OIL BURNERS CONTROL BOX SERIES 599 SE Riello Burners - TRAining CEntre.

Similar presentations


Presentation on theme: "OIL BURNERS CONTROL BOX SERIES 599 SE Riello Burners - TRAining CEntre."— Presentation transcript:

1 OIL BURNERS CONTROL BOX SERIES 599 SE Riello Burners - TRAining CEntre

2 CONTROL BOX 599 SE PH N + M - TR ST PTC
Riello Burners - TRAining CEntre

3 CONTROL BOX 599 SE PH N Electrical supply: 230 V±10% fuse 6A 250V
ST L1 Valve coil starting:30V; 280mA running:3V; 30mA PH Valve coil: 100 Ignition transformer 20 kHz 8 kV 10 mA W Pre-purge timer: 12’’ by a capacitor 22µF and a resistence 1M N 1 A 700 VL input: 48 AC output: 72 DC Motor 150W Safety relais (bimetallic) Amplifier Pre-heater PTC max 150W + M - Safety relais (bimetallic) Remote lock-out signal 230 V; max 0.1A Internal relais 12V Riello Burners - TRAining CEntre

4 CONTROL BOX 599 SE 12+ 10- 11 SENSOR IN:
pre-purge & running ===> 54÷83,2 VDC ignition ===> min 53.7 VDC SENSOR OUT: pre-purge ===> 1.5V max 0.3mA ignition&running ===> min 6V; 1.2mA

5 CONTROL BOX 599 SE start up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre

6 CONTROL BOX 599 SE start up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre

7 CONTROL BOX 599 SE start up procedure: pre-heating
PH N + PTC M - Riello Burners - TRAining CEntre

8 CONTROL BOX 599 SEstart up procedure: pre-heating
PH N + PTC M - Riello Burners - TRAining CEntre

9 CONTROL BOX 599 SE start up procedure: pre-purge
PH N 70° C + PTC M - Riello Burners - TRAining CEntre

10 CONTROL BOX 599 SE start up procedure: pre-purge
PH N + PTC M - Riello Burners - TRAining CEntre

11 CONTROL BOX 599 SE start up procedure: pre-purge
PH N + PTC M - Riello Burners - TRAining CEntre

12 CONTROL BOX 599 SE start up procedure: pre-purge
PH N + PTC M - Riello Burners - TRAining CEntre

13 CONTROL BOX 599 SE start up procedure: pre-purge
PH N 52 V AC 72V DC + PTC M - Timer is supplied (12”) Riello Burners - TRAining CEntre

14 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - Riello Burners - TRAining CEntre

15 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - Riello Burners - TRAining CEntre

16 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - Riello Burners - TRAining CEntre

17 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - TRAining CEntre Riello Burners - TRAining CEntre

18 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - Riello Burners - TRAining CEntre

19 CONTROL BOX 599 SE start up procedure: ignition
PH N + PTC M - Riello Burners - TRAining CEntre

20 CONTROL BOX 599 SE start up procedure: post-ignition (4 secs)
PH N + PTC M M -

21 CONTROL BOX 599 SE start up procedure: post-ignition (4 secs)
PH N + PTC M M - Riello Burners - TRAining CEntre

22 CONTROL BOX 599 SE start up procedure: post-ignition (4 secs)
PH N + PTC M - Riello Burners - TRAining CEntre

23 CONTROL BOX 599 SE start up procedure: running
PH N + PTC M - Riello Burners - TRAining CEntre

24 CONTROL BOX 599 SE faults: no flame at ignition PH N 280 mA
ST PH 280 mA N + 280 mA at bimetallic relais PTC M - Riello Burners - TRAining CEntre

25 CONTROL BOX 599 SE faults: no flame at ignition PH N + M - TR ST PTC
Riello Burners - TRAining CEntre

26 no flame at ignition => lock-out
CONTROL BOX 599 SE faults: no flame at ignition => lock-out TR ST PH N + PTC M - Riello Burners - TRAining CEntre

27 light into the chambre (or short at photoresistence)
CONTROL BOX 599 SE faults: light into the chambre (or short at photoresistence) TR ST PH N + PTC M - Riello Burners - TRAining CEntre

28 light into the chambre (or short at photoresistence)
CONTROL BOX 599 SE faults: light into the chambre (or short at photoresistence) TR ST PH N + PTC M - Riello Burners - TRAining CEntre

29 light into the chambre (or short at photoresistence)
CONTROL BOX 599 SE faults: light into the chambre (or short at photoresistence) continous pre-purge TR ST PH N + PTC M - Riello Burners - TRAining CEntre

30 valve coil interrupted : continous pre-purge
CONTROL BOX 599 SE faults: valve coil interrupted : continous pre-purge TR ST PH N Timer is not supplied + PTC M - Riello Burners - TRAining CEntre

31 Short at Darlington R3381 by Texas
CONTROL BOX 599 SE faults: Short at Darlington R3381 by Texas TR ST PH N + PTC M - Riello Burners - TRAining CEntre

32 Short at Darlington R3381 by Texas
CONTROL BOX 599 SE faults: Short at Darlington R3381 by Texas TR ST PH N + PTC M - Riello Burners - TRAining CEntre

33 Immediate change of position
CONTROL BOX 599 SE faults: Short at Darlington R3381 by Texas TR ST Immediate change of position PH N + PTC M - 2A at bimetallic relais Riello Burners - TRAining CEntre

34 Short at Darlington R3381 by Texas
CONTROL BOX 599 SE faults: Short at Darlington R3381 by Texas TR ST PH N + PTC M - Riello Burners - TRAining CEntre

35 Short at Darlington R3381 by Texas Immediate lock-out
CONTROL BOX 599 SE faults: Short at Darlington R3381 by Texas Immediate lock-out TR ST PH N + PTC M - Riello Burners - TRAining CEntre