Top & Bottom Plates = 90 x 45 F5 Step 1 – Determine Floor & Ceiling Floor Carpet = 20mm Ceiling Gyprock = 13mm Step 2 – Calculate Stud Length Minimum Clearance = 2400mm Plus Flooring = mm Plus Ceiling = mm Wall Height = 2440mm less Wall Plates = mm Stud Length = 2350mm

347 Ground Fl Finish = Timber (40mm) First Floor = Carpet (20mm)
Upper Level Joists = 200 x 50 F5 Top & Bottom Plates = 90 x 45 Step 1- Determine SFL (Structural Floor Level) SFL First Floor = (FFL First Fl) -20 (Carpet) SFL= SFL Ground Fl = (FFL Gnd) - 40 (Timber) SFL = Step 2 – Calculate Height Difference SFL First Floor = – SFL Ground Fl = Height Difference = Ground Floor First Floor

348 Step 3 – Structural Elements Height Diff = 2.750 Less Flooring = 0.017
Less Floor Joist = 0.200 Less T & B Plate = 0.090 Stud Length = 2.443 Ground Floor First Floor

349 Carpet Both Floors (20mm) Ceilings 10mm Plasterboard (Allow 20mm)
Dimensions are clear measurements Lower level plates Upper Level Plates Bottom Plate = 90 x 35 F5 Bottom Plate = 90 x 45 F5 Top Plate = 90 x 45 F5 Top Plate = 90 x 70 F5

350 Calculating Door Heights
On Concrete Slab Using a standard 2040mm x 820mm Allow 22mm for Carpet (17mm + 5mm) 2040 mm Door Height 2mm Clearance between Door & Jamb 20mm for Jamb 10mm Clearance between Jamb & Head 15mm Clearance between Jamb & Lintel Total = 2094mm Say 2100mm

351 Calculation of Door Width

352 Calculation of Window Check with manufacturer if windows are not on site Generally at same height of doors Check on elevations for window heights 15mm Clearance between Jamb & Lintel Allow 10mm under sill

353 Window Width Care should be taken when setting out to brick bond!
Client may want window to line up with internal fitting Client may want window dead center of room

354

355

356

357 Lintels

358

359

360

361

362 Construct Wall Frames Number Wall Frames Clock Wise Direction
Internal Walls Left to Right Top To Bottom

363 Setting Out Plates Confirm Dimensions of Slab/ Subfloor Select Suitable Timber & Cut to Length Tack Together Mark Appropriate ID Number on Plate Mark Required Studs – In Following Order End Studs Wall Intersections Openings Common Studs

364 Setting Out Plates If required prepare a storey rod with the appropriate markings (ie Horizontal & Vertical Bond) Set out position of window and doors studs remembering to allow for required jamb studs If required adjust position to match brickbond Set out Common Studs, Jack Studs at required spacing

365 Preparing Studs Use Storey Rod (Pattern Stud) to cut required studs
Mark and check out window and door studs

366 Fixing Wall Frames To Floors
AS

367 Wall Frame Assembly What are Advantages & Disadvantages of Prefabricated Wall Frames?

368 Assembling Wall Frames

369

370

371

372

373

374 Frame Erection

375

376

377

378

379 Nominal Fixings For Bottom Plates AS 1684.2

380

381

382

383


Download ppt "Construct Wall Framing"

Similar presentations


Ads by Google