MSR Effects Upon Secondary Cycle. ## # 666 Heater Drain Pump Main Steam Main Turbine #6 FWH MSR #5 FWH #4 FWH MOV Drain Tank Manual Valve AOV Note: Most.

Slides:



Advertisements
Similar presentations
An Introduction To Marine Steam Propulsion Plant [Source: US Navy]
Advertisements

Use of Regeneration in Vapor Power Cycles
CONTROLS OF SUPER CRITICAL BOILERS
Steam and Water Accessories
OFF DESIGN PERFORMANCE PREDICTION OF STEAM TURBINES
Rankine Cycle Figures from Cengel and Boles, Thermodynamics, An Engineering Approach, 6th ed., McGraw Hill, 2008.
What is STEAM MASTER WHAT IS STEAM MASTER? Thermoflow, Inc.
Circulating Water System
What is STEAM MASTER While STEAM PRO is the design program for conventional steam cycle plants, STEAM MASTER is the associated simulation program for off-design.
Vapor and Combined Power Cycles
Reheat cycle.
WHAT IS THERMOFLEX? Thermoflow Inc.
Walter G Bischoff Brunswick station Duke Energy
Marine Steam Power Plant Heat Balance By Steven Gelardi
Main Condensate & Feed Systems
ANY PIPE CONNECTION TO THE TURBINE IS A POTENTIAL SOURCE OF WATER EITHER BY INDUCTION FROM EXTERNAL EQUIPMENT OR BY ACCUMULATION OF CONDENSED STEAM.
EGR 334 Thermodynamics Chapter 4: Section 9-10
A Vapor Power Cycle Boiler T Turbine Compressor (pump) Heat exchanger
Thermal_Power_Plant_2 Prepared by: NMG
Cogeneration.
NEIL Requirements for Testing of FWH Electrical Equipment and AOV’s.
TURBINE & COOLING SYSTEM Presented By – AVIJEET PRATAP 07ME12 IET AGRA
ACADs (08-006) Covered Keywords Description Supporting Material
Cook Nuclear Power Plant
Introduction: True North Consulting, LLC Phone (970)
Vapor and Combined Power Cycles (2)
Unit 4 Exercise – Gas Vapour and Combined Power Cycle
Eric Backus FW System Engineer Exelon - LaSalle Station FSRUG Executive Board Member.
CMS CO2 Test Stand Specifications and Installation Status Erik Voirin Fermilab PPD - Process Engineering Group CMS CO2 Cooling Test Stand1.
Lesson 8 SECOND LAW OF THERMODYNAMICS
A Vapor Power Cycle Boiler T Turbine Compressor (pump) Heat exchanger
Chapter 10 VAPOR AND COMBINED POWER CYCLES
Analysis of Rankine Cycle with FWHs P M V Subbarao Professor Mechanical Engineering Department I I T Delhi Engineering solution to Pure Thoughts..…..
Lecture Objectives: Finish with absorption cooling Power generation Rankine cycles Connect power generation with heating and cooling –CHP –CCHP.
Page 1 Petten 27 – Feb ALFRED and ELFR Secondary System and Plant Layout.
ENGR 2213 Thermodynamics F. C. Lai School of Aerospace and Mechanical Engineering University of Oklahoma.
Presentation on Steam Power Plants R.C.Chaturvedi
ENGR 2213 Thermodynamics F. C. Lai School of Aerospace and Mechanical Engineering University of Oklahoma.
Hilario J. Negrón (787) ext 3223 (787) Measuring Operational Efficiency.
SNS COLLEGE OF ENGINEERING Coimbatore-107 Subject: Thermal Engineering
Review Questions Chapter 5
Chapter 10 VAPOR AND COMBINED POWER CYCLES
Chapter 10 VAPOR AND COMBINED POWER CYCLES
Heat Exchangers and Condensers
Objectives Evaluate the performance of gas power cycles for which the working fluid remains a gas throughout the entire cycle. Analyze vapor power.
VARIABLE EFFECTING EFFICIENCY OF RANKINE,REHEAT,REGENERATIVE CYCLE
Thermodynamics Cycles.
Thermodynamics Processes.
Lecture Objectives: Answer question related to Project 1 assignment
prepared by Laxmi institute tech. Mechanical eng. Department.
Simple Thermal Power Plant
TOPIC:- VAPOUR CYCLES CREATED BY:
Power and Refrigeration Systems
VAPOR & COMBINED POWER CYCLES
2012 Operating Experience for Feedwater and Related Systems
SNS COLLEGE OF ENGINEERING Coimbatore-107 Subject: Thermal Engineering
What is Desuperheater Water heater and its Applications?
Power Plant Technology Steam and Gas Cycle Power Plant (Assignment 1)
UNIT IV- Vapour Power Cycles
Pressurized Water Reactor
Leveraging Glass Panel Simulator Usage
By: JAGDEEP SANGWAN Refrigeration Basics 101.
Cogen, Regen Combined Cycle
Refrigeration and Air Conditioning
Refrigeration and Air Conditioning
What is a Turbine ? A Turbine is a device which converts the heat energy of steam into the kinetic energy & then to rotational energy. The Motive Power.
Generation of Most Eligible Steam for Rankine Cycle
Heat Recovery Steam Generators
Condenser in Power Plants
Presentation transcript:

