Presentation is loading. Please wait.

Presentation is loading. Please wait.

Mikkelin university of applied sciences Building services

Similar presentations


Presentation on theme: "Mikkelin university of applied sciences Building services"— Presentation transcript:

1 Mikkelin university of applied sciences Building services
COOLING OF BUILDINGS Kuva: Pemco Mikkelin university of applied sciences Building services Principal lecturer (TkL) Aki Valkeapää Martti Veuro, senior lecturer Aki Valkeapää

2 COOLING OF BUILDINGS Cooling of buildings is based on atleast still compressor cycle where the cooling medium / refrigerant is evaporated (heat transfer from surroundings to the refrigerant) and condensed (heat transfer from refrigerant to the surroundings, heat is rejected) in turn. This cycle and the required pressure difference between evaporator (low pressure) and condenser (high pressure) is maintained by the compressor. Kuva: Danfoss Aki Valkeapää

3 COOLING OF BUILDINGS Kuvat: Danfoss, Fincoil, Coiltech 20.11.2018
Aki Valkeapää

4 COOLING OF BUILDINGS Condensing pressure and
temperature in the condenser Amount of rejected heat by condensation of refrigerant Saturated liquid Pressure difference across expansion valve Saturated vapour Amount of heat for evaporation of refrigerant Evaporation pressure and pressure Reference: Aittomäki 2008 Aki Valkeapää

5 L L+V V C B A COOLING OF BUILDINGS
COP2 (EER) = HEAT NEEDED /HEAT REJECTED = (B-C)/(A-B) Aki Valkeapää

6 - ODP(ozone depletion potential) - GWP (global warming potential)
COOLING OF BUILDINGS refrigerants - ODP(ozone depletion potential) - GWP (global warming potential) - CFC – substances (Chloro-Fluoro-Carbon), e.g. R12 (ODP=1, GWP=8100) - HCFC -substances, e.g. R22 (ODP=0,055, GWP=1500) -HFC -substances, R134a, R404A, R407C, R410A (ODP=0, GWP=1300…3260) - ammonia (ODP=0, GWP=0) - CO2 carbon dioxide (ODP=0, GWP=1) - HC-refrigerants, e.g. isobutane R600a is common in household refrigerators (fridges) Aki Valkeapää

7 Mechanical thermostatic expansion valve
COOLING OF BUILDINGS Mechanical thermostatic expansion valve Lähde:Danfoss Aki Valkeapää

8 The future solutions of cooling do not seem to be simpler than today
COOLING OF BUILDINGS Compressor cooling can be realized as a centralised or decentralised system Centralised or decentralised cooling system can be executed either with a direct system or with an indirect system Centralised or decentralised cooling system can be executed either with a direct condensing or with an indirect condensing Rooms / spaces can be cooled / air conditioned with supply air or with chilled water or both of them can be used at the same time Addition to those also there is systems like district cooling, night ventilation, utilization of ground or water “cold”, heat pumps,... The future solutions of cooling do not seem to be simpler than today Aki Valkeapää

9 AIR CONDITIONING SYSTEM
ALTERNATIVES COOLING SYSTEM direct cooling – direct condensing direct cooling – indirect condensing indirect cooling – direct condensing indirect cooling – indirect condensing indirect cooling – indirect condensing + free cooling indirect cooling – direct condensing + free cooling indirect cooling – indirect condensing + gliding / floating condensing pressure + free cooling (?) AIR CONDITIONING SYSTEM cooling with supply air cooling with chilled water (and supply air) cooling with circulating air Aki Valkeapää

10 DECENTRALISED DIRECT COOLING
Compressor +condenser evaporator Figure: Koja Figure: Koja vakioilmastointikone Direct condensing vakioilmastointikone Indirect condensing (fluid) split-unit (refrigerant cycle) Reference: Kaappola 1996 Aki Valkeapää

