1 A/C Pressure Test and Evacuation. 2 Leak Detection Leak detection must be done after every repair job. It must also be done anytime the appliance can.

Slides:



Advertisements
Similar presentations
Refrigeration Basics 101 By: Eric Nelson.
Advertisements

Air Conditioners and Heaters
Refrigeration Systems
Coach Air Conditioning
Chapter 4 Air-Conditioning Components
General System Maintenance BUS 4 COMPONENT FLOW.PPT
Left Side Discharge Pressure Regulator
SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES
Terms and Definitions Base Metal: Metal to be welded Fusion Welding: process that joins metals by heating them to a melting point and allowing them to.
…just got better.
Working with refrigerants After studying this chapter, you will be able to Purge system with nitrogen. Pressurize system for leak detection Describe different.
Unit 8: Leak Detection, System Evacuation, and System Clean-up
Trouble Shooting and Performance Testing
Air Conditioning EPA Type II.
A/C testing and service. Before testing and service, technician must be certified by ASE, MACS, or IMACA.
1 Basics of Heating and Air Conditioning Heat energy Heat measurement Heat movement States of matter Latent and sensible heat Boiling points Pressures-
JHCBC AUTO A/C PERFORMANCE TESTING CHAPTER 3 Page
BASIC PNEUMATICS. Properties of Compressed Air Availability Easily stored in large volumes Simplicity in design and control Provides linear and rotary.
SYSTEM COMPONENTS CHAPTER 5page 91C & 93 L. OBJECTIVES l IDENTIFY AND COMPARE THE STATE OF REFRIGERANT IN EACH SECTION OF A/C SYSTEM. l EXPLAIN PURPOSE.
CHAPTER 6 Moving Heat: Heating and Air Conditioning Principles
1 Air Conditioning EPA Type 1. 2 Type One Certification.
Refrigerant Charge Procedures
Left side compressor behind Left control box Right side compressor behind Right control box.
PRINCIPLES OF HEAT TRANSFER
SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES
Forging new generations of engineers. Basic Pneumatics.
CCNA1 v3 Module 9 v3 A+ Type 1 JEOPARDY K. Martin.
1 HVACR318 – Refrigeration II Diagrams. 2 Hooking up Gauges on Suction and Discharge Lines.
CCNA1 v3 Module 9 v3 A+ Type 2 JEOPARDY K. Martin.
Air Conditioning Charging.
CCNA1 v3 Module 9 v3 A+ Type 1 JEOPARDY K. Martin.
3. Climate Control Systems Service Automotive – Heating & Air Conditioning Topics covered in this presentation: Gauge set and refrigerant Service ports.
Chapter 4 Training Package HCFC Phase-out RACSS – UNEP 2014 Servicing of HCFC/HFC Based Air-conditioners.
Evacuation & Dehydration Seminar
Section 2: Safety, Tools and Equipment, and Shop Practices
Heat Transfer and Refrigeration Cycle
delivered with the compressor
Automotive Heating And Air Conditioning
Heat Transfer and Refrigeration Cycle
GROUND SERVICING OF VARIOUS SUB SYSTEMS
Climate Control Systems Service
14 Refrigerant Recovery, Recycling, and Recharging.
R1 Fundamentals of Refrigeration
Climate Control Systems Service Air Conditioning System Service
2009 CARE Evacuation & Dehydration Seminar
Refrigeration Basics By: Mohamed Iqbal Pallipurath.
Scotsman Refrigeration 101
R1 Fundamentals of Refrigeration
High Pressure Appliance Leak Detection
BASIC PNEUMATICS.
Leak Detection All Refrigerant: Soap bubble
Small Appliance Recovery Requirements
By: JAGDEEP SANGWAN Refrigeration Basics 101.
SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES
Leaky Appliance Trigger Rate
Pneumatic System Conditioning
Presentation transcript:

1 A/C Pressure Test and Evacuation

2 Leak Detection Leak detection must be done after every repair job. It must also be done anytime the appliance can not hold vacuum or pressure - like a low charge. If you are looking for a leak, look for oil spots on the piping at the source of a leak. Leak detection must be done after every repair job. It must also be done anytime the appliance can not hold vacuum or pressure - like a low charge. If you are looking for a leak, look for oil spots on the piping at the source of a leak.

