1 INTRUSION ALARM TECHNOLOGY POWER SUPPLIES. 2 INTRUSION ALARM TECHNOLOGY Security systems shall have a primary power source and a secondary power source.

Slides:



Advertisements
Similar presentations
The D.C. Scout Battery Distribution System Ground Locator
Advertisements

EMerge Browser Managed Security Platform Module 2 Hardware install.
2014 NEC Code Changes Ted “Smitty” Smith E Light Electric.
BPS12 Battery Power Supply. December 2003 Page 2 Better Than Standard UPS systems Longer battery life –unique charging scheme DC power output –instead.
BSA Electricity Merit Badge Electricity Merit Badge AC Alternating Current.
ELECTRICAL SYSTEMS 21.3.
Circuits. 1.Identify a parallel circuit. 2.Determine the voltage across each parallel branch. 3.Determine the current across each parallel branch. 4.Apply.
20.3 Electric Circuits Key Concepts What is included in a circuit diagram? How do series and parallel circuits differ? How do you calculate electrical.
EET Survey of Electronics
Electrical Power Systems
The Association of Electrical and Medical Imaging Equipment Manufacturers Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical.
Electric Circuits.
© 2011 Ericson Manufacturing, Willoughby, Ohio
CCTV SYSTEMS CAMERA POWER SUPPLIES.
Residential Wiring By: Ing. Hector M Lugo-Cordero, MS 03/25/2009.
INTRUSION ALARM TECHNOLOGY
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
Purpose Power lines Equipment Assured Grounding GFCI Conclusion.
To bring electric current into a building, an electrician installs wiring. In a house, all of the wires usually come from one main box.
INTRUSION ALARM TECHNOLOGY
Residential Construction Unit 5- Energy Efficiencies and Mechanicals Mr. Todzia.
ELECTRICITY. Electric Current  Currents are the rate that electricity flows thru a wire  2 types of currents:  Alternating Current (AC) electricity.
L 27 Electricity and Magnetism [4]
JEOPARDY GreenAnythingGoes MeasurePowerConnectionsElectricity Micro Comp. Final.
Electrical Power Systems
Electricity and power supplies
Applied Circuit Analysis Chapter 3 - Power and Energy Copyright © 2013 The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Parallel wiring in the circuit breaker panel!. No matter which path the river takes, its change in elevation, from the mountaintop to the plain, is the.
Series and Parallel Circuits Making Electricity Work for Us.
20.3 Electric Circuits
 Safety  Protective devices - devices designed to automatically limit or shut off the flow of electricity in the event of a ground-fault, over-load or.
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Home Electrical Wiring Types of Receptacles and Wiring them for 120v – 15Amp/20Amp.
Home Electrical Systems. Behavior Objectives  Define the basics of Electrical Systems  Explain the basic principles of Electricity.  Describe the different.
1 comes from the electrons in an atom when they are transfered them between objects. + + electrons have a negative (-) charge.
My Book of Circuits Open ClosedSeries Parallel Short Name Class Period Date.
PR570 POWERITE II TRAINING Dedicated to Success in Electronic Servicing for 50 Years.
Concepts of Engineering and Technology Basic Electricity and Electronics: DC Circuits Copyright © Texas Education Agency, All rights reserved. 1.
Electrical Safety in the Home 1.Circuit Breakers 2.Fuses 3.Wall Outlets 4.Circuit Breakers 5.GFCI/RCD.
ELECTRICAL SYSTEMS. Chapter Twenty One: Electrical Systems  21.1 Series Circuits  21.2 Parallel Circuits  21.3 Electrical Power.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
Basic Equipment and Schematic Reading. Objectives Learn the basic equipment that will be used in the Lab. Learn some of the basic symbols used on electrical.
Unit 13 Electric Circuits
What makes substation work?
Electrical Testers Basic test equipment used in today’s shops may include an analog type meter, a VAT (Volt-Amp-Tester), DMM (Digital Multimeter),
ELECTRICAL WIRING WIRING BASICS Written by Bobby Joslin
Series and Parallel Circuits
Electrical Repair and Maintenance
Every electrical system must have three parts, a source, a load, and a circuit.  Source - the origin of electrical potential, such as a battery or 120.
Making Circuits Safe SNC1P1 Findlay.
Open Parallel Closed Series Short My Book of Circuits.
Electrical Systems Civil Engineering and Architecture
Elevator Control Unit.
Water Efficient Plumbing Fixtures Required: Kitchen Remodel Tip Sheet
Circuit Protection Unit 9.
Lighting Branch Circuit and Small-Appliance Circuits for Kitchen
Electrical Systems Electrical Systems
Smitty’s Two Minute Drill Mixed Content -05
The D.C. Scout Battery Distribution System Ground Locator
HVI HIPOT TEST SET Pft sERIES.
Your Inspection Business Name Goes Here.
Outlet Branch Circuit Arc Fault Circuit Interrupter (OBC AFCI)
The Safe Use of Electricity
Circuits.
Conductor A material, such as copper, that permits the flow of electricity; usually refers to the a wire.
Objectives Learn about Electricity Pricing Electric systems.
Chapter Twenty One: Electrical Systems
Objectives Review conductor and conduit selection
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Presentation transcript:

1 INTRUSION ALARM TECHNOLOGY POWER SUPPLIES

2 INTRUSION ALARM TECHNOLOGY Security systems shall have a primary power source and a secondary power source. The primary power source shall be provided by a 20 amp source and it should be a dedicated outlet, if the outlet is not dedicated it shall not exceed combined load of 20 amps. Security systems shall have a primary power source and a secondary power source. The primary power source shall be provided by a 20 amp source and it should be a dedicated outlet, if the outlet is not dedicated it shall not exceed combined load of 20 amps.

3 INTRUSION ALARM TECHNOLOGY THE PRIMARY POWER OUTLET SHALL NOT BE A SWITCHED OUTLET. If an existing outlet is to be used you should verify that it can’t be shut off by a wall switch. The outlet should not be a GFCI or an arc fault outlet either, if the outlet trips it will put unnecessary wear on the battery backup. THE PRIMARY POWER OUTLET SHALL NOT BE A SWITCHED OUTLET. If an existing outlet is to be used you should verify that it can’t be shut off by a wall switch. The outlet should not be a GFCI or an arc fault outlet either, if the outlet trips it will put unnecessary wear on the battery backup.

4 INTRUSION ALARM TECHNOLOGY Surge protection should be provided to prevent system damage and eliminate false alarms from electrical surges or spikes. Receptacles for dedicated kitchen, dining rooms, laundry or other such circuits should not be used for alarm systems. Surge protection should be provided to prevent system damage and eliminate false alarms from electrical surges or spikes. Receptacles for dedicated kitchen, dining rooms, laundry or other such circuits should not be used for alarm systems.

5 INTRUSION ALARM TECHNOLOGY The primary power for alarm systems is delivered by a class 2 power limiting device like a power transformer. These transformers are hardwired by the installer. The primary power for alarm systems is delivered by a class 2 power limiting device like a power transformer. These transformers are hardwired by the installer.

6 INTRUSION ALARM TECHNOLOGY Typical voltages for burglar alarm systems can range from 9VAC to 17VAC at 20VA to 50VA. The screw is designed to secure the power pack to the outlet and is not used as a ground connection. These transformers should be screwed to the outlet to prevent accidental disconnection. Typical voltages for burglar alarm systems can range from 9VAC to 17VAC at 20VA to 50VA. The screw is designed to secure the power pack to the outlet and is not used as a ground connection. These transformers should be screwed to the outlet to prevent accidental disconnection.

7 INTRUSION ALARM TECHNOLOGY The cable used for wiring the transformer is called lamp cord or zip cord. It’s an 18/2 cable and looks like the cords used on traditional lamps, hence the name lamp cord. The cable used for wiring the transformer is called lamp cord or zip cord. It’s an 18/2 cable and looks like the cords used on traditional lamps, hence the name lamp cord.

8 INTRUSION ALARM TECHNOLOGY Because the transformer is plugged into an AC power source polarity doesn’t matter, so you do not need to use polarized wire. Polarized wire simply has a white stripe on one side to indicate the ground or negative side of the cord, this mark is also commonly found on speaker wire. Because the transformer is plugged into an AC power source polarity doesn’t matter, so you do not need to use polarized wire. Polarized wire simply has a white stripe on one side to indicate the ground or negative side of the cord, this mark is also commonly found on speaker wire.

9 INTRUSION ALARM TECHNOLOGY The power cord from the transformer up to the control panel should be placed in wire mold to protect the cable and keep it from being accidently snagged or caught on anything.

10 INTRUSION ALARM TECHNOLOGY The secondary power must be an approved generator or back up battery for the intrusion alarm system. The battery back up must maintain the system in idle condition for four hours. The secondary power must be an approved generator or back up battery for the intrusion alarm system. The battery back up must maintain the system in idle condition for four hours.

11 INTRUSION ALARM TECHNOLOGY If the system is a combination burglar fire alarm system the secondary power must maintain the system in non-alarm mode for 24 hours. This doesn’t apply to a burglar alarm system that incorporate smoke detectors. The secondary power must activate within 10 seconds after primary power is lost. If the system is a combination burglar fire alarm system the secondary power must maintain the system in non-alarm mode for 24 hours. This doesn’t apply to a burglar alarm system that incorporate smoke detectors. The secondary power must activate within 10 seconds after primary power is lost.

