Download presentation
Presentation is loading. Please wait.
1
EE6352 - Electrical Engg & Instrumentation
Unit 2- Transformer S. Arulmozhi, AP/EE 11/27/2018
2
Syllabus TRANSFORMER 9 Introduction – Single phase transformer construction and principle of operation – EMF equation of transformer-Transformer no–load phasor diagram –– Transformer on–load phasor diagram – Equivalent circuit of transformer – Regulation of transformer –Transformer losses and efficiency-All day efficiency –auto transformers. 11/27/2018
3
Transformer Transformer is a static device which transfers electric power from one circuit to another without changing its frequency The principle of operation of a transformer depends upon Faraday's Law of Electomagnetic Induction. Actually mutual inductance between 2 or more windings is responsible for transformation action in an electrical transformer. According to Faraday's Law, “Rate of change of flux linkages with respect to time is directly proportional to the induced EMF in a conductor or a coil”. e = MdI/dt or N.dϕ / dt 11/27/2018
4
Transformer 11/27/2018
5
Primary coil and Secondary coil
Consists of two inductive coils which are electrically seperate but magnetically linked through a path of low reluctance. Primary coil and Secondary coil 11/27/2018
6
transfers electric power from one circuit to another
Transformer - transfers electric power from one circuit to another does so without change of frequency accomplishes this by electromagnetic induction where the two electric circuits are linked by mutual induction. 11/27/2018
7
Types of transformer Based on terminal voltage, Step-up transformer
Step down transformer Based on supply voltage, Single phase transformer Three phase transformer Based on construction, Core type transformer Shell type transformer Spiral type or wound core type transformer (spirakore) Based on type of cooling, Oil-filled self cooled Oil-filled water cooled Air blast type 11/27/2018
8
Core Type Transformer The windings surround a considerable part of the core It is a single magnetic circuit Rectangular in shape having 2 limbs The coils used are of cylindrical type. The coils are wound in helical layers with different layers insulated from each other by paper or micaor cloth. The core is made up of large number of thin laminations. LV winding is placed nearest to the core with interleaved structure. 11/27/2018
9
Lecture - 2 Review of Lecture 1 Construction & Types of Transformer
EMF equation of transformer Summary 11/27/2018
10
Review - Transformers operate only on AC
Frequency of DC supply = 0Hz Inductive reactance XL = 2πfL The effective impedance of the winding -very low = resistance of the copper used. Winding draws very high current from the DC supply (I = V/R) Overheat & Burnout of windings 11/27/2018
11
Construction - Core Core is either square or rectangular in size
The vertical portion in which the coils are wound are called the limb and carries the windings The horizontal portion is called the yoke which carries the flux produced by one winding to another.
12
Core Core is made up of laminations to prevent eddy current losses.
Laminations are made up of silicon steel of 0.3 to 0.5mm thick Laminations are insulated from each other by insulating materials like varnish. Laminations are overlapped to avoid airgap at the joints. 'L', 'E' , 'I' or 'T' shaped laminations are used.
13
Laminations In core type transformers, the steel core laminations are in the shape of 'L' , and these laminations are placed one above the other alternatively.
14
Laminations In shell type transformers, the steel core laminations are in the shape of 'E and I' and placed similar to that of core type.
16
Types of laminations
18
Windings Transformer windings are made of solid copper or aluminium strip conductors. The coils used are wound on the limbs and are insulated from each other. It carries the current and produces the flux necessary for the functioning of the transformer.