11 (containing refrigerant)
DIRECT COOLING Direct cooling coil (containing refrigerant) supply air Expansion valve Liquid refrigerant from the liquid tank or condenser discharge / hot gas to the condenser compressor Aki Valkeapää

12 heat recovery finned coil (condenser) exit air expansion valve
CENTRALISED DIRECT COOLING (cooling machine in the air handling unit AHU) finned coil (condenser) Scroll-compressor exit air heat recovery expansion valve supply air direct cooling coil (evaporator) Aki Valkeapää

13 CENTRALISED DIRECT COOLING
compressor (rotation speed controlled scroll-compressor) direct cooling coil (refrigerant) condensing coil (refrigerant) Photo: Intervent Aki Valkeapää

14 DIRECT COOLING – capacity regulator by hot gas by-pass
Figure: Danfoss Lähde: Coiltech Reference: Seppänen 2004 Figure: Danfoss Figure: Srcoils Capacity regulator with a hot gas by-pass valve (9) (100% > 50%) - hot gas is injected between thermostatic expansion valve (7) and evaporator (8) – energy is wasted, better solution would be rotation speed controlled (scroll) compressor Aki Valkeapää

15 Air cooled condensing units
A cooling system is executed with three compressor-condenser units and the direct cooling coil is divided into three horizontal sections. Refrigerating effect is controlled by the number of compressors in operation at the same time. Air cooled condensing units Reference: Seppänen 2004 Reference: Aittomäki 2008 Figure: Chiller Oy Aki Valkeapää

16 CENTRALISED INDIRECT COOLING CONSTANT AIR FLOW RATE
Chiller ”plant” without separated condenser (A+B) with a separated condenser (A+B+C) C A B Reference: Seppänen 2004 Aki Valkeapää

17 CENTRALISED INDIRECT COOLING CONSTANT AIR FLOW RATE, AIR CONDITIONING WITH CHILLED BEAMS
Iv-kone = AHU Lauhdutin=condenser Vesisäiliö=water tank Vedenjäähdytin=chiller Ilmastointipalkki=chilled beam Kaukolämmön alajakokeskus= District heating substation Term.venttiili ja vesiradiaattori= Radiator thermostat and radiator Reference: Seppänen 2004 Aki Valkeapää

18 CENTRALISED INDIRECT COOLING AIR CONDITIONING WITH FAN COILS
Figure: Chiller Reference: Seppänen 2004 Figure: Fläktwoods Aki Valkeapää

19 CENTRALISED INDIRECT COOLING AIRCONDITIONING AND VAV (VARIABLE AIR VOLUME)
Iv-kone=air handling unit Vedenjäähdytin=chiller Vesisäiliö=water tank Lauhdutin=condenser Reference: Seppänen 2004 Aki Valkeapää

20 INDIRECT COOLING cooling coil (chilled water) compressor
water or brine (liquid) charging circuit refrig. cycle plate heat exchanger (evaporator) chilled water tank Aki Valkeapää

21 INDIRECT COOLING AND DIRECT CONDENSING WITH AIR COOLED CONDENSER
Figure: Genemco Photo: Danfoss compressor condenser refrigerant cycle charging circuit expansion valve Figure: Fincoil plate heat exchanger (evaporation) Figure: Danfoss Aki Valkeapää

22 INDIRECT COOLING AND DIRECT CONDENSING ”air cooled liquid chiller”, roof (outdoors) mounting
TV 1 condenser Figure:Koja EVAPORATOR +27°C +7°C brine P1 +12°C Aki Valkeapää

23 INDIRECT CONDENSING AIR COOLED LIQUID COOLER
refrigerant cycle Brine circuit Plate heat exchanger (condenser) Figure: Fincoil Aki Valkeapää

24 CHILLER WITH FREE COOLING AND INDIRECT CONDENSING
P1 LS 1 LS 2 water brine TV 1 P2 brine P3 TV 3 TV 2 LS 3 Figures: Chiller Aki Valkeapää

