Presentation is loading. Please wait.

Presentation is loading. Please wait.

BECSys5.

Similar presentations


Presentation on theme: "BECSys5."— Presentation transcript:

1 BECSys5

2 BECSys5 – new in 2008 Enhancements to Hardware
Individual relay commons C1+C2 together, C3, C4 110/220 VAC selection White LCD display

3 BECSys5 – new in 2008

4 BECSys5 – new in 2008 Programming Features
Amperometric Sensor support for Bromine Conductivity Input / TDS Control The BECSys5 can now be configured to accept a conductivity sensor All 4-20mA inputs are re-assignable based upon installed sensors Provides maximum flexibility in the use of the standard 4-20mA input channels Turbidity Reading Control Polymer Feed Surge Pit Monitoring - AutoFill Advanced AutoFill algorithm includes Overfill Delay setting Pressure/Vacuum Readings Filter Influent, Filter Effluent, Strainer Vacuum Used in TDH calculations; Alarms (High strainer vacuum alarm signals a dirty strainer) Enzyme (timed) feed Daily timed feed that operates like the enhanced sensor wash function Power Saver Incorporates a circulation pump schedule with the Alternate feed settings Vacuum Filter Support System now allows assignment of Vacuum Transducer to filter influent

5 Integral Ethernet

6 Integral Ethernet PC on-site access through LAN (Ethernet)
4 simultaneous connections per controller Easy WLAN (wireless) conversion Advanced Alarm Notification Sites that do not have a LAN Controller interlocks (next phase) Multiple BECSysBWs and BECSys7s interlock shared B/W pit BECSys5 and BECSysBW manage circ pump Phone Line sharing (next phase)

7 Existing Local Ethernet
Existing LAN BECSys7 BECSys for Windows Unlimited number of controllers can go on local Ethernet Each needs it’s own network drop BECSys for Windows BECSys5 BECSys for Windows BECSysBW

8 Phone Line Sharing BECSys7 BECSys5 BECSysBW Existing LAN Remote PC
BECSys for Windows One BECSys controller gets an Ethernet/Modem combo card, and have access to all BECSys controllers. BECSys5 BECSys for Windows BECSysBW

9 No Local Ethernet (LAN)
BECSys5 BECSysBW Remote PC Ethernet BECSys for Windows Any 2 BECSys5-BW-7 controllers can be linked together via Ethernet cable Circ pump interlock between 5 & BW Backwash pit interlock between BWs and 7s Remote access to both with 1 phone line Unlimited number of controllers can go on local Ethernet Each needs it’s own network drop

10 No LAN, > 2 controllers
Standard Hub Remote PC BECSys7 BECSys for Windows Unlimited number of controllers can go on local Ethernet Each needs it’s own network drop BECSys5 BECSysBW

11 Add local PC to hub BECSys7 BECSysBW BECSys5 Ethernet Switch Remote PC
BECSys for Windows Local PC Unlimited number of controllers can go on local Ethernet Each needs it’s own network drop BECSys for Windows BECSysBW BECSys5

12 Alarm Notification 8 “Recipients”
Text Message Fax Pager Enhanced Pager Alarm Notification/Callout features Pager Alarm Notification now uses 2 sets of phone numbers: Pager Service #: The pager service to call, and Callback #: The number to leave as a callback Alarm callout status display Added display of Current State to each Recipient’s Setup Menu

13 Alarm Notification Detailed Information Future Enhancements
System Type (BECSys7, BECSys5, etc.) Serial Number Location System ID All active alarms, including the date and time each alarm was triggered Future Enhancements Partial Status Report, including setpoints, alarm points, etc.

