NOVEC Fire Suppression System

Slides:



Advertisements
Similar presentations
General Safety Overview and Information
Advertisements

HVAC523 Heat Sources.
Furnaces also called Fired Heaters
Fire Extinguisher Training
Portable Fire Extinguisher Safety Emergency Procedures.
How would you explain this on the 3394? If Fire Erupts on YOUR Boat If Underway, stop the boat Have everyone who is not wearing a PFD put one on Position.
Evaluating Kitchen Hoods Rudy Hawkins C-1. Hood Designs and Categories - Background o Commercial Kitchen Hoods have two designs: o Exhaust Hoods o Grease.
Fire Prevention & Protection Gordon Cooper Technology Center
Halon Systems Ch. 5, pages HALogenated hydrocarbON not the same as halogen F, Cl, Br, I 1940’s ’s extremely effective.
© Siemens Industry, Inc Confidential / Drive Your Business Forward Ignite the Power of New Products and Partnerships Siemens Fire Partner Summit.
Fire Detection and Suppression Chapter 7 Special Extinguishing Systems.
Viking TotalPac2 FireFlex Dual / 1230
FIRE FIGHTING PROCESS HAZARDS
Fire Prevention.
Section 2 Safety, Tools and Equipment, Shop Practices Unit 4 General Safety Practices.
Atlantic Beach Fire Department Presents: For Business Employees and the General Public.
The three essential ingredient for creating a fire are HEAT, AIR AND FUEL Fire triangle.
Fire safety is an important business. You need to take proper precaution in order to prevent a fire. Yes, fire may be inevitable but if prepared, you can.
1 Fire Safety Emergency Preparedness Session 10 Laboratory Safety Training.
Fire Safety and Utility Controls CERT Basic Training Unit 2.
Copyright © Center for Systems Security and Information Assurance Lesson Seven Physical Security.
In today’s global business environment, the need for clean agent fire suppression has never been greater. Pem All.
Introduction to Hydraulics ClassAct SRS enabled. In this presentation you will: identify the fundamental parts of a hydraulic system and safety issues.
LNG Hazards.
What you will learn in this session 1.The characteristics of fire, smoke and toxic fumes 2.Fire hazards involved in the working environment 3.Significant.
Fuel Oil Systems Fuel Oil Systems consist of: Storage Tanks Pumps
Kidde Engineered Fire Suppression System 25 bar Equipment Hardware Engineered for use with 3M™ Novec™ 1230 Fire Protection Fluid.
Technology in Architecture Lecture 12 Electrical Equipment Electrical Power Management Fire Protection Systems Lecture 12 Electrical Equipment Electrical.
Patrick Thornton, SNS/FPE June 9, 2008
NEXT GENERATION Kidde Engineered Fire Suppression System Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid.
Lesson 17 KEEPING WATCH. WATCHKEEPING 4 STCW 1978 (1995) 4 Watch (1) time period; (2) personnel 4 Personnel: Engineer officer in charge (watchstanding.
Dry and Wet Chem Systems Ch. 8, pages Dry Chemical Systems Dry Chem. System Components Dry Chem. Sequence of Operation Applications for Dry Chem.
Fire Extinguisher Training
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Select and deploy the appropriate hose lines to accomplish fire confinement and extinguishment.
CXS490 Carbon Dioxide Systems
Before we learn how to extinguish fires, we first need to know a little about how they work. The fire triangle to the right shows the three things that.
MODULE:3 FIRE CONFINMENT AND EXTINGUISHMENT. OBJECTIVES Module 3 Overview Select and deploy the appropriate hose lines to accomplish fire confinement.
3M™ Novec 1230™ Fire Protection Fluid
1 CXS490 - Characteristic of Fire. 2 Other Resources NFPA Standards (available through Seneca Libraries Link NFPA Handbook Manufacturer’s Technical Information.
Fire Hazards (this is not an introduction to urban warfare)
FIRE SERVICES AT DATA CENTRE
1 CXS490 - Pre-Engineered Fire Protection Systems Off-Road Vehicle Systems.
Add name of trust / organisation in box 1 and name of trainer in box 2. Delete THIS box.
Kidde FM-200® Product Review
Weekly Checks Monday – VSP Room Tuesday – Pilothouse System Controls Wednesday – Starboard / Engine Room Thursday – Foam Room Friday – Port / Engine Room.
Power Distribution System General Location. Power Distribution The Main Switchboard is the hub of the electrical distribution system. Everything ties.
Red/Green Fire Fighting Systems Fi Fi Mains ●Red System: Port Side Fire Main supplies two Monitors. M7 (6000) gpm on centerline on the fwd Wheelhouse top.
Breathing Air Scott-RevolveAir Charge station with X4 controller. Storage Auto-fill capable. Unit can fill 2 SCBA bottles at a time behind a burst shield.
Fire/General Service/Ballast Pumping Systems
Bilge Pumping Systems General Locations.
Machinery Cooling Water System Locations and Operations.
MODULE 2 Operate the Propane Liquid Supply System.
What you will learn in this session 1.The characteristics of fire, smoke and toxic fumes 2.Fire hazards involved in the working environment 3.Significant.
HOT-LOADING SAFETY TRAINING FOR THE NEPTUNE BAE 146.
Clean Lube Oil Transfer System General Locations and Operations.
Striving For Safety Excellence HunterDouglas Corporate Environmental, Safety, Risk Management Lock Out Tag Out Affected Employees.
Fire Extinguisher Training
“Portable Fire Extinguishers Safety”
Fire Extinguisher Training
What you will learn in this session
Fire Suppression (Fire Fighter II)
What Library Staff Should Know About Fire Safety
“ Highlighting the risks and challenges presented by modern data-center cooling systems in fire detection and suppression applications. “ Dave Boyack Sales.
Flammable and Combustible Liquids
Furnaces (also called Fired Heaters)
Firefighting equipment
HAZOP Guidewords Base Set
MACHINERY SPACE FIRE.
Presentation transcript:

