Power Quality Impacts of Distributed Generation Roger C. Dugan Sr. Consultant Electrotek Concepts, Inc. Tennessee Tech. February 9, 2004.

Slides:



Advertisements
Similar presentations
Alternator Protection for Emergency Standby Engine Generators
Advertisements

New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Interconnection Protection Issues Protection related problems in the distribution systems due to presence of Distributed Generation.
DOD Microgrids The Missing Link: Microgrid Applications Michael Dempsey P.E. Burns & McDonnell June 12, 2013 © 2013 Burns & McDonnell. All Rights Reserved.
GENERATOR PROTECTION.
Distribution System Analysis for Smart Grid Roger C. Dugan Sr. Technical Executive, EPRI Webcast Feb 8, 2011.
1 Distributed Generation and Power Quality. 2 Relaying considerations DG infeed may reduce the reach of overcurrent relays –DG feeds fault, so utility.
Project 1.4 Operational Strategies and Storage Technologies to Address Barriers for Very High Penetration of DG Units in Intelligent.
1 Distributed Generation and Power Quality. 2 Distributed Generation Distributed generation (DG) or distributed generation resources (DR) –Backup generation.
IMPACTS OF LARGE DISTRIBUTED GENERATORS ON CENTERPOINT ENERGY’S DISTRIBUTION SYSTEM 1 Presented by Ed Briggs, P.E. Manager of Electric Distribution Planning.
Campus da FEUP Rua Dr. Roberto Frias, Porto Portugal T F © 2009 Decentralised Energy Systems.
AC circuit breaker with series connected switches George G Karady.
Sean A. Kufel, P.E. Power System Engineering, Inc. April 20, 2015 Distributed Generation System Impact Analysis with Computer Modeling Tools IEEE Rural.
Proposed Design and the Operation of a Disconnecting Device for Small EG Installations Prepared by Hendri Geldenhuys.
EE 369 POWER SYSTEM ANALYSIS
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
Chapter 7 SYSTEM PROTECTION
5/21/2015 Using Simulation Tools to Predict and Prevent Vacuum Circuit Breaker Switching Induced Transformer Failures Steven B. Swindler,
Interconnect Protection of Dispersed Generators
Roger C. Dugan Fellow, IEEE Review of the Impacts of Distributed Generation on Distribution Protection 2015 IEEE Rural Electric Power Conference Asheville,
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Protection Against Transient Overvoltages
1 Power Quality Mary Santori, P.E. Senior Engineer September 12, 2013.
Transient Overvoltages
Applying the Distribution System in Grid Restoration/NERC CIP-014 Risk Assessment Srijib Mukherjee, Ph.D., P.E. UC Synergetic.
SWEDE - April 26 th, Bastrop Tommy Nylec Austin Energy Fusing and Fault Indicator Applications.
Overcurrent Protection and Voltage Sag Coordination in Systems with Distributed Generation J. Carlos Gomez 1 M. M. Morcos 2 1 Rio Cuarto National University,
 Interconnecting DER With Electric Power Systems POWER SYSTEM 2002 CONFERENCE -- IMPACT OF DISTRIBUTED GENERATION Image.
POWER SYSTEM PROTECTION
Frankfurt (Germany), 6-9 June 2011 GONZALEZ–CH–RIFS4–0182 OPERATIONAL STABILITY OF SHUNT CIRCUIT-BREAKER SYSTEMS IN UNGROUNDED MV NETWORKS WITH DISTRIBUTED.
New proposed BU circuit and control logic design University of Washington.
By J DAVID MANOHAR (08A31A0232). NECESSITY OF SUPERCONDUSTOR  Damage from short circuit is constant threat in power systems  All the power systems components.
Lecture 18 Markets, Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Assumption University Thailand EE4503 Electrical Systems Design Main Circuit 1.
CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION.
Frankfurt (Germany), 6-9 June 2011  PV in Spain: Basically Large plants connected to MV or HV Mainly in rural areas (generation exceeds consumption) 3,000.
Energy Storage Applications at AEP Emeka Okafor American Electric Power Presentation to SouthWest Electric Distribution Exchange May 7, 2009.
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Clemson University Electric Power Research Association CHANDANA BOMMAREDDY CLEMSON UNIVERSITY DG VOLTAGE CONTROL IN AN ISLANDING MODE OF OPERATION.
Lecture 18 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
KEM_Cespedes_A1 Colombia Session 3 – Block 1 Barcelona May ACCURATE MODELING FOR LOSSES REDUCTION USING A REAL-TIME POWER FLOW AT ENELVEN.
Announcements Read Chapters 10 and 11
1 Distributed Generation and Power Quality-Continued.
Steady State Analysis Of A Microgrid Connected To A Power System
NEPTUNE Power Low Voltage Circuit Fall 2003 Quarterly Meeting Tim McGinnis Sept 11-12, 2003.
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
DISTRIBUTED GENERATION ISSUES Technical Issues Non-Technical Issues.
Survey of Smart Grid concepts and demonstrations Smart substation Ari Nikander.
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
This project on Primary sub station of Visakhapatnam port trust at Visakhapatnam. It is 132kv/11kv substation with incoming feeder from APTransco and 11.
Impact of Distributed Generation on Fault Induced Transients: A Case Study Sukumar Brahma Adly Girgis Clemson University Electric Power Research Association.
Protection of Power Systems
Power System Protective Relaying-Part One
Protection of Power Systems
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Power Quality at Solar Distributed Generation Facilities
Protection of Power Systems
Distributed Generation
Interconnect Protection of Dispersed Generators
Advanced Fuse-Saving Techniques
EE6501 POWER SYSTEM ANALYSIS
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Design of Electric Power Systems and Utilities
Protective Relaying Conference
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
EET 323 – Electrical System Design Lecture 9: Grounding
Interconnection of AES With The Grid
Power System Protective Relaying-Part One
Presentation transcript:

