Refrigeration Components

Slides:



Advertisements
Similar presentations
Basic Refrigeration, Its Components, and Its Cycle
Advertisements

Automotive A/C systems
Refrigeration Basics 101 By: Eric Nelson.
Refrigeration Systems
Truck-Trailer Refrigeration Equipment
Coach Air Conditioning
Chapter 4 Air-Conditioning Components
Mobile Air Conditioning
ADX 150 – Engine Repair ADX 170 – Climate Controls
General System Maintenance BUS 4 COMPONENT FLOW.PPT
Student CD for Commercial Refrigeration for A/C Technicians
Basic Refrigeration Cycle
Left Side Discharge Pressure Regulator
Refrigeration Flow Control
Tennessee Technology Center Center at Pulaski. Superheat & Sub-cooling A Technician’s Guide to HVACR Diagnostics.
COMMERCIAL REFRIGERATION
HVACR312 - Refrigeration Metering Devices.
Section 5: Commercial Refrigeration
Introduction to Air Conditioning
COMMERCIAL REFRIGERATION UNIT 25
Product Introduction.
Trouble Shooting and Performance Testing
Evaporators For Air Conditioning
STEAM HEATING.
Hydronic Mechanical Controls
SYSTEM COMPONENTS CHAPTER 5page 91C & 93 L. OBJECTIVES l IDENTIFY AND COMPARE THE STATE OF REFRIGERANT IN EACH SECTION OF A/C SYSTEM. l EXPLAIN PURPOSE.
CHAPTER 6 Moving Heat: Heating and Air Conditioning Principles
Air Conditioning in tropical climates Presented by Ranjeet Kumar Nayak.
Air Conditioning Metering Devices.
Refrigeration Basics 101.
The Refrigeration Process
Pressure-Enthalpy and the Variable Refrigerant Cycle
Introduction to Energy Management
Refrigeration Systems
TITLE OF THE PROJECT:- AUTOMOBILE AIR CONDITIONING AIM OF THE PROJECT:- TO STUDY ABOUT AIR CONDITIONING SYSTEM OF AN AUTOMOBILE PRESENTED BY: INAMUL.
7 A/C System Components, Operation, and Service.
AIR CONDITIONING (COOLING)
James McIntyre VRF Training Manager V5 Key Components.
CHAPTER 6 Basic Refrigeration Systems. CHAPTER 6 Basic Refrigeration Systems.
Teknologi dan Rekayasa Air Condition System Component.
SNS COLLEGE OF ENGINEERING Coimbatore-107 Subject: Thermal Engineering
Understanding the system.
Fixed Orifice Tube Cycling Clutch System (FOTCC)
Fixed Orifice Tube Cycling Clutch System (FOTCC)
Pressure Regulators KVR + NRD Presentation , Jbm - Page 1.
Heat Transfer and Refrigeration Cycle
TXV Devices.
Automotive Heating And Air Conditioning
GROUND SERVICING OF VARIOUS SUB SYSTEMS
Visit for more Learning Resources
Fixed Orifice Tube Cycling Clutch System (FOTCC)
R1 Fundamentals of Refrigeration
SNS COLLEGE OF ENGINEERING Coimbatore-107 Subject: Thermal Engineering
Refrigeration Basics By: Mohamed Iqbal Pallipurath.
R3 Controls, Valves, Accessories & Heat Pumps
1 Mobile Air Conditioning Basic A/C Operation. 2 System Components All systems contain six major components: Compressor to circulate the refrigerant Condenser.
Student CD for Commercial Refrigeration for A/C Technicians Chapter 6 Controls and Accessories.
Scotsman Refrigeration 101
Refrigeration and Air conditioning
R1 Fundamentals of Refrigeration
By: JAGDEEP SANGWAN Refrigeration Basics 101.
Air Treatment School Refrigerated Dryer Training
Presentation transcript:

Refrigeration Components CHAPTER Refrigeration Components 14 Instructor Name: (Your Name)

Learning Objectives Describe the purpose of the compressor, condenser, metering valve, and evaporator. Explain the construction of the compressor, condenser, metering valve, and evaporator. Illustrate the operation of service valves and Schrader valves. Describe the purpose and construction of a vibrasorber.

Learning Objectives (continued) Demonstrate the operation of a thermostatic expansion valve. Explain the superheat setting of the TXV. Describe the mounting location of a sensing bulb. Determine the superheat setting of the TXV. Explain the purpose of the distributor. Describe the purpose of the receiver tank.

