E People and ideas you can trust. TM ©2014 Daikin Applied Seasonal Equipment Operational Considerations Joe Leichner, Daikin Applied Strategic Sales Project.

Slides:



Advertisements
Similar presentations
Sustainable School Design Creating Healthy, High Performance School Facilities Presented by Stephen M. Koontz, Energy Services Leader, Tampa Bay Trane.
Advertisements

Chapter 3. HVAC Delivery Systems
HVAC Basics Bin Yan HVAC – Heating, Ventilation, Air-conditioning.
BUILDING AIR CONDITIONING
Improve Facility Operation through Commissioning-A Case Study Mingsheng Liu, Ph.D., P. E. University of Nebraska.
HEALTHCARE BUILDING AUTOMATION
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Commercial Mechanical Requirements
TYPES OF MECHANICAL SYSTEMS
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Foundations of Real Estate Management BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building ®
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
Innovative Air Distribution for Healthcare Facilities.
Mechanical Engineering Department  Temperature Control  Cooling  Heating  Humidity Control  Humidification  Dehumidification  Air Quality Control.
University of Iowa Indoor Practice Facility Outside-the-box HVAC Lincoln Pearce, PE – KJWW Engineering David Hahn – University of Iowa Chilled Water Plant.
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
Engineer Presentation
Energy Saving DDC Control Strategies
HVAC Systems Overview HVAC Overview - # 1 Tom Lawrence
Energy Management with the use of an Intelligent Building Management System.
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
44 th Annual Conference & Technical Exhibition By Thomas Hartman, P.E. The Hartman Company Georgetown, Texas Sustainable Chilled Water.
Jim Chmielewski – HVAC Sales Manager Emerson Control Techniques
UTSW Thermal Energy Plants, Power Generation and Electrical System What do we do to meet the Emission Reduction, Energy usage Reduction and Electrical.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
September 18, 2009 Critical Facilities Round Table 1 Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
1 Medical Office Building. 2 Occupancy – 400 persons 8 a.m. – 5 p.m. Monday - Friday Building Characteristics Three stories 40,000 square feet (200’ x.
Temperature Control Loop
NOVO ETS IMPROVING YOUR ORGANIZATIONS’ ENVIRONMENTAL, HEALTH AND SAFETY PERFORMANCE ENERGY MANAGEMENT IN THE CONTEXT OF GREEN PRODUCTIVITY.
N VAV system varies the air quantity rather than temperature to each zone n Single main duct is run from AHU n Branch duct are run from this main through.
AIA Guidelines for Design and Construction of Hospital and Healthcare Facilities Presented By: Michael A. Rogers, PE
Sizing Variable Flow Piping – An Opportunity for Reducing Energy
How Facilities Can Help Commitment by facilities director Facilities energy committee Energy officer position Include conservation commitment in: Strategic.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
Facilities Management and Design Chapter 7 HVAC Systems.
HEATING AND COOLING SYSTEMS
Authors: William Tschudi, Lawrence Berkeley National Lab Stephen Fok, Pacific Gas and Electric Company Stephen Fok, Pacific Gas and Electric Company Presented.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
7/15/2002PP.AFD.09 1 of 43 Yaskawa Electric America Variable Frequency Drives In HVAC Applications.
ANNEXE OFFICE CONVERSION. Heating Operation Two gas fired boilers provide hot water to two separate circuits, a constant temperature circuit and a variable.
The key to comfort and reduced fuel use for all heating and cooling The key to comfort and reduced fuel use for all heating and cooling.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Maria’s Restaurant Chapter 2 Section 9
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
The Data Center Challenge
Story of No-Cost Energy Savings at Ohio Union
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Lecture Objectives: Answer questions related to HW 4
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
Munters DH Systems for Hospital Applications
Lecture Objectives: Answer questions related to HW 4
Energy Efficiency in District Coiling System
Chilled Beam Performance:
HCB 3-Chap 19A: All-Air Systems_Single Zone
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Technician’s Guide and Workbook for Zoning Section 1: Introduction
Lecture Objectives: Discuss HW4 parts
The key to comfort and reduced fuel use for all heating and cooling
FBE03: Building Construction & Science
Objective Revie the Cooling Cycle Learn about air distribution systems
Presentation transcript:

e People and ideas you can trust. TM ©2014 Daikin Applied Seasonal Equipment Operational Considerations Joe Leichner, Daikin Applied Strategic Sales Project Developer September 9, 2014

