1 TECHNICAL TRAINING 2007

2 SELECTION SOFTWARE

3 Sample of Installation

4 These item will influence the piping layout and length of the design
Unit & Piping Selection Main Factors to consider during Piping Selection Location of equipment Indoor Unit Outdoor Unit Refnet & Distributor Joint These item will influence the piping layout and length of the design

5 Unit & Piping Selection
Some other factors to consider during Piping Selection Equivalent Piping Length Type of Joint for branches Outdoor capacity factor Piping length & height factor Refrigerant Pipe Specification

6 Equivalent Piping Calculation
Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow: Equivalent length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap

7 Restriction of Piping Length

8 Important Factor to Consider
Example: Outdoor Model : MDS100BR Pipe Diameter : mm Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = ( ) + (10 X 0.5) + (3 X 3.7) = m

9 Important Factor to Consider
Criteria 1 When the equivalent length is more than 90% of the maximal real length of the main tubing , the gas pipe need to be increase to one size bigger (diameter). Criteria 2 After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow: Expanded Equivalent Length = Equivalent length of main piping X equivalent length of the branch

10 Important Factor to Consider
Example: Maximum allow actual length for 10Hp is 125m Calculated Equivalent Length is 116.1m Ratio of Equivalent Length over Maximum allow Actual Length= 92.88% Equivalent length is more than 90% of the maximal real length. Hence the gas Pipe of MDS100BR need to change.

11 Unit & Piping Selection
Refrigerant Copper Pipe Specification : MDS-B

12 Important Factor to Consider
Example: Hence the gas Pipe of MDS100BR need to change from 28.6 mm to mm After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. Expanded Equivalent Length = Equivalent length of main piping X equivalent length of the branch Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = ( ) + (10 X 0.5) + (3 X 3.7) = m Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X Expanded Equivalent Length = m

13 Unit & Piping Selection
Type of Joint for branches Influence the piping layout design Outdoor capacity factor Influence by the design ambient temperature and indoor temperature Piping length & height factor Influence by the location of outdoor and the total piping length Refrigerant Pipe Specification Use to determine the branches diameter

14 Unit & Piping Selection
Selection of branch joint / distributors for MDS

15 Unit & Piping Selection
MDS-Y1~Y4 dimensional drawing

16 Unit & Piping Selection
MDS-Y6 dimensional drawing

17 Unit & Piping Selection
MDS-Y7 dimensional drawing

18 Unit & Piping Selection
MDS-C1 dimensional drawing

19 Unit & Piping Selection
MDS-C2~C3 dimensional drawing

20 Using Distribution Header may lead to imbalance refrigerant flow.
Unit & Piping Selection Caution Using Distribution Header may lead to imbalance refrigerant flow.

21 Allow Unit & Piping Selection
Connection Type of Refnet Joint/Distributors Allow Refnet Joint

22 Allow Unit & Piping Selection
Connection Type of Refnet Joint/Distributor Allow Distributor

23 Allow Unit & Piping Selection
Connection Type of Refnet Joint/Distributors Allow Refnet Joint Distributor

24 Not Allow Unit & Piping Selection
Connection Type of Refnet Joint/Distributors Not Allow Refnet Joint Distributor

25 Unit & Piping Selection
Cooling Capacity Correction Factor

26 Unit & Piping Selection
Heating Capacity Correction Factor

27 Unit & Piping Selection
Cooling Capacity Correction Factor Cooling cap. factor

28 Unit & Piping Selection
Heating Capacity Correction Factor

29 Unit & Piping Selection
Refrigerant Pipe Specification : MDS-A

30 Unit & Piping Selection
Refrigerant Pipe Specification : MDS-B

31 Unit & Piping Selection
Example C A B D E F Building Type: Bungalow

32 Unit & Piping Selection
Example Requirement Cooling only model Ambient temperature : 40.0 °C Indoor temperature : 21.0 °C Other Information Piping length:70m Height between I/O:4m Outdoor Unit located below indoors

33 Unit & Piping Selection
Indoor Requirement

34 Unit & Piping Selection
Example Total Indoor capacity is 32.3 kW

35 Unit & Piping Selection
Example Selection Criteria Total Indoor capacity must be range between 50% ~ 120% of the outdoor capacity. We recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor capacity

36 Unit & Piping Selection
Example Selected Outdoor : MDS120B Cooling Capacity : 32.5kW Comply to selection criteria

37 Unit & Piping Selection
Example Selected Outdoor and Indoor Model

38 Unit & Piping Selection
Example Outdoor Capacity factor Cooling only model Ambient temperature : 40.0 °C Indoor temperature : 22.0 °C 1.03

39 Unit & Piping Selection
Example Piping length & height factor Piping length:70m Height between I/O:4m Outdoor Unit located below indoors 91%