NOVEC Fire Suppression System Configuration and Operation

NOVEC Fire Suppression System What is NOVEC? 3M Novec 1230 Fire Protection Fluid Is a next-generation halon alternative offering outstanding performance, large margin of safety, and an excellent environmental profile. • Zero ozone depletion potential • 5-day atmospheric lifetime • A global warming potential of 1 • A large margin of safety for occupied spaces Novec 1230 Fire Protection Fluid is based on a proprietary chemical from 3M called a fluoroketone. The full chemical name for this compound is dodecafluoro-2-methylpentan-3-one. Its ASHRAE nomenclature – the way it is designated in the NFPA 2001 and ISO 14520 clean agent standards – is FK-5-1-12. Novec 1230 fluid offers a unique combination of safety, low environmental impact and extinguishing performance, making it the first chemical halon replacement to offer a viable, long-term, sustainable technology for special hazards fire protection.

NOVEC Fire Suppression System How does NOVEC Work? Extinguishes by: Absorption of heat Interruption of Chemical Chain Reaction Don’t Just Manage a Fire. Extinguish It. 3M™ Novec™ 1230 Fire Protection Fluid is a highly-effective clean agent fire suppressant, designed to extinguish a fire in its incipient stage before it has a chance to spread. It is applied as a gas, but is liquid at room temperature, and can be effectively used in streaming, flooding systems, or for use in inerting and explosion suppression applications. Knocks down fires fast Novec 1230 Fluid has a very low heat of vaporization, approximately 25 times less than that of water. This, along with a higher vapor pressure, causes Novec 1230 Fluid to evaporate more than 50 times faster than water. It also allows the clean agent to transition from a liquid to a gaseous state very rapidly when discharged through a nozzle, and readily achieve vapor extinguishing concentrations in air. With high extinguishing efficiency and a wide margin of safety, Novec 1230 fluid is a great alternative to water sprinkler systems, foam and dry chemicals due to: • Low toxicity (no harm to personnel) • Extinguishes fires in less than half the time of CO2 & inert gases • No damage to sensitive equipment • Not targeted for emission reduction or phaseout

NOVEC Fire Suppression System Is NOVEC Safe?

NOVEC Fire Suppression System Configuration Engine Room is only space protected by the NOVEC Fire Suppression System. System may be activated from any of the following stations: Port Main Deck Entry at the top of E/R Stairs. Wheelhouse, Port, Forward, Stack Bulkhead. VSP Room Local Station.

NOVEC Fire Suppression System Configuration Nitrogen, through stainless steel tubing, actually send the “signals” to the valves at the local station to open. No cables or wires like our old boats systems! Wheelhouse NOVEC Remote Station

NOVEC Fire Suppression System Configuration Port Entry NOVEC Remote Station

NOVEC Fire Suppression System Configuration VSP Room NOVEC Local Station

NOVEC Fire Suppression System Configuration 900 Pounds of NOVEC agent are stored in a pressure tank in the Starboard, FWD VSP Room. NOVEC is a liquid at standard pressures and temperatures, but when released at high pressure expands quickly to a “gaseous state.” A flexible stainless steel hose connects the pressure tank to the galvanized discharge piping that leads into the Engine Room.

NOVEC Fire Suppression System Configuration The NOVEC discharge piping terminate at (4) nozzles, evenly spaced around the E/R

NOVEC Fire Suppression System How the System Works When you operate the levers on the nitrogen bottles at either remote station, it sends nitrogen down stainless steel tubing to the NOVEC Local Station in the VSP Room. The bottle on the left causes the Nitrogen Pilot Valve to open The bottle on the right causes the system Control Valve to open Note: You MUST lift BOTH Levers to discharge NOVEC (it does not matter what order)

NOVEC Fire Suppression System How the System Works Nitrogen from the remote stations opens the Control Valve seen here. Nitrogen from the remote stations opens the Nitrogen Pilot Valve seen here Down in the Port, Aft VSP Room

NOVEC Fire Suppression System How the System Works Nitrogen released from the Pilot Tank causes several things to happen: Opens the valve on the Time Delay Bottle. Triggers the two pneumatic switches which trigger machinery and ventilation Emergency Stops. Opens the valve on the large nitrogen bottle which: Sounds the NOVEC Release Siren Sends nitrogen to remotely close the Fuel Oil Day Tank Remote Closing Valves (Nitrogen pressure is reduced through a preset regulator).