©2014 Daikin Applied Agenda 1. “Seasonal” – Means not full load heating or cooling! 2. Controls settings to save energy and optimize comfort 3. Designing/selecting new systems for replaced equipment Page 2

©2014 Daikin Applied Seasonal = 99.9% of the Year Page 3 Historical data and choosing weather criteria for a hospital: 1.If there is a “worst-case scenario”, your hospital will see it. 2.Seems to not account for north winds through north-facing outside air dampers! 3.Does not account for 100 and -10 degree F. days. 4.When designing a new building, help guide your design team. 5.Systems and equipment degrade in performance and capacity. 6.Bigger equipment will help handle “peak” loads, but affect efficiency at part-load. 7.Diversity is tough to estimate, but it very important to equipment selection and operation.

©2014 Daikin Applied Heating Design Temperatures Page 4

©2014 Daikin Applied Cooling Design Temperatures Page 5

©2014 Daikin Applied Seasonal = 99.9% of the Year Page 6

©2014 Daikin Applied Seasonal Weather and Internal Loads Page 7 Not only is the weather dynamic, your internal loads are dynamic as well. Surgery suite loading Emergency room usage Patient flow and overnights Conference rooms/meetings Others

©2014 Daikin Applied Seasonal Weather and Internal Loads Page 8 The use of your building affects your support systems: Food service Laundry Housekeeping Many others

©2014 Daikin Applied Seasonal Weather, Internal Loads, and Comfort Page 9 Human comfort is both physical and mental. Physical aspects are: Airflow RH% Air Temperature Odor CO2 and more! HOW DO YOU KEEP EVERY OCCUPANT AND PATIENT COMFORTABLE?

©2014 Daikin Applied Seasonal Control Settings Page 10 Controls settings for patient comfort Controls settings for medical staff comfort Controls settings for safety

©2014 Daikin Applied Seasonal Control Settings Page 11 Controls settings for patient comfort Patient satisfaction surveys and reimbursements Healing rate improvement if person is comfortable? Controls settings for medical staff comfort Physician and nursing staff retention Job satisfaction improved if environment of care is comfortable Productivity enhanced if conditions are maintained

©2014 Daikin Applied Seasonal Control Settings for Safety Page 12 Air pressurization maintenance for critical environments Airflow for biological safety cabinets, fume hoods Airflow for surgery suites and burn treatment areas (and others) Food storage and food preparation areas IT IS NOT JUST ABOUT THE TEMPERATURE; FLOWS AND PRESSURES MATTER AS WELL.

©2014 Daikin Applied Seasonal Control Settings for Occupant Safety Page 13 First Priority – Airflow and pressure maintenance In ante rooms, isolation rooms, and other specialized areas, the difference in room pressures must be maintained. How many of you fight with negative air pressure in the building especially in the winter? Load and ventilation analysis – Not expensive, but very worthwhile for comfort and energy.

©2014 Daikin Applied Load and Ventilation Analysis Page 14 Optimizes recirculation requirements based upon space type determination Defines exact minimum outside air requirement by zone Defines inflow and exhaust flow for each zone Identifies lighting, people, computer, medical equipment loads (by room or zone) Measures current AHU peak airflow and pressure delivery

©2014 Daikin Applied Load and Ventilation Analysis Page 15 Measures current outside air intake quantity, zone temps and settings Identifies needs for fan/coil cleaning, damper repairs, etc. Provides information for optimizing comfort in the occupied spaces through air/water bal. Creates awareness of concern by your staff for patient outcomes, staff satisfaction, etc. Can assure of proper AHU ventilation control throughout facilities