40 Unit & Piping Selection
Example Total Capacity = Outdoor Capacity X Outdoor Capacity Factor X Piping length & height Factor = 32.5 kW X 1.03 X 94% = kW Comply to requirement

41 Unit & Piping Selection
Example C A B D E F Building Type: Bungalow

42 Unit & Piping Selection
Example Selection pipe diameter MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW

43 Unit & Piping Selection
Refrigerant Pipe Specification : MDS-B

44 Unit & Piping Selection
Example Downstream capacity Point A A-B-C : 14.9 kW A-D-E : 17.4 kW Point B B-C : 8.4 kW D-E : 8.4 kW Main pipe diameter : ø 15.88mm / ø 28.6mm MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW

45 Unit & Piping Selection
Refrigerant Pipe Specification : MDS-B Point A A-B-C : 14.9 kW A-D-E : 17.4 kW

46 Unit & Piping Selection
Example Main pipe diameter : ø 15.88mm / ø 28.6mm A-B diameter : ø 9.52mm / ø 19.05mm MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G A-D diameter : ø 12.7mm / ø 25.4mm WMD 20G 2.8 kW 9.0 kW 5.6 kW

47 Unit & Piping Selection
Example Point B B-C : 8.4 kW B-CCD25C : 6.5 kW MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW

48 Unit & Piping Selection
Refrigerant Pipe Specification : MDS-B Point B B-C : 8.4 kW B-CCD25C : 6.5 kW

49 Unit & Piping Selection
Example A-B: ø 9.52 / ø 19.05 B-C: ø 9.52 / ø15.88 B-CCD25C: ø 9.52 / ø15.88 MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW

50 Unit & Piping Selection
Example

51 Unit & Piping Selection
Example Main Pipe: ø / ø 28.6 A-B: ø 9.52 / ø19.05 B-C: ø 9.52 / ø15.88 MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 20G 5.6 kW WMD 10G 2.8 kW 9.0 kW A-D: ø12.7 / ø25.4 D-E: ø9.52 / ø15.88

52 Unit & Piping Selection
Example All unit in mm Selection of branch A-B diameter : ø 9.52 / ø 19.05 Main Pipe diameter : ø / ø 28.6 A Select the refnet joint of point A A (liquid) : MDS-Y2 A (gas) : MDS-Y1 A-D diameter : ø 12.7 / ø 25.4

53 Unit & Piping Selection
Example Main Pipe: ø / ø 28.6 A-B: ø 9.52 / ø19.05 B-C: ø 9.52 / ø15.88 MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW A-D: ø12.7 / ø25.4 D-E: ø9.52 / ø15.88

54 Unit & Piping Selection
Example MDS120B A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW 6.5 kW D E CKD 30A WMD 10G WMD 20G 2.8 kW 9.0 kW 5.6 kW

55 Unit & Piping Selection
Example Using liquid tube length to calculate required refrigerant. Add in refrigerant. Formula: G = ∑ Li* Gi G : Refrigerant charge amount Li : The each section of liquid tube length in all (m) Gi : Charge amount per length(g/m)

56 Unit & Piping Selection
Total Piping Length 15.88mm – 10m 12.7mm – 25m 9.52mm – 21m 6.35mm – 14m Example ø (10m) ø 9.52 (5m) ø 9.52 (2m) ø 9.52 (4m) ø 6.35 (2m) MDS120B ø 6.35 (5m) A B C WMD 20G CCD 25C WMD 10G 5.6 kW 2.8 kW ø 12.7 (25m) 6.5 kW ø 6.35 (2m) D E ø 6.35 (5m) ø 9.52 (5m) CKD 30A WMD 20G WMD 10G ø 9.52 (5m) 9.0 kW 5.6 kW 2.8 kW

57 Unit & Piping Selection
Example Total Piping Length 15.88mm – 10m 12.7mm – 25m 9.52mm – 21m 6.35mm – 14m Additional charge amount : = ∑ Li* Gi = (Piping Length for 15.88mm X Refrigerant Charge Amount) + (Piping Length for 12.7mm X Refrigerant Charge Amount) + (Piping Length for 9.52mm X Refrigerant Charge Amount) + (Piping Length for 6.35mm X Refrigerant Charge Amount) = (10 X 180) + (25 x 120) + (21 x 80) + (14 x 50) = 7180 g Liquid tube diameter (mm) 6.35 9.52 12.7 15.88 Refrigerant charge amount (g/m) 50 80 120 180

58 Unit & Piping Selection
Electronic Expansion Valve EXV Box

59 Unit & Piping Selection
Electronic Expansion Valve 2 units 2 units 1 unit 1 unit

60 Unit & Piping Selection

61 Software Demo