19
Core type Windings are wrapped around two sides of a laminated square core. 11/27/2018
20
Shell type transformer
The core surrounds a considerable portion of the windings. It is a double magnetic circuit The core has 3 limbs. The coils used are multilayered disc type or sandwich coils. The core is laminated. All the joints at alternate layers are staggered to avoid narrow airgaps at the joints. Such joints are called as overlapped or imbricated joints. Windings are wrapped around the center leg of a laminated core. 11/27/2018
21
Shell type - sandwich coil structure
HV winding lies between two LV windings Controls leakage 11/27/2018
22
Sectional view of transformer
Windings are wrapped around the center leg of a laminated core. Windings are wrapped around two sides of a laminated square core. 11/27/2018
23
Comparison between Core & Shell Type
Description Core Type Shell Type Construction Easy to assemble & Dismantle Complex Mechanical Strength Low High Leakage reactance Higher Smaller Cooling Better cooling of Winding Better cooling of Core Repair Easy Hard Applications High Voltage & Low output Low Voltages & Large Output 23 11/27/2018
24
Berry type transformer
It has distributed magnetic circuit The core type is like the spikes of a wheel. The transformers are generally placed in tightly fitted sheet metal tanks. Tanks are made up of high quality steel plate, formed and welded into a rigid structure. The tanks are filled with special insulating oil. All the joints are painted with light blue chalk solution disclosing even a minute leak. 11/27/2018
25
Symbol for ideal transformer
Ideal Transformers Zero leakage flux: -Fluxes produced by the primary and secondary currents are confined within the core The windings have no resistance: - Induced voltages equal applied voltages The core has infinite permeability - Reluctance of the core is zero - Negligible current is required to establish magnetic flux Loss-less magnetic core - No hysteresis or eddy currents NP : NS VP VS Primary Secondary Symbol for ideal transformer 11/27/2018
26
Ideal transformer V1 – supply voltage ; I1- noload input current ;
V2- output voltgae; I2- output current Im- magnetising current; E1-self induced emf ; E2- mutually induced emf 11/27/2018
27
Transformer Equations
Using Faraday’s law, expressions for the primary and secondary voltages is as follows. Dividing the above equations we get, Assuming that there is no power loss, K - transformation ratio 11/27/2018
28
EMF Equation of a transformer
Let N1= No. of primary turns N2= No. of secondary turns φm= Maximum flux density in transformer core in Weber =BmA where Bm-> flux density in the transformer core A -> cross sectional Area of the transformer In an EMF equation, flux increases from its zero value to maximum value Фm in one quarter of cycle Average rate of change of flux = Фm/(1/4f)=4f Фm wb/sec The average value of emf induced / turn = 4f Фm If flux Фm varies sinusoid ally, then R.M.S value of induced EMF is obtained by multiplying the average value with form factor. ……(1) ……(2)
29
EMF Equation of a transformer -contd
Form factor=R.M.S value/Average value = = (for sine wave) R.M.S value of EMF/turn=1.11*4fФm volts Now, R.M.S value of the induced EMF in the whole primary winding = (induced EMF/turn)*No of primary turns. E1 = 4.44fN1Фm llly, E2 = 4.44fN2Фm ……(3) ……(4) ……(5) ……(6)
30
EMF equation of transformer - contd
If ip is sinusoidal, the flux produced also sinusoidal, i.e = m sin 2ft ……(7) therefore v1 = N12fmcos 2ft = N12fmsin (2ft + /2) ……(8) The peak value = Vpm = N12fm and v1 is leading the flux by p/2. ……(9) The rms value ……(10) 11/27/2018
31
Summary Construction - Core & Shell type EMF equation of a transformer
Queries???????? 11/27/2018
32
Power Transmission (CONTENT BEYOND SYLLABUS)
Transformers play a key role in the transmission of electric power. 11/27/2018
33
Transformer with conservator and breather(CONTENT BEYOND SYLLABUS)
11/27/2018
34
Parts of a transformer (CONTENT BEYOND SYLLABUS)
Conservator Oil is stored in the conservator It prevents the oil from moisture contact in air during the expansion and contraction. Breather It is a device which contains silica gel crystals. The gel absorbs the moisture in the atmosphere when the oil expands and contracts. Explosive Vent It bursts when pressure inside the transformer becomes excessive and protects the transformer from damage. Transformer Tank filled with transformer Oil
35
Transformer-No load condition
36
Phasor diagram: Transformer on No-load
11/27/2018
37
Transformer – On load condition
38
Transformer on load assuming no voltage drop in the winding
Fig shows the Phasor diagram of a transformer on load by assuming No voltage drop in the winding Equal no. of primary and secondary turns 11/27/2018
39
Transformer on load Fig. a: Ideal transformer on load