3 Leak Test NEVER use compressed air to leak test. Compressed air mixed with some refrigeration oil will explode. Nitrogen is the acceptable method to leak test. Look for low side test pressure NEVER use compressed air to leak test. Compressed air mixed with some refrigeration oil will explode. Nitrogen is the acceptable method to leak test. Look for low side test pressure

4 Safety Rules Always wear safety glasses. Never use oxygen or acetylene to pressurize a system. – Oxygen will explode on contact with oil. Never use dry nitrogen without a regulator. – Nitrogen cylinders contain pressures in excess of 2000 psi. – The regulator reduces this pressure to a safe level. Always wear safety glasses. Never use oxygen or acetylene to pressurize a system. – Oxygen will explode on contact with oil. Never use dry nitrogen without a regulator. – Nitrogen cylinders contain pressures in excess of 2000 psi. – The regulator reduces this pressure to a safe level.

5 Methods of Leak Detection Pressurized with dry nitrogen (system not operational) – Use soap bubbles to find any leaks. R22 and Dry Nitrogen – Electronic – Halide – Soap Bubbles Pressurized with dry nitrogen (system not operational) – Use soap bubbles to find any leaks. R22 and Dry Nitrogen – Electronic – Halide – Soap Bubbles

6 Methods of Leak Detection Normal Operation – Use soap bubbles – Ultrasonic – Electronic – Halide Normal Operation – Use soap bubbles – Ultrasonic – Electronic – Halide

7 Leak Detection Methods Ultrasonic Older Electronic

8 Leak Detection Methods Ultraviolet Method Halide Torch

9 Leak Detection Methods Nitrogen Pressure Method

10 Electronic Testers Make sure when you are using electronic testers that the tip is actually over the leak. If the tip misses the refrigerant it will not find the leak.

11 Methods of Leak Detection Per the EPA Small Appliance Leaks Do Not Have to Be Repaired – If the appliance has under 5 pounds of charge. – If the appliance was charged in the factory. – Leak repair, however small is good and profitable service practice. Per the EPA Small Appliance Leaks Do Not Have to Be Repaired – If the appliance has under 5 pounds of charge. – If the appliance was charged in the factory. – Leak repair, however small is good and profitable service practice.

12 Leak Test (Running system) Steps to determine if a leak exists: – Check evaporator for temperature. – Check suction pressure – Check high side pressure (Careful) – Look for oil spots – Look for obvious line breaks – Check the sight glass (Careful) Steps to determine if a leak exists: – Check evaporator for temperature. – Check suction pressure – Check high side pressure (Careful) – Look for oil spots – Look for obvious line breaks – Check the sight glass (Careful)

13 Leak Test (Running system) Pressure readings alone are not determining factors of a refrigerant leak. The bubbles in a sight glass are not always indicators of a low charge. Do not rely on this. New refrigerants may show bubbles in a sight glass with a full charge. Pressure readings alone are not determining factors of a refrigerant leak. The bubbles in a sight glass are not always indicators of a low charge. Do not rely on this. New refrigerants may show bubbles in a sight glass with a full charge.

14 Evacuation – The removal of air and moisture from a refrigeration system. Vacuum – The pressures below atmospheric pressure, indicated by inches of mercury (HG) on a 0 to 30” scale. Evacuation – The removal of air and moisture from a refrigeration system. Vacuum – The pressures below atmospheric pressure, indicated by inches of mercury (HG) on a 0 to 30” scale.

15 Evacuation Noncondensibles – Substances which remain in a gaseous form (state) in a refrigeration system, such as nitrogen and oxygen. Micron – Unit of pressure measurements in millionths of meters of mercury. Noncondensibles – Substances which remain in a gaseous form (state) in a refrigeration system, such as nitrogen and oxygen. Micron – Unit of pressure measurements in millionths of meters of mercury.

16 Evacuation Single Stage Pump – Discharges directly into the atmosphere and is capable of pulling down to 1000 microns. Two Stage Pump – Discharges into a second vacuum and is capable of pulling down to.1 microns. Single Stage Pump – Discharges directly into the atmosphere and is capable of pulling down to 1000 microns. Two Stage Pump – Discharges into a second vacuum and is capable of pulling down to.1 microns.