©2014 Daikin Applied Seasonal Control Settings for Occupant Comfort Page 16 Second Priority – Occupant Comfort

©2014 Daikin Applied Seasonal Control Settings for Occupant Comfort Page 17 Second Priority – Occupant Comfort

©2014 Daikin Applied Seasonal Control Settings for Occupant Comfort Page 18 Many other considerations for occupant comfort: Physical health of the individual Use of clothing (sweaters, thin shirts, etc.) Density and length of hair (traps heat from head) Air velocity across the skin Noise of the air and within the rooms Lighting (% of natural lighting, color of lighting, etc.) Wall and room aesthetics (white, shiny painted walls vs. calm colors and artwork, etc.) Sensitivity to temperature swings (heating dead-band and cooling dead-band)

©2014 Daikin Applied Seasonal Control Settings for Occupant Comfort Page 19 Second Priority – Occupant Comfort Energy Policy – Temperature settings by functional space Given all of this information, where should you set the room temperature? 74 Degrees is the mid-point between heating and cooling. Expensive. 76 for Cooling is most common; 78 may be too high (Dehumidification <50%) 72 for Heating is most common; 68 may be too low (Humidity at 30%/35%)

©2014 Daikin Applied Ventilation Quantities Page 20 Set outside air quantities as required to meet minimum volumes (periodically check the damper positions to ensure these are set in the proper position during occupancy and un-occupied conditions) Maintain annual certifications for FHs/BSCs and space pressurization controls Test and adjust kitchen, laundry, and other exhaust systems periodically as renovations happen (adjust sheaves as needed) – Turn on only when needed Maintain and calibrate building static pressure controls and relief systems

©2014 Daikin Applied Ventilation Quantities Page 21 Check economizer sequences of operation for AHUs that vary outside air quantity Check and calibrate CO2 sensors/transmitters/controllers (Ambient air 350 ppm CO2 – adjust to control less than 800 ppm appx. – above this, people can sense the air is “stuffy” and can begin to feel tired.) (If set lower than 800 ppm, energy cost increases significantly.)

©2014 Daikin Applied Ventilation Quantities Page 22 Normal CO 2 Levels* The effects of increased CO 2 levels on adults at good health can be summarized: normal outdoor level: ppm acceptable levels: < 600 ppm complaints of stiffness and odors: ppm ASHRAE and OSHA standards: 1000 ppm general drowsiness: ppm adverse health effects expected: ppm maximum allowed concentration within a 8 hour working period: 5000 ppm * Source: EngineeringToolbox.com

©2014 Daikin Applied Seasonal Control Settings for AHUs Page 23 Mixed air temperature and economizer control – 55 degrees +/- with reset from OAT (Minimize chilled water cooling as much as possible.) Supply air temperature Low temp systems – 40 degrees (maintains fan efficiency) Normal systems – 55 degrees (VAV systems reset from zone average to limit) Minimize fan energy as much as possible

©2014 Daikin Applied Seasonal Control Settings for AHUs Page 24 Supply air pressure – Duct static to maintain +/- 0.5” at furthest outlet (dumping and throw/noise concerns can happen if static too low or too high) (minimize fan motor energy) Hot deck temperature – reset 180 to 120 from OAT 0 to 60 degrees (minimize hot water pump energy) Cold deck temperature – maintain at 52 to 55 degrees depending upon fan size (heat from fan motor) and duct heat absorption (long runs of duct) (minimize chilled water pump energy) Building pressure (Return air fan or relief air damper) – +0.1” normal (can vary by zone)

©2014 Daikin Applied Seasonal Control Settings for Heating Plants Page 25 Deaerator pressure – 3 to 5 psig (for aeration efficiency and feed water heating) Boiler feedwater pressure – 10 psig over generation pressure (reduce pump energy) Steam pressure – minimum pressure for loads served – distribution pressure losses (Autoclaves, sterilizers, linen presses, cooking, humidification, etc.) (Can reset pressure setting on a schedule when high pressure loads are not in operation – do not set too low as condensate volume increases drastically on large campus systems)