Fig. b: Main flux and leakage flux in a transformer 11/27/2018
40
Phasor diagram of transformer with UPF load
11/27/2018
41
Phasor diagram of transformer with lagging p.f load
11/27/2018
42
Phasor diagram of transformer with leading p.f load
11/27/2018
43
Equivalent circuit of a transformer
No load equivalent circuit: 11/27/2018
44
Equivalent circuit parameters referred to primary and secondary sides respectively
11/27/2018
45
Contd., The effect of circuit parameters shouldn’t be changed while transferring the parameters from one side to another side It can be proved that a resistance of R2 in sec. is equivalent to R2/k2 will be denoted as R2’(ie. Equivalent sec. resistance w.r.t primary) which would have caused the same loss as R2 in secondary, 11/27/2018
46
Transferring secondary parameters to primary side
11/27/2018
47
Equivalent circuit referred to secondary side
Transferring primary side parameters to secondary side Similarly exciting circuit parameters are also transferred to secondary as Ro’ and Xo’ 11/27/2018
48
equivalent circuit w.r.t primary
where 11/27/2018
49
Approximate equivalent circuit
Since the noload current is 1% of the full load current, the nolad circuit can be neglected 11/27/2018
50
Transformer Tests The performance of a transformer can be calculated on the basis of equivalent circuit The four main parameters of equivalent circuit are: - R01 as referred to primary (or secondary R02) - the equivalent leakage reactance X01 as referred to primary (or secondary X02) - Magnetising susceptance B0 ( or reactance X0) - core loss conductance G0 (or resistance R0) The above constants can be easily determined by two tests - Oper circuit test (O.C test / No load test) - Short circuit test (S.C test/Impedance test) These tests are economical and convenient - these tests furnish the result without actually loading the transformer 11/27/2018
51
Open-circuit Test In Open Circuit Test the transformer’s secondary winding is open-circuited, and its primary winding is connected to a full-rated line voltage. Usually conducted on H.V side To find (i) No load loss or core loss (ii) No load current Io which is helpful in finding Go(or Ro ) and Bo (or Xo ) 11/27/2018
52
Short-circuit Test In Short Circuit Test the secondary terminals are short circuited, and the primary terminals are connected to a fairly low-voltage source The input voltage is adjusted until the current in the short circuited windings is equal to its rated value. The input voltage, current and power is measured. Usually conducted on L.V side To find (i) Full load copper loss – to pre determine the efficiency (ii) Z01 or Z02; X01 or X02; R01 or R02 - to predetermine the voltage regulation 11/27/2018
53
Contd… 11/27/2018
54
Transformer Voltage Regulation and Efficiency
The output voltage of a transformer varies with the load even if the input voltage remains constant. This is because a real transformer has series impedance within it. Full load Voltage Regulation is a quantity that compares the output voltage at no load with the output voltage at full load, defined by this equation: Ideal transformer, VR = 0%. 11/27/2018
55
Voltage regulation of Transformer
recall Secondary voltage on no-load V2 is a secondary terminal voltage on full load Substitute we have 11/27/2018
56
Transformer Phasor Diagram
To determine the voltage regulation of a transformer, it is necessary understand the voltage drops within it. 11/27/2018 56
57
Transformer Phasor Diagram
Ignoring the excitation of the branch (since the current flow through the branch is considered to be small), more consideration is given to the series impedances (Req +jXeq). Voltage Regulation depends on magnitude of the series impedance and the phase angle of the current flowing through the transformer. Phasor diagrams will determine the effects of these factors on the voltage regulation. A phasor diagram consist of current and voltage vectors. Assume that the reference phasor is the secondary voltage, VS. Therefore the reference phasor will have 0 degrees in terms of angle. Based upon the equivalent circuit, apply Kirchoff Voltage Law, 11/27/2018 57
58
Transformer Phasor Diagram
For lagging loads, VP / a > VS so the voltage regulation with lagging loads is > 0. When the power factor is unity, VS is lower than VP so VR > 0. 11/27/2018 58
59
Transformer Phasor Diagram
For lagging loads, the vertical components of Req and Xeq will partially cancel each other. Due to that, the angle of VP/a will be very small, hence we can assume that VP/k is horizontal. Therefore the approximation will be as follows: 11/27/2018
60
Transformer Phasor Diagram
With a leading power factor, VS is higher than the referred VP so VR < 0 11/27/2018 60
61
Voltage regulation Lagging P.F. VP/ k > VS V.R. > 0 Unity P.F.