NOVEC Fire Suppression System How the System Works Once the Time Delay has occurred (34 seconds), nitrogen is released from the Time Delay Nitrogen tank, through stainless tubing, and triggers the NOVEC Storage Tank Valve to open. All NOVEC is now released into Engine Room.

NOVEC Fire Suppression System How the System Works The following equipment is effected by the NOVEC actuated pneumatic switches and will need to be reset after a NOVEC release: All Engines and Generators F.O. Transfer Pumps Clean L.O./Uses L.O./ Oily Water Transfer Pumps Clean L.O. Tank Isolation Valve E/R Ventilation Fans shut-down E/R Ventilation Dampers closed (magnetic hold-back) VSP Room/Aft Hold Ventilation Fans shut down VSP Room/Aft Hold Ventilation dampers closed Machinery Space Relief Air Louvers close (Port and Starboard Stack plenum) HVAC supply fans shut down (maybe…still waiting to verify) Bulkhead fire dampers 1,2,3, & 4 shut down.(maybe…still waiting to verify)

NOVEC Fire Suppression System How the System Works All the equipment on the previous list is tripped through the pneumatic switches seen here. Nitrogen from the Pilot Bottle activates these switches. In turn, the switches interact through the Emergency Stop System to shut down machinery, close dampers, etc. Pilot Bottle

NOVEC Fire Suppression System How the System Works The following equipment is effected directly by a nitrogen pressure signal from the NOVEC system and will need to be reset after NOVEC activation: F.O. Day Tank Remote Closing Valves (Fill, and supply valves)

NOVEC Fire Suppression System How the System Works To Day Tank remote closing valves Step down regulator The Fuel Oil Day Tank Valves are pneumatically actuated remote closing, so when the NOVEC system is activated, nitrogen from the siren driver bottle, also pneumatically trips these valves closed. The nitrogen is stepped down in pressure to around 100 psi to close these valves. Note: The Fuel Oil Day Tank Valves may also be tripped from the from the Fire Control Station Panels (Main Deck Entry, Wheelhouse). This is an electric over service air signal. Siren driver nitrogen

NOVEC Fire Suppression System Activating the NOVEC System The decision to activate the NOVEC System should not be taken lightly. It is only after all offensive, and defensive tactics to control a fire in the Engine Room of the Fireboat have been exhausted should activation of NOVEC be considered, as well as the risks and consequences of a NOVEC release. Prior to releasing NOVEC, it is assumed the General Alarm has been sounded and all crew members are aware of the emergency. It is a joint decision between Fire Captain, Pilot, and Engineer whether to release NOVEC or not. Remember: Once NOVEC discharge is initiated, all machinery, ventilation, fuel oil, etc. in the machinery space will be shut down, and you will have a virtually dead ship. Make sure the fireboat is in a position (if possible) where a dead ship will not create more problems (grounding, collision, hazard to navigation, blocking a shipping channel, sinking/flooding). Ensure Engine Room is evacuated of all personnel prior to initiating NOVEC release!

NOVEC Fire Suppression System Activating the NOVEC System Prior to activating the NOVEC system you should ensure the following is done: Engine Room Evacuated Crew Accounted for Issue a distress call - call 911 (ha ha) Vessel in safest area possible, consider anchoring or mooring vessel. Secure all Engine Room Machinery, Ventilation, Ventilation Dampers, Fuel Oil Day Tank Valves (If you forget any of these the NOVEC system will secure it automatically) Secure all Machinery Space Doors: VSP Room Watertight Door Aft Hold Water Tight Door Port Main Deck Entry Doors Engine Room Escape Hatch VSP Room Escape Hatch

NOVEC Fire Suppression System Activating the NOVEC System NOVEC release may be initiated from either remote activation station. Pull the pins and lift the levers of both nitrogen bottles. You only have to do it from one or the other remote station! Wheel House NOVEC Port Entry NOVEC Note: Once you activate from this station, get out of here and close the doors behind you. This area is technically the top of the Engine Room!!

NOVEC Fire Suppression System Activating the NOVEC System To Activate NOVEC System from the VSP Room Station: Close Water Tight Door between Engine Room and VSP Room Pull pin and lift this lever The system will start the release cycle, so head out of VSP Room through escape hatch. If you wish to by-pass the time delay (34 seconds), pull pin and lift lever on this cylinder, and NOVEC will release immediately.

NOVEC Fire Suppression System Resetting after NOVEC Release We have researched the re-set procedures for the E-Stop and NOVEC automated machinery shut-down systems. Unfortunately, at this time, we do not have enough information to provide you with an accurate re-set procedure. We will work with the shipyard team to develop a procedure for resetting machinery after E-Stop activation and/or NOVEC System activation. This procedure will be provided to you in a subsequent training document, or during on site training once the boat makes it to Long Beach.