©2014 Daikin Applied Seasonal Control Settings for Heating Plants Page 26 Hot water supply temperature – 180 reset to 120 from outside air at 0 to 60 degrees Re-heat loop supply temperature – 140 reset to 120 from outside air at 0 to 60 degrees Perimeter heating system supply temp – 180 to 120 reset. Cycle off pump at OAT>60. Hot water pumping system pressure – minimum to maintain sufficient circulation and not below 25% flow (surging and cavitation)

©2014 Daikin Applied Seasonal Control Settings for CHW Plants Page 27 Constant flow pumping system – reset chilled water supply temperature to highest temp to satisfy all zones (one valve at 100% open) Variable flow pumping system – maintain 42/43 degree chilled water supply temp to minimize pumping energy – may reset chilled water supply temp up if chiller efficiency gain is more efficient than pumping energy spent by pumping more flow.

©2014 Daikin Applied Seasonal Control Settings for CHW Plants Page 28 Chilled water supply temperature – maintain 42 to 45 degrees for variable water pumping systems or chillers with VFDs. For constant pumping systems and chillers without VFDs, reset the chilled water supply temperature as high as possible while maintaining space temperature and relative humidity.

©2014 Daikin Applied Seasonal Control Settings for CHW Plants Page 29 Condenser water supply temperature – maintain lowest inlet temperature to chiller to reduce chiller lift requirement to minimum input temperature permitted by chiller design. Outdoor air wet-bulb temperature reset of condenser water supply temperature based upon your load and equipment. Fan speed control given constant condenser water flow. (Sorry, not a definitive answer.)

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 30 Chiller Replacement Evaluate chillers based upon the Integrated Part Load Value (IPLV) (This is intended to show the part load performance/efficiency and is weighted based upon some assumed capacities and hours of use.) (The IPLV is an ARI/ASHRAE Standard that all manufacturers must use and will clearly indicate which chiller is the most efficient given the stated parameters.) Consider redundancy; low load operation needs (Mutt chillers, plant configuration, VF pumping conversion, etc.); and future load additions (remodels, additions, expansions, etc.)

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 31 Cooling Tower Replacement Evaluate towers based upon chiller installed capacity and free- cooling needs/wants Consider redundancy, fan speed control type and drive, and future load additions

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 32 Pump Replacement If you are replacing your chiller or tower, you should also replace your pump and motor. Choosing the new pump in the highest efficiency portion of the curve can save lots of money every hour the pump runs. Consider conversion to variable flow systems on hot water and chilled water systems; but be very cautious on condenser water and water source heat pump loops. (Requires pressure control and 3-way to 2-way control valve replacement.)

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 33 Boiler Replacement Consider the boiler efficiency at part load, once sizing is confirmed. Consider redundancy, low load operation needs (Mutt boilers, etc.) Consider future load additions (remodels, additions, expansions, etc.) Consider redundant fuel supply (fuel oil, propane, and required storage) Consider cost for alternative fuels

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 34 RTU Replacement Consider overall cost for energy, repairs and maintenance given unit life time. Much higher efficiency units are available. AHU Replacement/Refurbish Consider conversion of constant volume to VAV system for supply fan motors greater than 20 hp. (See table on next page.) Best seasonal performance versus constant volume.

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 35

©2014 Daikin Applied Designing New Systems for Replaced Equipment Page 36

©2014 Daikin Applied Take Aways Page 37 1.Ensure your design team uses seasonal weather data to properly size HVAC systems. 2.Periodically check your controls settings to ensure they are set for the best mix of comfort and efficiency. 3.If it has been a while since you have had a loads analysis and ventilation study, it can be money well spent as energy savings can result from minimizing and controlling ventilation rates. 4.When equipment replacement is needed, ensure that HVAC capacities for its zone/service needs are identified, choose the most efficient equipment available, and control the equipment/system in the most efficient manner that compliments occupant comfort.

e People and ideas you can trust. TM Questions? ©2014 Daikin Applied Page 38

e People and ideas you can trust. TM Thank You! ©2014 Daikin Applied Page 39