12 INTRUSION ALARM TECHNOLOGY When the system diverts to battery back up the keypad should indicate that the system is using battery back up. If primary power is working and the system keypad indicates battery, then the circuit breaker is probably tripped an should be addressed immediately. Most systems will also indicate low battery. When the system diverts to battery back up the keypad should indicate that the system is using battery back up. If primary power is working and the system keypad indicates battery, then the circuit breaker is probably tripped an should be addressed immediately. Most systems will also indicate low battery.

13 INTRUSION ALARM TECHNOLOGY Batteries for intrusion systems are typically sealed lead acid (SLA) batteries. The batteries are rated by voltage and amp hours (Ah). Amp hours indicate how long the battery will supply power (hours) based on how many amps are being drawn from the system (amps). Batteries for intrusion systems are typically sealed lead acid (SLA) batteries. The batteries are rated by voltage and amp hours (Ah). Amp hours indicate how long the battery will supply power (hours) based on how many amps are being drawn from the system (amps).

14 INTRUSION ALARM TECHNOLOGY Manufactures will provide the minimum specifications for battery back up, i.e. 12VAC-4Ah. These specifications will cover the minimum 4 hour back up time. If the customer wants a longer back up time you will have to calculate the amp hour requirements for the system. Manufactures will provide the minimum specifications for battery back up, i.e. 12VAC-4Ah. These specifications will cover the minimum 4 hour back up time. If the customer wants a longer back up time you will have to calculate the amp hour requirements for the system.

15 INTRUSION ALARM TECHNOLOGY The installation manual will provide you with the amperage draw of each device connected to the system. They may even provide a work sheet for determining amp hours. If you’re using generic devices on a burglar alarm system you can get the specs for each device from that manufactures installation form. The installation manual will provide you with the amperage draw of each device connected to the system. They may even provide a work sheet for determining amp hours. If you’re using generic devices on a burglar alarm system you can get the specs for each device from that manufactures installation form.

16 INTRUSION ALARM TECHNOLOGY Bottom line is you want to add up all of the amperages for all of the devices connected to the system. Multiply the total current times the number of back up hours desired and it will equal the total amp hours needed AMPS x HOURS = Ah Bottom line is you want to add up all of the amperages for all of the devices connected to the system. Multiply the total current times the number of back up hours desired and it will equal the total amp hours needed AMPS x HOURS = Ah

17 INTRUSION ALARM TECHNOLOGY Alarm devices typically draw milliamps so you will need to convert milliamps to amps. A key pad may draw 50 mA or.05 amps, to convert from milliamps to amps you move the decimal point 3 places to the left. It is easier to add all of the device amperages first and then convert them to amps. Alarm devices typically draw milliamps so you will need to convert milliamps to amps. A key pad may draw 50 mA or.05 amps, to convert from milliamps to amps you move the decimal point 3 places to the left. It is easier to add all of the device amperages first and then convert them to amps.

18 INTRUSION ALARM TECHNOLOGY Here is an example of a current draw worksheet with the part number and the current it uses, notice that you need to indicate how many of each device your installing.

19 INTRUSION ALARM TECHNOLOGY If we add up all of the amperages assuming we are only installing one of each, the sum equals 785mA (15 & 35mA was used for the two with the subscript ). The control panel uses approximately 100mA, 785mA + 100mA + 885mA. 885mA converted to amps =.885 amps. If we add up all of the amperages assuming we are only installing one of each, the sum equals 785mA (15 & 35mA was used for the two with the subscript ). The control panel uses approximately 100mA, 785mA + 100mA + 885mA. 885mA converted to amps =.885 amps.

20 INTRUSION ALARM TECHNOLOGY If the customer wants 24 hour back up for the system then we would multiply.885 x 24 hours = 21.24Ah. This would require installing three 12VAC 7Ah hour batteries. In order to increase amperage the batteries will need to be connected in parallel, to increase voltage batteries are connected in series. If the customer wants 24 hour back up for the system then we would multiply.885 x 24 hours = 21.24Ah. This would require installing three 12VAC 7Ah hour batteries. In order to increase amperage the batteries will need to be connected in parallel, to increase voltage batteries are connected in series.

21 INTRUSION ALARM TECHNOLOGY Batteries connected in series and parallel, notice the outputs of each;

22 INTRUSION ALARM TECHNOLOGY If there isn’t any room in the panel for three batteries then another enclosure will need to be added to house the batteries. A piece of conduit should be installed between the two enclosures. If there isn’t any room in the panel for three batteries then another enclosure will need to be added to house the batteries. A piece of conduit should be installed between the two enclosures.