V.R. >0 (smaller) Leading P.F. VS > VP/ k V.R. < 0 11/27/2018
62
Voltage regulation for Lagging Power Factor
63
Voltage Regulation for Leading Power Factor
64
Formula: voltage regulation
11/27/2018
65
Transformer Efficiency
Transformer efficiency is defined as (applies to motors, generators and transformers): Types of losses incurred in a transformer: Copper I2R losses Hysteresis losses Eddy current losses Therefore, for a transformer, efficiency may be calculated using the following: 11/27/2018
66
Losses in a transformer
Core or Iron loss: Copper loss: 11/27/2018
67
Condition for maximum efficiency
11/27/2018
68
Contd., The load at which the two losses are equal = 11/27/2018
69
AUTO TRANSFORMER At some occasions it is desirable to change voltage level only by a small amount i.e. may need to increase voltage from 110 to 120 V or from 13.2 to 13.8 kV This may be due to small increase in voltage drop that occur in a power system with long lines In such cases it is very expensive to hire a two full winding transformer, however a special transformer called: ”auto-transformer” can be used
70
AUTO TRANSFORMER Diagram of a step-up auto-transformer shown in figure below: C: common, SE: series
71
AUTO TRANSFORMER A step-down auto-transformer : IH=ISE IL=ISE+IC
72
AUTO TRANSFORMER In step-up autotransformer: VC / VSE = NC / NSE (1)
NC IC = NSE ISE (2) voltages in coils are related to terminal voltages as follows: VL=VC (3) VH=VC+VSE (4) current in coils are related to terminal currents: IL=IC+ISE (5) IH=ISE (6)
73
AUTO TRANSFORMER Voltage & Current Relations in Autotransformer
VH=VC+VSE since VC/VSE=NC/NSE VH=VC+ NSE/NC . VC Noting that: VL=VC VH=VL+ NSE/NC . VL= (NSE+NC)/NC . VL VL / VH = NC / (NSE+NC) (7) Current relations: IL=IC+ISE employing Eq.(2) IC=(NSE / NC)ISE IL= (NSE / NC)ISE + ISE, since ISE=IH IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IH IL / IH = (NSE + NC)/NC (8)
74
AUTO TRANSFORMER Apparent Power Rating Advantage of Autotransformer Note : not all power transferring from primary to secondary in autotransformer pass through windings Therefore if a conventional transformer be reconnected as an autotransformer, it can handle much more power than its original rating The input apparent power to the step-up autotransformer is : Sin=VLIL And the output apparent power is: Sout=VH IH
75
AUTO TRANSFORMER And : Sin=Sout=SIO
Apparent power of transformer windings: SW= VCIC=VSE ISE This apparent power can be reformulated: SW= VCIC=VL(IL-IH) =VLIL-VLIH employing Eq.(8) SW= VLIL-VLIL NC/(NSE+NC) =VLIL [(NSE+NC)-NC] /(NSE+NC)=SIO NSE /(NSE+NC) SIO / SW = (NSE+NC) / NSE (9)
76
AUTO TRANSFORMER Internal Impedance of an Autotransformer
Another disadvantage: effective per unit impedance of an autotransformer w.r.t. the related conventional transformer is the reciprocal of power advantage This is a disadvantage where the series impedance is required to limit current flows during power system faults (S.C.)
77
Example of Variable Auto-Transformer
78
All day efficiency All day efficiency is defined as the ratio of total energy output of transformer to thetotal energy input in 24 hours. All day efficiency is always less than the commercial efficiency 11/27/2018
79
Transformer Voltage Regulation and Efficiency - Tutorial
(a) Find the equivalent circuit referred to H.V. side (b) Find the equivalent circuit referred to L. V. side (c) Calculate the full-load voltage regulation at 0.8 lagging PF, 1.0 PF, and at 0.8 leading PF (d) Find the efficiency at full load with PF 0.8 lagging SOLUTION: Open circuit impedance angle is: Excitation admittance is:
80
Transformer Voltage Regulation and Efficiency
Impedance of excitation branch referred to primary: Short Circuit Impedance angle: Equivalent series Impedance: Req=4.45 Ω, Xeq=6.45 Ω
81
Transformer Voltage Regulation and Efficiency
The equivalent circuits shown below:
82
Transformer Voltage Regulation and Efficiency
(b) To find eq. cct. Referred to L.V. side, impedances divided by a²=NP/NS=10 RC=1050 Ω , XM=110 Ω Req= Ω , Xeq= Ω (c) full load current on secondary side: IS,rated=Srated/ VS,rated=15000/230 =65.2 A To determine V.R., VP/ a is needed VP/a = VS + Req IS + j Xeq IS , and: IS=65.2/_-36.9◦ A , at PF=0.8 lagging
83
Transformer Voltage Regulation and Efficiency
Therefore: VP / a = V.R.=( )/230 x 100 %=2.1 % for 0.8 lagging At PF=0.8 leading IS=65.2/_36.9◦ A
84
Transformer Voltage Regulation and Efficiency
V.R. = ( )/230 x 100%= % At PF=1.0 , IS= 65.2 /_0◦ A VP/a= V.R. = ( )/230 x 100% = 1.28 % for PF=1
85
Transformer Voltage Regulation and Efficiency
Example: Phasor Diagrams …
86
Transformer Voltage Regulation and Efficiency
(d) to plot V.R. as a function of load is by repeating the calculations of part “c” for many different loads using MATLAB
87
Transformer Voltage Regulation and Efficiency
(e) Efficiency of Transformer: - Copper losses: PCu=(IS)²Req =(65.2)² (0.0445)=189 W - Core losses: PCore= (VP/a)² / RC= (234.85)² / 1050=52.5 W output power: Pout=VSIS cosθ=230x65.2xcos36.9◦=12000 W η= VSIS cosθ / [PCu+PCore+VSIS cosθ] x 100%= 12000/ [ ] = %
Similar presentations
© 2025 SlidePlayer.com Inc.
All rights reserved.