Learning Objectives (continued) Compare the drier materials and explain the purpose of the filter dryer. Describe the purpose and operation of the heat exchanger Describe the purpose and operation of the accumulator. Explain the purpose of pressure regulating devices. Describe the purpose and operation of the different types of refrigerant safety valves.

The Four Basic Component The Compressor The Condenser The Metering Device The Evaporator Refrigerant, the fifth basic component

Four Cylinder Compressor

The Compressor Pumps refrigerant through the system Pressurizes the vapor refrigerant Raises the temperature of the refrigerant Draws a very low suction pressure High discharge and low suction pressures help control the boiling of the refrigerant

Compressor Operation Refrigerant passes through suction throttling valve (if equipped) into compressor crankcase. Piston moves down cylinder, refrigerant is drawn in through suction reed valve. Piston moves upward, refrigerant compresses to 50:1 ratio. Compressed vapor exits through the discharge valve plate to discharge manifold.

Compressor Cycle

Service Valves Located on compressor suction and discharge ports Allows service manifold connection Can isolate the compressor for service or repairs Back seated- isolates service port Mid seat- opens service ports Front seat- isolates compressor from system

Service Valves

CAUTION Care must be taken to NEVER front seat the discharge service valve while the compressor is operating. Even thought the high pressure cut-out switch might be positioned below the valve, it would not operate fast enough to prevent major damage to the compressor and prevent possible personal injury.

Schrader Service Valves

Vibrasorbers Flexible suction and discharge lines Positioned at the compressor Prevent engine and compressor vibrations from reaching the copper piping of the refrigerant system There are two types of vibrasorbers Typical discharge vibrasorbers are made up of bellows shaped stainless steel center and a covering of braided stainless steel wire Typical suction vibrasorber made up of reinforced fabric covered hoses, often using replaceable mechanical fittings

Vibrasorbers

Condenser Located outside of controlled space Releases heat from controlled space to outside air Consists of copper tubing running through aluminum cooling fins Refrigerant changes state from a high pressure hot vapor to high pressure cooler liquid

Condenser

Receiver Tank Acts as storage tank for refrigerant Usually contains one or two sight glasses Usually have inlet and outlet service valve Refrigerant can be isolated between receiver and compressor for downstream service

Receiver Tank

Filter Dryer Filters and dries refrigerant Located in liquid line between receiver outlet and TXV May be between compressor and condenser May be between evaporator and compressor Three different materials commonly used Silica Gel Activated Alumina Molecular Sieve

Filter Dryer

Moisture Indicator

Heat Exchanger Located in liquid line between receiver and TXV or outlet of evaporator Two important functions: Subcools liquid refrigerant before TXV Evaporates any liquid refrigerant before it reaches the compressor

Heat Exchanger

Thermal Expansion Valve Division between high and low side of system Modulates the flow of refrigerant to the evaporator Monitors evaporator outlet temperature Internal or external equalization

Thermal Expansion Valve

Thermal Expansion Valve Operation Sensing bulb pressure applied to one side of the diaphragm tries to open valve against spring pressure. Evaporator outlet or compressor suction pressure applied to the opposite side of the diaphragm helps to make the valve responsive to compressor suction pressure. Spring pressure, which is applied to the needle assembly and diaphragm on the evaporator side, constantly tries to close the valve.

Determining Superheat Determine the suction pressure at the compressor suction service valve. Using a refrigerant pressure temperature chart, determine the saturation temperature at the observed pressure. Measure the temperature of the suction gas at the evaporator outlet. Subtract the saturated temperature read from the chart in Step 2 from the temperature measured in Step 3. The difference between the two is the superheat of the suction gas returning to the compressor.

TXV Sensing Bulb TXV sensing bulb regulates the flow of refrigerant to the evaporator Bulb is normally filled with same refrigerant used in the system Charge can be vapor or liquid Some are designed to control the maximum opening pressure of the TXV to prevent compressor slugging Sensing bulb must have good mechanical connection with the evaporator outlet

TXV Sensing Bulb (continued) Sensing bulb must be positioned on the suction line so it can monitor actual vapor or line temperature, follow manufacturers recommendations If mounted at 6 o’clock, refrigerant oil can provided insulation from true vapor temperature If mounted at 12 o’clock bulb would be in direct contact with line possibly causing incorrect sensing of vapor temperature

Distributor Tube Distributor and header are located between the TXV outlet and evaporator inlet Divides the refrigerant flow into several routes to the evaporator for greater efficiency Equipped with a passage so that during the heating and defrost cycle, hot gas is pumped into the evaporator, bypassing the TXV

