Presentation is loading. Please wait.

Selecting A FoamPro System. 153 Class A foam concentrates –NFPA 1150 or US Forest Service Approved Class B foam concentrates –Use of a lower % foam concentrate.

Similar presentations


Presentation on theme: "Selecting A FoamPro System. 153 Class A foam concentrates –NFPA 1150 or US Forest Service Approved Class B foam concentrates –Use of a lower % foam concentrate."— Presentation transcript:

1 Selecting A FoamPro System

2 153 Class A foam concentrates –NFPA 1150 or US Forest Service Approved Class B foam concentrates –Use of a lower % foam concentrate will increase the discharge capabilities; i.e., 1%x3% versus 3%x6%. –AFFF –AR-AFFF (Viscosity considerations) –Control at each discharge Emulsifiers –Viscosity considerations What Type(s) Of Foam Concentrate Do You Want To Proportion?

3 154 What Are Water/Foam Flow Requirements? What discharges require foam solution? –Pre-connected hand lines, trash lines, etc. –2-1/2” and/or larger discharge(s) –Deck gun or aerial waterway (secondary feed) What are min. & max. GPM requirements of solution? What are min. & max concentrate levels? Properly size proportioner, main waterway check valve and flowmeter

4 155 Class B Foam Sizing Considerations Performance expectations NFPA standards Storage requirements (On and off vehicle) Logistical requirements Concentrate proportioning rates Control at each discharge (AccuMax single or multi-point injection)

5 156 Gallons per minute of foam concentrate required Sizing The Proportioner

6 157 Class A Example Flow requirements –Maximum: One deck gun 500 gpm –Minimum: One 1-1/2” 35 gpm (mop up) Concentrate level requirements –Maximum 1.0% (exposure protection) –Minimum 0.3% (initial attack) Calculate concentrate requirements –Maximum: 500 gpm x 1.0% = 5 gpm –Minimum: 35 gpm x 0.3% =.105 gpm Choose pump and flowmeter from charts

7 158 Fuel Hydrocarbon Polar Solvents Foam Type AFFF or FFFP AR/AFFF Application.10 gpm/ft 2 @ 1%.10 to.20 gpm/ft 2 @ 3% Rate Formula or 3% or 6% Spill Area 50 x 50 = 2500 sq.ft. Critical 2500 2500 Application Rate x.10 gpm/ft 2 x.17 gpm/ft 2 250 gpm 425 gpm Total Foam 250 gpm 425 gpm Concentrate x 15 min x.01 = 37.5 x 15 min x.03 = 191 on Scene or x.03 = 112 or x.06 = 382 Class B Foam Application Rates NFPA 11 or Manufacturers Rate

8 159 The FoamPro Product Line Model Capacity (Class A foam only) 1600 0.1-1.7 gpm 1601 0.1-1.1 gpm (Class A and/or B foam) 2001 0.01-2.6 gpm 2002 0.01-5.0 gpm 3012 0.1-12.0 gpm Maximum operating pressure 400 psi Model Capacity 3020 4.0 - 20.0 gpm 3040 4.0 - 40.0 gpm 3060 4.0 - 60.0 gpm 3090 6.0 - 90.0 gpm 3150 6.0-150.0 gpm 3300 10.0-300.0 gpm Dual pump option available for flows below 3000 series minimums Maximum operating pressure 250 psi

9 Product Lineup Class A Single Point Injection

10 161 FoamPro 1600 Series Ideal applications: –Brush rigs/skid units –Fast attack vehicles –Municipal apparatus –Retrofits –Compressed Air Foam Systems Treats up to: –340 gpm @ 0.5% –170 gpm @ 1.0%

11 Product Lineup Class A And/Or B Single Point Injection

12 163 FoamPro 2000 Series Ideal applications: –Municipal pumpers –Wildland pumpers –Marine and shipboard –Dual foam systems –Compressed Air Foam Systems Treats up to: –1000 gpm @ 0.5% –500 gpm @ 1.0%

13 164 Capabilities Of A 5.0 GPM System Class A Attack Capability % SolutionAttack Capability 0.2%2,000 GPM200,000 cu. ft. 0.5%1,000 GPM100,000 cu. ft. 1.0%500 GPM50,000 cu. ft. Solution flow and critical application rate using the Iowa formula

14 165 Capabilities Of A 5.0 GPM System Class B Attack Capability % SolutionAttack Capability 1%500 GPM4,980 sq. ft. 3%166 GPM1,660 sq. ft. 6%87 GPM830 sq. ft. Solution flow and critical application rate on Hydrocarbon @ 0.10gpm / sq ft

15 166 FoamPro Model 3012 Ideal applications: –Municipal pumpers –Wildland pumpers –Marine and shipboard –Dual foam systems –Compressed Air Foam Systems Treats up to: –2400 gpm @ 0.5% –1200 gpm @ 1.0%

16 167 Capabilities Of A 12.0 GPM System Class A Attack Capability % SolutionAttack Capability 0.2%6,000 GPM600,000 cu. ft. 0.5%2,400 GPM240,000 cu. ft. 1.0%1,200 GPM120,000 cu. ft. Solution flow and critical application rate using the Iowa formula