MSR Effects Upon Secondary Cycle

## # 666 Heater Drain Pump Main Steam Main Turbine #6 FWH MSR #5 FWH #4 FWH MOV Drain Tank Manual Valve AOV Note: Most plants have a Heater Drain Tank between the FWH and HDP To LP Turbine

MSR Effects Upon Secondary Cycle There had been approximately 3 cycles (4-1/2 years) of continual FWH level alarms in the #4, #5 and #6 FWH. I&C would be sent at least once a week to try and adjust the tuning to stabilize the level control. Level control valves, positioners and diaphragms were experiencing degraded operation and pre-mature failures (Fisher V-Ball valves) due to the frequency and magnitude of the valve cycling. The level controllers were experiencing similar problems as the level control valves.

MSR Effects Upon Secondary Cycle What was not heard or listened to? I&C stated that the controls were maintaining FWH level BUT there would be a surge in the level THEN the FWH level control would try to respond AND this surge would cascade through the FWH string!! The FWH level swings started WHEN we installed the new MSR’s!!

MSR Effects Upon Secondary Cycle What given information do we need to validate our assumption(s)? FWH operation: What do we know about inlet flows? (extraction steam, cascaded & MSR drainage) 1.Constant unit load results in constant extraction steam flows. 2.Varying inlet drain flows can cause erratic FWH levels due to cascaded drainage from one FWH to the next. 3.Varying flows from the MSR’s can occur due to drain tank level control or some other anomaly in the MSR.

MSR Effects Upon Secondary Cycle MSR operation: What do we know about inlet MSR drain flows? (2 nd pass drain, 4 th pass drain, separator drain) 1.Constant unit load results in constant turbine exhaust flow as well as the volume of moisture removed from the turbine exhaust steam flow. The separator drain flow must be constant. 2.2 nd pass drain flow was constant due to a stable level in the drain tank and stable level control valve position. 3.4th drain flow could not be determined due to a lack of instrumentation.

MSR Effects Upon Secondary Cycle ## # 666 Heater Drain Pump Main Steam Main Turbine #6 FWH MSR #5 FWH #4 FWH MOV Drain Tank Manual Valve AOV Note: Most plants have a Heater Drain Tank between the FWH and HDP To LP Turbine

MSR Effects Upon Secondary Cycle MSR operation: How do we verify if the drain flow is stable and remembering that the problem of FWH level alarms started WHEN we installed the new MSR’s!! Reviewed EPRI TR Reviewed the scope of the MSR commissioning. Based upon EPRI-We needed to verify if there is condensate slugging from the 4 th pass drain!!

MSR Effects Upon Secondary Cycle What was outcome of the performance of the manufacturer’s commissioning protocol (ASME Performance Test Code 12.4)? Answer: We did NOT satisfy the manufacturer’s protocol !! The protocol required achieving 10 to 20 F of sub-cooling and we had 0 F of sub-cooling!! Consulted EPRI publications : MSR Source Book, : Level Control Guide for Feedwater Heaters, Moisture Separator/Reheaters, and Other Equipment Sub-cooling is the temperature difference between the saturated steam entering the heaters (1 st pass) and the temperature of the condensate existing the MSR (4 th pass).

MSR Effects Upon Secondary Cycle ## # 666 Heater Drain Pump Main Steam Main Turbine #6 FWH MSR #5 FWH #4 FWH MOV Drain Tank Manual Valve AOV Note: Most plants have a Heater Drain Tank between the FWH and HDP To LP Turbine

MSR Effects Upon Secondary Cycle >>>> CONDENSATE SLUGGING!! The manufacturer’s protocol was implemented to achieve 10 to 20 F of sub- cooling. (ASME PTC 12.4) We throttled the Manual Valve and monitor the manufacturer’s thermocouples to achieve approximately 20 F of sub-cooling.

MSR Effects Upon Secondary Cycle Outcome: We achieved closer to 20 F of sub-cooling. The FWH levels stabilized. Went from 30 to 50 level alarms per day to maybe one or two a week-that as fast as the alarm annunciated-the alarm cleared. I&C was able to fine tune the FWH level control. The stability of the turbine driven MFP improved since the flow from the heater drain pumps stabilized.

MSR Effects Upon Secondary Cycle The MSR’s were 20% oversized for future EPU and there were further savings to be realized. The main steam flow was throttled to the MSR steam heater (reheater section) by closing the inlet AOV and throttling the MOV. Results: Achieved an additional 8 MW e !! NOTE: There is still more room to throttle to achieve further increase in MW e.

MSR Effects Upon Secondary Cycle ## # 666 Heater Drain Pump Main Steam Main Turbine #6 FWH MSR #5 FWH #4 FWH MOV Drain Tank Manual Valve AOV Note: Most plants have a Heater Drain Tank between the FWH and HDP To LP Turbine

MSR Effects Upon Secondary Cycle Future Considerations: Achieved an additional MW e !! NOTE: There is still more room to throttle to achieve further increase in MW e. A graph of MW e verses valve position needs to be trended to determine were the peak in MW e occurs (Brayton Point) which would be the stopping point.