Power Quality Impacts of Distributed Generation Roger C. Dugan Sr. Consultant Electrotek Concepts, Inc. Tennessee Tech. February 9, 2004

Electrotek Concepts, Inc2 Introduction Renewed interest in Grid-connected DG –Utility Perspective T & D Capacity Relief Hedge against high market prices –End User Perspective CHP and Improved Reliability Incentives from Utility –Commercial Power Producer Sell kWh or “ancillary services”

Electrotek Concepts, Inc3 Emphasis of This Presentation Units connected to distribution (MV) –Typically < 10 MW –Commonly 1-2 MW –Frequently owned by end user Impact of these units on Power Quality –Operating conflicts –We will look at a few of the many …

OverCurrent Protection Conflicts

Electrotek Concepts, Inc5 Typical Overcurrent Protection

Electrotek Concepts, Inc6 Only One Device Has to Operate Operating Device Fault Current

Electrotek Concepts, Inc7 Transmission Fault Protection Multiple Sources Two Devices Must Operate to Clear Fault

Electrotek Concepts, Inc8 LV Network Systems

Electrotek Concepts, Inc9 Utility Fault Clearing Due to cost, distribution systems are designed expecting only one source of fault current –Only one device has to operate DG must disconnect to allow utility fault clearing process to continue This is the source of most operating conflicts

Electrotek Concepts, Inc10 Reduction of Reach Utility relays and DG relays may not know anything is wrong.

