Replacing Gas Chlorine with Onsite Sodium Hypochlorite Generation

Slides:



Advertisements
Similar presentations
The Committee and Research – Where are we and where might we be going?
Advertisements

CHEMICAL MANAGEMENT. Agency Missions: Agency Missions: OSHA – Protection of employees from workplace injury and illness. OSHA – Protection of employees.
Course Material Overview of Process Safety Compliance with Standards
BLR’s Safety Training Presentations
HAULED WATER Gary Carlson Municipal Systems EPA Region 8.
Water Treatment Processes Disinfection and removal of solids.
Arsenic/Iron Co-Precipitation and High Rate Filtration in the City of Portage Christopher Barnes, P.E., City of Portage Kendra Gwin, P.E., City of Portage.
Dairy Surface Water Disinfection - Case Study -. Dairy Farm - Continental, OH 600 head of dairy cattle Milked 3 times/day Facility Background.
HAZARD COMMUNICATION REQUIREMENTS Site Specific Written Program Chemical Inventory MSDSs/SDSs Labeling Non-routine Tasks Contractors Training.
Safety Training Presentation
Who We Are Alaska Native Tribal Health Consortium Division of Environmental Health & Engineering June 2011.
Confined Space Rescue Awareness Training
1 Procuring a Design Project engineers perspective on starting the design process and establishing the A/E scope of work Frank C. Quigley General Engineer.
HOUSEHOLD HAZARDOUS WASTE (HHW) Volunteer Safety Awareness
DISINFECTION: APPROPRIATE TECHNOLOGIES FOR WASTEWATER TREATMENT KA SAMSON Presented at the APPROPRIATE TECHNOLOGY CONFERENCE BMW CENTRE, CAPE TOWN, 3-4.
CHLORINE GAS Per gallon of water treated, possibly the safest form of residual disinfection.
South Old Bridge Vol. Fire Co. Standard Operation Procedures for Hazardous Material Incidents.
CONFINED SPACE ENTRY.
Safety Driven Performance 2013
Occupational Safety and Health Course for Healthcare Professionals.
TEXAS COMMISSION on ENVIRONMENTAL QUALITY. PROPOSED STUCTURE FOR CHAPTER 217 < Subchapter A Administrative Provisions < Subchapter B Design Bases < Subchapter.
Sodium Hypochlorite & Ammonia Safety
Decision for DCWASA “ SELECT CHEMICALS TO IMPROVE WASTEWATER TREATMENT PROCESS”
/0409 Copyright © 2004 Business & Legal Reports, Inc. BLR’s Safety Training Presentations Reactive Chemicals 29 CFR at my my parents.
Resource Conservation and Recovery Act.
District Engineer/Manager
Secondary Disinfection with Chloramines Charlotte Smith Charlotte Smith & Associates, Inc. Groveland Community Services District Community Education Meeting.
California Accidental Release Prevention Program California Accidental Release Prevention (CalARP) Program.
1 Risk Assessment Develop Objectives And Goals Develop and Screen Cleanup Alternatives Select Final Cleanup Alternative Communicate Decisions to the Public.
Permitting, Fees, and Reports Cal Poly Lecture Tour Ron Scholtz Analog Devices, Inc.
PSM Covered Chemical Facilities National Emphasis Program.
Hazardous Waste and Emergency Response
The Texas Hazard Communication Act Certification and Recertification Seminar 2006.
Personal Protective Equipment
Dailies, Weeklies, Monthlies, PSM Maintenance - Simplify IT If you’d like to reach SCS Engineers, Tracer Environmental Division please contact us at:
Presented to: RETA National Conference – Atlanta November 5, 2014 If you’d like to reach SCS Engineers, Tracer Environmental Division please contact us.
LABORATORY SAFETY Chemical Hazard Label. What is a MSDS sheet? A Material Safety Data Sheet (MSDS) is designed to provide both workers (students and staff.
Process Safety Management
HAZCOM Hazard Communication Standard “The Right-to-Know”
CTC 450 Review Water processing.
Workplace Hazardous Materials Information System (WHMIS)
Volvo Group North America, LLC Reuse of Wastewater - A Manufacturer’s Experience Steve Pierett, Env.Mgr. CEM, CRM, CP EnMS-Industrial.
Ert 312 LECTURE 4 OSHA & DOSH.
SPWSTAC 2006 From POU to Centralized Arsenic Treatment: A Small Water System Case Study 2006 NGWA Naturally Occurring Contaminants Conference J. Mitchell.
Welding and Cutting for construction. Welding safety program guidelines Person responsible Accountability and enforcement Job hazard assessment Special.
RED = FLAMMABILITY Inflammable means the material will burn. 0 – Will not burn 1 – Must be preheated to ignite. 2 – Must be exposed to high temperatures.
Rockwall-Heath HS Annual Lab Safety Refresher Training.
SUB-TOPICS: -THE PROCES -HEALTH -THE COSTS -DISINFECTION -THE DANGER OF DRUGS IN OUR BODY How drinkwater is purified in The Netherlands.
Infrastructure management system Managers and engineers need clear guidelines for life-cycle management of infrastructure systems for water, sewer, and.
Florida Accidental Release Prevention and Risk Management Planning (ARP/RMP) Act State Emergency Response Commission Preparing for Facility Risk Management.
Overview of the NSF 375 Draft Sustainability for the Water Treatment and Distribution Industry October 30, 2012.
Workplace Hazardous Materials Information Systems.
March 2004 Material Safety Data Sheets Hazard Communications Training for Employees.
© Module 4—Hazard Prevention and Control Safety Management Worksite Analysis Management Commitment and Employee Involvement Hazard Prevention and.
NC AWWA-WEA 2015 Annual Conference Monday, November 16, 2015 The Use of Chlorine Dioxide to Reduce TOC at Davidson Water, Inc. Water Treatment Plant.
2011 PLANT OPERATIONS MODULE 8 Maintain Bulk Plant Systems and Equipment.
Workplace Hazardous Materials Information System. This system provides workers and employers nationwide with vital information about hazardous materials.
The Shepherd Chemical Company Lisa Thamann 11/12/2013 AMMONIUM NITRATE A New Understanding.
1 Highland Water District CAPITAL IMPROVEMENT PLAN.
Lowell Randel Global Cold Chain Alliance/ International Institute of Ammonia Refrigeration.
Messaging & Testimonials
Recycled Water Project Basis of Design Report
CTC 450 Review Water processing.
LABORATORY SAFETY Chemical Hazard Label Chemistry
Using Safer Treatment chemicals
CITY OF MARSHALL CHLORIDE ISSUES September 26, 2017
CITY OF MARSHALL CHLORIDE ISSUES NOVEMBER 22, 2016
OSHA Chemical and Refinery National Emphasis Program
Process Safety Management
Effects of Disasters on Wastewater Treatment and Collection Systems
Presentation transcript:

Replacing Gas Chlorine with Onsite Sodium Hypochlorite Generation Tim Geraghty, P.E. Division Manager Alliance Water Resources, Inc. Introduce topic. Discuss my education and 24 yrs experience in design, construction and operation of water systems.

Replacing Gas Chlorine with Onsite Sodium Hypochlorite Generation Goal: help other utility managers decide if changing disinfectants would be worth considering What made us consider a change What options we considered Costs & benefits Design Construction

Background Most water treatment facilities use chlorine as their primary disinfectant Chlorine use became widespread in the early 1900’s Chlorine has a proven track record Chlorine gas is a highly hazardous chemical

Background St. Charles County, MO Water Treatment Plant has successfully used chlorine gas in 1-ton containers as a disinfectant since 1941 Plant capacity 8 MGD average 22 MGD peak

Water Treatment Plant, St. Charles County, MO 1940 2013 Discuss plant’s history 1940 2013 They don’t build ‘em like they used to

Water Treatment Plant 1940 2013 Not much has changed

Background 2005 - Water District purchased the treatment plant 2012 - Water District completed an overall WTP assessment Reviewed existing condition of the plant facilities & equipment Reviewed plant processes Developed and prioritized a capital improvement plan

Background Results of the plant assessment Electrical/efficiency upgrades $1.4M Filter upgrades $2.3M Booster pump station replacement $4.0M Replacement of the gas chlorine feed system $2.5M Lime, ammonia and fluoride system improvements $0.9M Total $9.7M