25 INDIRECT COOLING AND INDIRECT CONDENSING WITH FREE COOLING
air cooled liquid cooler +42°C +36°C Summer case = compressor cooling +30°C P1 LS 1 LS 2 TV 3 water +12°C TV 1 P2 brine P3 TV 2 LS 3 +7°C Aki Valkeapää

26 INDIRECT COOLING AND INDIRECT CONDENSING WITH FREE COOLING
Air cooled liquid cooler winter case = compressor off temp. outdoors < +4°C +4°C P1 LS 1 LS 2 TV 3 water +14°C TV 1 P2 brine P3 TV 2 LS 3 +9°C Aki Valkeapää

27 INDIRECT COOLING AND INDIRECT CONDENSING WITH FREE COOLING
air cooled liquid cooler summer case = compressor cooling +36°C +42°C +30°C LS 3 P1 LS 1 LS 2 TV 3 water +14°C TV 1 P2 brine +7°C P3 Aki Valkeapää

28 INDIRECT COOLING AND INDIRECT CONDENSING WITH FREE COOLING
air cooled liquid cooler winter case = compressor off temp. outdoors < +4°C +4°C LS 3 P1 LS 1 LS 2 TV 3 water +9°C +14°C TV 1 VJK P2 brine P3 Aki Valkeapää

29 CHILLER 200 … 700 kW Figure: Chiller Aki Valkeapää

30 CHILLER 1=screw compressor 2=tube bundle heat exchanger (condenser)
3=tube bundle heat exchanger (evaporator) 4=filter drier 5=solenoid valve 6=sight glass 7=expansion valve Reference: Kaappola 2007 Aki Valkeapää

31 CHILLER Tube bundle heat exchanger as condenser:
Figure: Bitzer Tube bundle heat exchanger as condenser: refrigerant in bundle outside tubes brine in tubes (non freezing liquid) Tube bundle heat exchanger as evaporator: refrigerant in tubes brine in bundle outside tubes (non freezing liquid) Reference: Aittomäki 2008 Figure: SEC heat exchanger Aki Valkeapää

32 CENTRALISED INDIRECT COOLING DIRECT CONDENSING 3-port control valves
Refernce: Kaappola Aki Valkeapää

33 CENTRALISED INDIRECT COOLING DIRECT CONDENSING 2-port control valves
Reference: Kaappola tasaussäiliö=chilled water tank Aki Valkeapää

34 CENTRALISED INDIRECT COOLING DIRECT CONDENSING chilled beam system, three port control valve
Reference: Kaappola Aki Valkeapää

35 DISTRICT COOLING Figure : Helsingin energia
jäähdytysverkko=district cooling network kaukojäähdytyshuone=DC tech. room jäähdytyskeskus=cooling plant asuintalo=residential building liiketila oy=offices and shops Aki Valkeapää

36 replaces a compressor cooling systems in a real estate
DISTRICT COOLING replaces a compressor cooling systems in a real estate cooling is produced centrally, distributed through pipework to the real estates and is transferred with a heat exchanger to cooling pipework in the building (compare cf. district heating) temperatures - primary side +8°C / +16°C (DC network temp.) - cooling of AHU +10°C/+17°C - fan coils +15°C/+18°C or if condensing water from air +10°C/+18°C - chilled beam distribution network +15°C/+18°C secondary side with two port control valves Aki Valkeapää

37 ? DISTRICT COOLING District cooling production in Helsinki
Figure: Helsingin energia Vapaajäähdytys=free cooling lämpöpumppu=heat pump absortio=absortion Aki Valkeapää

38 Heat pump, wintertime DISTRICT COOLING Figure: Helsingin energia
Meri=sea Jätevesi= waste water Lämmönvaihdin=heat exchanger Figure: Helsingin energia Aki Valkeapää

39 Heat pump, summertime DISTRICT COOLING Figure: Helsingin energia
Aki Valkeapää


Download ppt "Mikkelin university of applied sciences Building services"

Similar presentations


Ads by Google