14 Email Alarm Notification

15 Email Alarm Notification

16 SMS Text Alarm Notification

17 BECSys5 – new in 2008 Advanced Recirculation Pump Features
VFD control algorithm Controls recirc pump to maintain desired flow rate Four manual and four scheduled turndowns Override setting for backwash Ramp up and ramp down settings Minimum output setting Total Dynamic Head (TDH) monitoring Monitors pump for proper operation Requires strainer vacuum and filter influent pressure transducer inputs TDH high and low alarms (can be disabled) Fireman Switch controls Ozone feed fireman switch timer Heater

18 BECSys VFD VFD BECSys BECS is focusing activity on the interaction of our Water Chemistry Systems with Variable Frequency Drives/Pumps

19 Water Chemistry – VFD Integration
Benefits of water chemistry/VFD Integration Piggy-backing Ease of Use Water Quality improvement Ongoing enhancement

20 Integration Benefits: Piggy-Backing
Convenience: We already have functions and features in place familiar to the aquatics industry Why establish duplicate, parallel, separate systems? Multiple systems to install, learn, maintain, support, etc. User Interface Data Logging Remote Access / PC Software Unified Alarm Notification and Setup How else will you set up remote alarm notification? And BECS is further innovating and developing Why not take advantage of these facilities, regardless of the manufacturer of the VFD?

21 Integration Benefits: Ease of Use
Water Chemistry controllers are customized to the aquatics application User Interface Terminology, Manuals, Wiring Diagrams, etc are all market-specific. More than piggy-backing: a VFD will be less intimidating if considered part of the water chemistry system Installation / Startup The most simple (and cost-effective) VFD will work Inputs can be brought into the BECSys controller system Intelligence built into the BECSys controller, so VFD need only run a very basic “slave” program

22 Integration Benefits: Ease of Use
Programming BECSys controller knows the difference between a circ pump and a feature pump Will know specific requirements of different feature pumps Water slide pump programming may differ from Lazy River Analysis Water quality readings graphed with pump readings pH, ORP, temperature… flow rate, TDH Alarms show together in Event Log Status Reports include water chemistry and pump info

23 Integration Benefits: Water Quality
Can we modify the pump rate to actively improve water quality? Filtration System support (BECSys7) Filter Backwash can adjust pump rate (even stop) to support particular BW requirements More sophisticated filtration opportunities will benefit from control integration Advanced control algorithms May adjust pump rate based upon water quality inputs Blended flow rate; real-time peak/off-peak flow rate determination, with daily minimum average rate. Europe already going here; North America may not be quite ready yet, but we will get there

24 Integration Benefits: Ongoing Development
BECS is committed to ongoing development of General Capabilities - networking, remote access, data analysis, etc. Specific VFD algorithms If integrated, advancements will include VFDs PC software improvements VFD algorithms – BECSys firmware release If separate… VFD reprogramming for new features? What about remote access?

25 Signet Flowmeter or psi sensor
BECSys VFD BECSys VFD Circulation Pump 4-20ma, relay Signet Flowmeter or psi sensor

26 BECSys VFD Control Features
Control of Circulation Pump flow rate or effluent filter pressure Specify set point and alarm points Backwash override Ramp up / Ramp down settings Minimum output (floor) setting Four Manual Turndowns Triggered through BECSys front panel Sets alternate settings for pre-determined period Rename: Race, Free swim, Cleaning… Four Scheduled Turndowns Programmed with day/week start/stop time Example: Night setting from 10:00PM – 6:00 AM Rename: Weeknight, Weekend night…

27 High-quality membrane sensor
Total Chlorine Sensor High-quality membrane sensor Not disposable; membrane & electrolyte are replaceable 0 – 20.0 ppm range Single-point recalibrations based on DPD test

28 Combined Chlorine Compliance Alarm Points Air Handling Systems
Combined chlorine on screen and in data logs Alarm Points Notify when combined chlorine too high Air Handling Systems Manage the amount of fresh (cold) air required

29 Combined Chlorine UV Control Breakpoint Chlorination
Manage UV system to reduce energy costs and prolong bulb life Breakpoint Chlorination Prevent formation of chloramines Adaptive chlorine setpoint Dynamically determine chlorine setpoint based upon combined chlorine levels