Why consider changing from chlorine gas? Need to update existing chemical processes, controls and equipment due to age Safety Employees People in the surrounding community Environment

Why consider changing from chlorine gas? 1997 – one ton container split 25 miles away in Kirkwood, Missouri 2012 – one ton container leaking 10 miles away in Chesterfield, Missouri

48,000 pounds released - 63 people injured Why consider changing from chlorine gas? 2002 – leaking 1” hose connected to 90-ton railcar 50 miles away in Festus, Missouri 48,000 pounds released - 63 people injured Pictures from US Chemical Safety & Hazard Investigation Board Report, 2003

Why change? Federal OSHA Safety Regulations (TOSHA requirements may be more stringent) EMPLOYEES Coordination with LEPC OSHA Process Safety Management (29 CFR 1910.119) Management of Change Chlorine Institute Pamphlet 65 for PPE Respirators – fit testing, medical baselines and periodic evaluations Chlorine Institute Pamphlet 155 for water and wastewater operators Hot Work Confined Space Training Contractor Safety & Record Keeping Record keeping, record keeping, record keeping

Federal Safety Regulations - EPA Why change? PEOPLE IN THE SURROUNDING COMMUNITY Estimating offsite receptors Hazard reviews US EPA Risk Management (in section 112(r) of the Clean Air Act) Operating procedures Compliance Audits Mechanical integrity Worst case release scenario Employee participation Coordinating with LEPC Alternative release scenarios Communication with the Public Offsite consequence analysis Regular re-submittals Federal Safety Regulations - EPA

Protect the Environment Why change? Water Plant Missouri Conservation Department -Wildlife Area US Army -Training Area University Research Area (added political pressure from regulators) Protect the Environment

To decide if a disinfectant change was worthwhile, we reviewed our goals and other disinfectants

Review of Alternatives - Water Quality Considerations Requirements for disinfection Groundwater Rule 4-log removal of viruses Chlorine contact time Effects of chlorination on pH Distribution system bacteria re-growth potential THM’s/HAA’s Nitrate formation Chlorite formation Water Quality Considerations

Review of Alternatives - Selection Criteria Safety Life Cycle Costs Capital O&M labor Power Chemicals Waste treatment/hauling Chemical & power cost stability Chemical strength stability Chemical availability Review of Alternatives - Selection Criteria

Review of Alternatives - Selection Criteria Need for additional treatment Level of automation Permitting issues Space requirements Operational flexibility, familiarity & simplicity Equipment reliability Selection Criteria

Review of Alternatives Gas chlorine Ozone Ultraviolet (UV) Light Chlorine dioxide Hypochlorite Calcium hypochlorite Sodium hypochlorite Onsite hypochlorite generation Bulk deliveries Combinations of the above

Review of Alternatives Gas Chlorine in 1-ton containers (current practice) Advantages – low capital and operating cost, simple operation, low maintenance Disadvantages – hazardous and toxic chemical, potential of leaks & high level of regulation

Review of Alternatives Gas Chlorine in 150-pound cylinders Advantages – low capital and operating cost, simple operation, low maintenance Disadvantages – hazardous and toxic chemical, potential of leaks & high level of regulation Switching to smaller cylinders would reduce the quantity released during a major leak, but more changeovers & handling would be required

Review of Alternatives Ozone Expensive Additional disinfectant needed for maintaining residual in distribution Often used to eliminate a specific contaminant Ultraviolet (UV) Light Review of Alternatives

Review of Alternatives Chlorine dioxide Strong disinfectant Stops THM formation May require additional treatment for chlorite Often used for pre-treatment – not as the lone disinfectant

Review of Alternatives Bulk Sodium Hypochlorite (typically 12.5% solution) Advantages – Low capital cost, generally safer than chlorine gas Disadvantages – High operating cost, degradation, corrosive health hazard

Review of Alternatives Generated Sodium Hypochlorite (0.8% solution) Advantages – no storage of highly hazardous chemicals, consistent product concentration Disadvantages – High capital cost, hydrogen gas byproduct, short product storage time

Review of Alternatives Process Schematic Bulk hypochlorite components Onsite hypochlorite generation components