17 168 Capabilities Of A 12.0 GPM System Class B Attack Capability % SolutionAttack Capability 1.0%1,200 GPM12,000 sq. ft. 3.0%400 GPM4,000 sq. ft. 6.0%200 GPM2,000 sq. ft. Solution flow and critical application rate on Hydrocarbon @ 0.10 gpm / sq ft

18 AccuMax High Flow Industrial Systems

19 170 AccuMax Single Point Systems Ideal applications: –Industrial –Municipal pumpers –Airport rescue –Aerial apparatus –Compressed Air Foam Systems Treats up to: –10,000 gpm @ 3.0% –5,000 gpm @ 6.0%

20 171 Water Tank Check Valves Water Pump Multiple Discharges Flowmeter Foam Tank Line Strainer Digital Display Control AccuMax Single Point Injection

21 172 Size Max Accuracy Max Operating Tee Flow Range Flow Range 1-1/2x1" 5 - 110 gpm 3 - 145 gpm 1-1/2" 10 - 320 gpm 3 - 380 gpm 2" 15 - 520 gpm 5 - 625 gpm 2-1/2" 20 - 750 gpm 8 - 900 gpm 3" 30 - 1150 gpm 12 -1380 gpm 4" 55 - 1980 gpm 20 - 2380 gpm 6" ** 70 - 2800 gpm 30 - 3300 gpm 8" ** 120 - 4800 gpm 50 - 5600 gpm ** Electromagnetic flowmeter Determine Flowmeter Requirements

22 173 AccuMax Multi-Point Systems Microprocessor Control –On-demand multi-point foam injection at each discharge –Unmatched accuracy across full performance range Edwards Rotary Gear Pumps –40, 60, 90, 120, 150 & 300 GPM Models –All bronze construction Use Multiple Foam Sources –Foam tank or outboard pickup

23 174 Superior Performance –No flow restrictions –Not affected by external factors Calibration And Testing –Easy, fast, reuse the foam Applications Include: –Industrial Apparatus, Marine AccuMax Multi-Point Systems

24 175 Master Control –Provides total system control and performance information –Advanced self-diagnostics Individual Line Control –Each allows plain water or choice of injection percentage –Displays line performance along with water & foam totals Digital Displays –Simple push button control –Ultra-bright LED readout AccuMax Multi-Point Systems Operations

25 176 AccuMax Multi-Point Line Controller & Flowmeter Sizing

26 177 AccuMax Multi-Point Line Controller & Flowmeter Sizing

27 178 Plumbing Suggestions 1-1/2" or 2" Flowmeter tee –One or two preconnects and booster lines 2-1/2" or 3" Flowmeter tee –Two to three preconnects, 2-1/2" discharge and supplemental feed to deck gun 4" Flowmeter tee –Large waterway flow i.e. preconnects, multiple 2-1/2" discharges, deck guns and/or aerial waterway

28 179 FoamPro Options Manual Concentrate Management System * –Controls Tank A and Tank B with manual flush Electronic Concentrate Management system * –Controls Tank A and Tank B with automatic flush MultiFlo Interface * –Digital display of individual water flows, up to 4 discharges Dual Injection Selector * –Allows for two separate injection points Advanced Feature Controller * –Offers “Auto-On” Programming *Not Available on 1600 Series or AccuMax Multi-Point Systems

29 180 FoamPro Options (cont.) Poly Foam Tanks –5, 12 and 20 gallon Main Waterway Check Valves –1-1/2", 2", 2-1/2", 3", and 4" NPT, BSP, and Victalulic Stainless Steel Manifold –1-1/2", 2", 2-1/2", 3", and 4" Victaulic Solid State Contactor –Offers higher surge protection than solenoids Remote Start/Stop Switch –Allows driver to activate for pump and roll operations System Placards –Schematic and rating

30 181 AccuMax Multi-Point Options Low Flow Manual Override Pressure Readout at Each Discharge High Pressure Injection (300 PSI) Hydraulic Pump Configurations

31 Product Lineup Refill Systems

32 183 Power-Fill Improved Safety –No injuries from climbing on top of vehicles or lifting foam containers Increased Efficiency –Accomplish task faster with fewer personnel Added Economy –Purchase concentrate in larger containers for less cost Two Models –Greater flexibility

33 184 D.C. Model On-Board System –Pre-plumbed for fast, easy operation Easy To Use –Microprocessor control –Push button activation –Automatic shut-off –Manual override Heavy Duty Pump –Up to 12 GPM –12 volt ½ hp motor –24 volt available –Excellent drafting –Handles all viscosities

34 185 A.C. Model Portable System –Easily moved to apparatus –Pre-plumbed piping Simple Operation –Full tank indicator –Momentary switch Heavy Duty Pump –Up to 18 GPM –110 volt ½ hp motor –Excellent drafting –GFI protected –Handles all viscosities

35 186 Some Friendly Advice Define your needs –Immediate –Life of the vehicle Thoroughly check out all of the systems being considered –What the system will and will not do –Check with those who have experience –Consult with more than one reliable source

36 187 A “Solution” For Every Application


Download ppt "Selecting A FoamPro System. 153 Class A foam concentrates –NFPA 1150 or US Forest Service Approved Class B foam concentrates –Use of a lower % foam concentrate."

Similar presentations


Ads by Google