Evaporator Receives boiling refrigerant from the distributor As refrigerant boils it absorbs heat through the cooling fins which cools the air as it passes through them Refrigerant boils because of the pressure of the refrigerant is significantly lowered by the TXV Moist air can freeze on the fins reducing efficiency, a defrost cycle is needed to prevent this Most evaporators are constructed of copper tubing swedged into aluminum fins. Tubing configuration and number of tubes determine the BTU rating of evaporator

Evaporator

Accumulator Separates liquid refrigerant from vaporous refrigerant before entering the compressor When system is operating intermittently or as heat pump, large quantities of liquid refrigerant can pass through suction line and enter the compressor Liquid refrigerant can cause broken pistons, bent connecting rods, broken valves, blown head gaskets, and damaged bearings Accumulator normally has the capacity to hold the entire refrigerant charge to prevent compressor damage

Accumulator

Accumulator Operation Liquid and vapor enter accumulator and drop to the bottom Vapor returns through “U” shaped tube to compressor As vapor passes “U” tube it picks up liquid refrigerant and oil through metering hole in bottom of “U” tube To prevent to much liquid refrigerant from returning to compressor an anti-siphon hole is placed at the top of the “U” tube To aid in the evaporation process of the accumulator a device to heat the shell of the may be added

Evaporator Pressure Regulator Evaporator pressure regulator controls evaporator pressure regardless of compressor suction pressure The pressure setting is that which is equal to 30 to 32 degrees Fahrenheit inside the evaporator coil Oil by pass line between the base of the evaporator to the compressor suction is required This type of valve not used in many application because many cargos require the evaporator to reach very low pressures in order to obtain low box temperatures

Suction Pressure Regulator Designed to limit crankcase suction pressure during heat and defrost cycle or startup During startup when evaporator and crankcase pressures are high, valve is closed When the crankcase internal suction pressure is below the set point of the valve, it begins to open and lower evaporator pressure As the pressure of the evaporator is lowered the valve setting, it opens still more

Suction Pressure Regulator (continued) During defrost/heat cycle high pressure vapor is pumped from compressor to the distributor and evaporator, suction pressure rises. High pressure overcomes spring pressure in the valve and closes the inlet cutting off inlet flow of refrigerant The restriction caused by the valve provides needed restriction for compressor to pump against during heat/defrost cycle

Suction Pressure Regulator (continued) This process causes compressor to pump high-pressure (temperature) refrigerant to evaporator for heating/defrost cycle Suction pressure regulators do not totally restrict refrigerant flow, they do not require oil bypass line These valves are adjustable by increasing or decrease spring pressure

Pressure Regulating Devices

Safety Valves Most refrigeration units with more than 1 pound of refrigerant are equipped with a pressure relieving safety device Prevent possible explosion by relieving pressure caused by fire, coil blockage, or overheating of unit 2 types currently used, spring loaded and fusible metal plug Spring loaded type has spring loaded piston that excessive refrigerant pressure must overcome and vent through an exhaust port passage

Safety Valves (continued) Piston type may have slight refrigerant leak after venting but should reseal itself Fusible metal plug work on temperature only, usually 200 to 22 degree Fahrenheit or about 415 to 450 psi The core material is designed to melt away, allowing refrigerant to escape Once a fusible plug releases pressure they must be replaced

Safety Valves Fusible Plug Spring-loaded Piston

Summary There are four main components used in a refrigeration system There are many other components that improve the efficiency of the system but not necessary From the compressor superheated refrigerant passes service valves through the vibrasorber Vibrasorbers isolates system from vibration caused by engine and compressor

Summary (continued) Refrigerant then enters the condenser and gives up heat to ambient air Refrigerant cools in the condenser and condenses from gas to liquid Liquid refrigerant then enters the receiver where it is stored until needed Refrigerant leaves receiver and passes through the filter dryer which removes moisture and contaminants Refrigerant enters the heat exchanger which further removes heat from liquid refrigerant

Summary (continued) Refrigerant enters TXV and is metered to the distributor and then evaporator TXV balances inlet flow to outlet temperature and pressure of refrigerant so it all has time to change state from liquid to a gas before exiting evaporator Refrigerant then enters the accumulator if system is equipped Accumulator separates vapor to prevent liquid from entering the compressor

Summary (continued) Refrigerant flows from accumulator through suction line, through suction vibrasorber, through suction service valve, then through suction pressure regulator if equipped Regulator controls the load placed on the engine or electric motor Refrigerant flows out suction pressure regulator into suction side of compressor The refrigerant is then compressed and starts the journey again