Electrotek Concepts, Inc11 Reduction of Reach More of a problem at peak load –When peaking units are likely to be connected !! More of a problem for high resistance faults Longer fault detection times

Instantaneous Reclosing

Electrotek Concepts, Inc13 Reclosing Most faults are temporary Reclosing is prevalent in North America Reclosing Interval: 0.2 – 5 sec –“Instantaneous” < 30 cycles

Electrotek Concepts, Inc14 Reclosing, cont’d If DG does not get off, two bad things could happen: –DG is damaged by the reclose Shafts Winding damage –Fault is not cleared Reduced reliability Damage to utility system

Electrotek Concepts, Inc15 Reclosing DG Must Disconnect Here

Electrotek Concepts, Inc16 Instantaneous Reclosing Utilities use this for PQ concerns Increases the probability that DG will not disconnect in time –Makes it almost a certainty that some won’t If 1-2 sec, most operations will be easily detected by DG protection Some utilities use 5 sec reclose on feeders with DG

Unintended Consequences...

Electrotek Concepts, Inc18 Voltage Drop After Fault

Electrotek Concepts, Inc19 Low Voltage After Interruption A problem when there is a fault at peak loading –When peaking DG is likely to be on !! This is often the most limiting condition for how much DG can be accommodated without change –Particularly on rural feeders –500 – 1000 kW

Ferroresonance Sometimes Conflicting Interconnect Requirements Collide …

Electrotek Concepts, Inc21 Ferroresonance G 1) Fuse blows or switch opens 2) DG breaker detects negative sequence and trips leaving transformer isolated on cable capacitance with no load/generation 3) Ferroresonance develops DG Required to have separate Transformer and disconnect at first sign of trouble

Electrotek Concepts, Inc22 Ferroresonance

Electrotek Concepts, Inc23 Ferroresonance Waveform

Reduced Insulation

Electrotek Concepts, Inc25 Arrester Duty for SLG

Varying Generation

Electrotek Concepts, Inc27 Varying Generation Example 336 MCM ACSR (Untransposed) ft ft 1000 kW 500 kW Regulator Wind Gen 8 MW 600 kvar 115 kV12.47 kV Unbalanced impedances Rapidly-varying “load”

Electrotek Concepts, Inc28 Varying Generation Regulator Operations

Transformer Connection and Ground Faults

Electrotek Concepts, Inc30 Grd Wye-Delta Connection Some claim this is the best way to interconnect DG –Same way as nearly all central station generation is connected –However, most utilities don’t allow this connection on their system.

Electrotek Concepts, Inc31 Wye-Delta Connection

Electrotek Concepts, Inc32 Problems with Wye-Delta Increases ground fault current Interferes with coordination Faulted Circuit Indicators get fooled Transformer subject to failure –Special design and/or neutral reactor –Utilities often discourage “Specials”

Electrotek Concepts, Inc33 On Wye-Wye Most common U.S. connection Generally well behaved Does not block Triplen Harmonics –Leads to “Harmonic Surprise” when many machines paralleled with utility system Also occurs with Delta-Wye –2/3 pitch machines lessens the impact

Electrotek Concepts, Inc34 Conclusions Interconnected DG likely to increase DG must adapt to Distribution protection system Too much infrastructure already in place to overhaul the system to better accommodate DG Who would pay for it? Non-participating ratepayers?

Electrotek Concepts, Inc35 Conclusions DG impact on Power Quality –Often good for individual end users Largest gainers: Those with high-value product that suffer sustained interruptions But, should not expect power quality improvement in all areas –Maybe slightly negative for utility Contributes to operating conflicts Can we see it in the Average indices?

Electrotek Concepts, Inc36 Conclusions, cont’d Revisit Overcurrent Protection –Utilities may have to change some practices –Instantaneous reclosing ? –Use of line fuses Tradeoffs for Transformer Connections –WYE-Delta good for DG but not for ground fault coordination Special engineering req’d for some DG application.

Electrotek Concepts, Inc37 Despite These Conflicts … DG can almost always be successfully engineered –Larger conflict may be over who pays –Some long-standing utility practices may have to be changed

Electrotek Concepts, Inc38 How Much DG ? What is the “No Changes” “Penetration Limit” ? –Typical: 15% of feeder capacity –5% - 10% if Rural