17 Evacuation Low Vacuum – Vacuum of 2000 microns or more, obtainable with a single stage pump. High Vacuum – Vacuum of 2000 to.1 microns which requires a two stage pump. Deep Vacuum – Reducing the vacuum to between 200 and 50 microns. Low Vacuum – Vacuum of 2000 microns or more, obtainable with a single stage pump. High Vacuum – Vacuum of 2000 to.1 microns which requires a two stage pump. Deep Vacuum – Reducing the vacuum to between 200 and 50 microns.

18 Evacuation Reasons for evacuation: – To remove noncondensibles from the system. – To remove moisture from the system. Reasons for evacuation: – To remove noncondensibles from the system. – To remove moisture from the system.

19 Evacuation

20 Evacuation Effects of moisture in a refrigeration system: – Ice crystals will form at the metering device, stopping refrigerant flow. – Moisture combined with refrigerants creates acids. Hydrochloric acid Hydrofluoric acid Effects of moisture in a refrigeration system: – Ice crystals will form at the metering device, stopping refrigerant flow. – Moisture combined with refrigerants creates acids. Hydrochloric acid Hydrofluoric acid

21 Evacuation – Combined with refrigerant oil and heat moisture can create a sludge in the compressor and lines. – Moisture will cause a deterioration of the metal parts inside a refrigeration system. – Combined with refrigerant oil and heat moisture can create a sludge in the compressor and lines. – Moisture will cause a deterioration of the metal parts inside a refrigeration system.

22 Evacuation Effects of Air or Non- Condensibles in a refrigeration system: – Increases the discharge pressure – Stays in top of condenser Effects of Air or Non- Condensibles in a refrigeration system: – Increases the discharge pressure – Stays in top of condenser

23 Evacuation

24 Evacuation Effects of Ambient Temperatures on Evacuation: – Moisture is removed in a vapor state. – Boiling temperature will be reduced as pressure decreases. – Increasing the ambient temperature will decrease the evacuation time. Effects of Ambient Temperatures on Evacuation: – Moisture is removed in a vapor state. – Boiling temperature will be reduced as pressure decreases. – Increasing the ambient temperature will decrease the evacuation time.

25 Evacuation To reach a deep vacuum means the pressure is about 200 to 50 microns. – This is a slow process. – The deeper the vacuum the longer it takes. To reach a deep vacuum means the pressure is about 200 to 50 microns. – This is a slow process. – The deeper the vacuum the longer it takes.

26 Evacuation Checking the Vacuum 1.Reach the desired vacuum level. 2.Valve off the system from the vacuum pump and let it stand. 3.If pressure rises and stops 1.There is still moisture in the system. 2.Continue evacuation. Checking the Vacuum 1.Reach the desired vacuum level. 2.Valve off the system from the vacuum pump and let it stand. 3.If pressure rises and stops 1.There is still moisture in the system. 2.Continue evacuation.

27 Evacuation 4. If pressure continues to rise a leak is present. – Pressurize and leak check. 5. After leak is repaired continue evacuation. 4. If pressure continues to rise a leak is present. – Pressurize and leak check. 5. After leak is repaired continue evacuation.

28 Evacuation Trapped air and moisture: – Moisture may be trapped in the crankcase with the oil. Either run the crankcase heater to boil off the moisture (best method) Shake or agitate the compressor (strike with a rubber mallet) Trapped air and moisture: – Moisture may be trapped in the crankcase with the oil. Either run the crankcase heater to boil off the moisture (best method) Shake or agitate the compressor (strike with a rubber mallet)

29 Evacuation – Air / Moisture may be trapped under the valves in the cylinder of the compressor During the charged portion of the triple evacuation bump over (momentarily start) the compressor to release the trapped moisture. Never start a hermetic compressor under a deep vacuum or motor damage may occur. – Air / Moisture may be trapped under the valves in the cylinder of the compressor During the charged portion of the triple evacuation bump over (momentarily start) the compressor to release the trapped moisture. Never start a hermetic compressor under a deep vacuum or motor damage may occur.

30 Vacuum Measurement Compound Gauge – Not very accurate Electronic Vacuum Analyzer (gauge) – Measures Microns – 1000 Microns = 1 MM HG. – 759,000 Microns = Atmospheric Pressure Compound Gauge – Not very accurate Electronic Vacuum Analyzer (gauge) – Measures Microns – 1000 Microns = 1 MM HG. – 759,000 Microns = Atmospheric Pressure

31 System in a vacuum

32 Problems Sometimes the Schrader access valves can leak due to use and service problems. Replace core if any doubt.