OIL BURNERS RIELLO 2000 SERIES.

Similar presentations


Presentation on theme: "OIL BURNERS RIELLO 2000 SERIES."— Presentation transcript:

1 OIL BURNERS RIELLO SERIES

2 MODELS : G30BR G35B G3RK G55 G55KR G103 G214D*
1.3  kg/h G35B 1.6  3 kg/h G3RK G55 2.3  kg/h G55KR 1.3  kg/h G103 3.5  kg/h G214D* 6/7.9  18 kg/h * Two stage by two pressure levels

3 WORKING FIELDS [mbar] [kg/h]

4 A B C D E F G OVERALL DIMENSIONS

5 HYDRAULIC CONNECTIONS

6 PUMP GROUP part N°

7 1 - Suction line 2 - Return line 3 - By-pass screw 4 - Gauge connection 5 - 2 nd stage pressure adjuster 6 - Suction gauge connection 7 - 1 st stage pressure adjuster 8 - Pressure reducer piston 9 - 2 nd stage valve st stage valve 11 - Auxiliary pressure gauge Pump group part N°

8 It is important to equip the nozzle with a sintered filter
SETTINGS & SUGGESTED NOZZLES Monarch R - NS Delavan W - A - E Steinen H - Q Danfoss H B G 30BR It is important to equip the nozzle with a sintered filter

9 SETTINGS & SUGGESTED NOZZLES
Monarch R - NS Delavan W - A - E Steinen H - Q Danfoss H B G 35B

10 SETTINGS & SUGGESTED NOZZLES
Monarch R - NS Delavan W - A - E Steinen H - Q Danfoss H B G 55

11 From GPH 0.85 Till GPH 0.75 SETTINGS & SUGGESTED NOZZLES Monarch R Delavan W - B Steinen Q Danfoss S Satronic S Fluidics SF G 55KR

12 SETTINGS & SUGGESTED NOZZLES
Monarch R Delavan W - B Steinen S - Q Danfoss S - B G 103 For GPH 2.00 use, if possible, a full cone

13 SETTINGS & SUGGESTED NOZZLES
Monarch R -PLP Delavan W - B Steinen S - SS Danfoss S Hago P G 214D

14 AIR DAMPER ADJUSTMENT(one stage):
The air damper (A) opens due to the depression caused by the fan. In order to carry out the adjustment, operate on the screw (B) after loosing the nut (C). Once complete the adjust-ment, lock the nut. The settings refer to the burner with its cover fitted and combustion chamber with depression zero. These regulations are purely indicative. Each installation however, has its own unpredictable work-ing conditions: actual nozzle output; positive or negative pressure in the combustion-chamber, the need of excess air, etc. All these conditions may require a different air-damper setting. It is important to take account of the fact that the air out-put of the fan differs according to whether the burner has its cover fitted or not.

15 AIR DAMPER ADJUSTMENT (two stage):
2 nd STAGE ADJUSTMENT Adjustment of air shutter Unloosen the nut (6), turn the screw (7) until the air shutter (1) reaches the position desired. Then lock the nut (6). 1 st STAGE ADJUSTMENT Adjustment of air shutter Unloosen the nut (2), turn the screw (3) until the air shutter (1) reaches the position desired. Then lock the nut (2).

16 pre-heater thermostat
WORKING MODE (one stage) control box 555SE electrical supply 230V +-10% 50Hz ignition transformer 8kV; 10mA safety thermostat) fuse 6 A F (fast) L boiler thermostat remote lock out signal (230V max 0.1A) L1 N N fotoresistence T1 T2 S3 B4 valve coil 30 =>3V DC 100 h pre-heater (230V); 55W) hour counter (230V max 0.1A) motor (90W) pre-heater thermostat (55°C)

17 WORKING MODE (one stage) control box 555SE
h M

18 WORKING MODE (one stage) control box 555SE 0”
h M

19 WORKING MODE (one stage) control box 555SE 0”
h M

20 WORKING MODE (one stage) control box 555SE 0”
h M

21 WORKING MODE (one stage) control box 555SE 0-120” pre-heating

22 WORKING MODE (one stage) control box 555SE
h M

23 WORKING MODE (one stage) control box 555SE 12” -pre-purge
h + 50VAC M

24 WORKING MODE (one stage) control box 555SE ignition (max 5”)
h + M

25 WORKING MODE (one stage) control box 555SE ignition (max 5”)
h + M

26 WORKING MODE (one stage) control box 555SE working
h + M

27 WORKING MODE (one stage) control box 555SE lock out: no ignition
h + M

28 WORKING MODE (one stage) control box 555SE lock out: no ignition
h M

29 WORKING MODE (two stage) control box 554SE
electrical supply 230V +-10% 50Hz ignition transformer 8kV; 10mA safety thermostat) fuse 6 A F (fast) L 1st stage thermostat remote lock out signal (230V max 0.1A) L1 N N fotoresistence T1 T2 S3 B4 h1 2nd stage thermostat hour counter 1st stage (230V max 0.1A) 1st stage valve coil 30 =>3V DC 100 motor (150W) 2nd stage valve coil 230 VAC (diodes provided) h2 B5 EL. DELAYING DEVICE T6 T7 M T8

30 WORKING MODE (two stage) control box 554SE
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

31 WORKING MODE (two stage) control box 554SE 0”
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

32 WORKING MODE (two stage) control box 554SE 0”
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

33 WORKING MODE (two stage) control box 554SE 12” pre-purge
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

34 WORKING MODE (two stage) control box 554SE 12” pre-purge
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

35 WORKING MODE (two stage) control box 554SE 12” ignition
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

36 WORKING MODE (two stage) control box 554SE max 5” flame
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

37 WORKING MODE (two stage) control box 554SE working
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

38 WORKING MODE (two stage) control box 554SE 5” after: 2nd stage
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

39 WORKING MODE (two stage) control box 554SE 5” after: 2nd stage
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8

40 WORKING MODE (two stage) control box 554SE 1st stage
h1 h2 B5 EL. DELAYING DEVICE T6 T7 M T8


Download ppt "OIL BURNERS RIELLO 2000 SERIES."