Bulk Sodium Hypochlorite (11 - 15%) Hazardous to Environment, Users, and Community Chlorine Gas Bulk Sodium Hypochlorite (11 - 15%) NFPA Rating Health = 4 Flammability = 0 Instability = 0 Oxidizer Health = Lethal Short Term Exposure = Burns, Chest Pain, Emotional Disturbances, Lung Damage, Death Physical Hazards = Containers may rupture or explode. 4 NFPA Rating Health = 2 Flammability = 0 Instability = 1 Oxidizer Health = Intense or continued exposure could cause temporary incapacitation or residual injury. Instability = Can become unstable at elevated temperatures and pressures. 2 1 OX OX MIOX Proprietary and Confidential- DO NOT DISTRIBUTE

Environmentally Benign 0.45% Generated FAC or 0.8% Generated FAC NaCl (SALT) NFPA Rating Health = 1 Flammability = 0 Instability = 0 Health = Exposure may cause mild irritation Instability = Normally stable, even under fire conditions. NFPA Rating Health = 1 Flammability = 0 Instability = 0 Health = Exposure may cause mild irritation Instability = Normally stable, even under fire conditions. 1 1 MIOX Proprietary and Confidential- DO NOT DISTRIBUTE

Review of Alternatives Comparison Capital Cost Annual O&M Hazard Potential* Chlorine Gas (add scrubber & other controls) $900,000 $50,000 highly hazardous gas Ozone High limited UV low Bulk Sodium Hypochlorite $650,000 $160,000 highly corrosive liquid Generated Sodium Hypochlorite $1,900,000 $100,000 hydrogen gas by-product Of these alternatives, only gas chlorine requires PSM & RMP programs

Review of Alternatives Cost savings due to eliminating PSM training and administration 60 training hours annually for operators & maintenance staff 200 hours annually for contractor training 100 hours annually for administration per year training reports, maintenance reports, PSM Manual updates, PSM and RMP annual SOP certifications, periodic resubmission of PSM and RMP documentation, internal compliance audits, testing of chlorine sensors, … $10,000 - $15,000 per year

Review of Alternatives UV and Ozone were ruled out - high costs + additional need for residual disinfectant For the two hypochlorite alternatives, onsite generation preferred because of lower O&M Chosen Alternative: Onsite Generation of Sodium Hypochlorite because of reduced safety concerns; estimated additional cost of treated water less than $0.04 per 1,000 gallons (<1% of user rate)

Design Considerations First step – choose a hypochlorite generator manufacturer Equipment varies by manufacturer Major considerations Safety considerations Ease of operation/number of components Equipment footprint Life cycle costs Availability

Design Considerations Choosing a hypochlorite generator manufacturer The cost of materials varies by manufacturer but one pound of chlorine is generated by roughly: 15 gallons soft water (at 15-40 gpm and about 60 psi) 3 pounds salt 2 kilowatt-hours

Design Considerations – Site Visits Designers and operators visited several installations of various manufacturers

Design Considerations Efficiency & Complexity Indoor Equipment (generators, blowers, power and control panels) Room arrangement/ available space HVAC requirements & equipment heat loss Outdoor Equipment (tanks & accessories) Sunshades

Design Considerations Sodium Hypochlorite Storage Tanks Storage time Degradation (esp. for 12.5%) Sodium Hypochlorite Metering Pumps Based on each feed point’s chlorine demand Sized for both 12.5% and 0.8% solution

Design Considerations Standby Options Standby generator Provisions for bulk delivery Plant Shutdown (generally available at this location September through May)

Capital Costs Equipment Bids Construction Bids (includes equipment) ChlorTec (two 750 ppd units)$ 536,500 MIOX (three 500 ppd units) $ 572,980 PSI (two 800 ppd units) $ 619,500 Construction Bids (includes equipment) Engineer’s final estimate $2,041,000 Low of 5 bids: KCI Construction $2,213,500

Chosen Alternative - MIOX Simplicity / fewest components Smallest footprint / able to fit most equipment in the existing building

Design Considerations for Chosen Alternative System Control Panel Inputs Water hardness Brine tank level Storage Tank Level System Components Brine pump Generators/rectifiers Hydrogen dilution blowers Sodium hypochlorite storage tank level

Chosen Alternative - MIOX

Construction Construction Sequence Site work Install outdoor hypochlorite tanks Install new process piping and metering pumps Place bulk hypochlorite (12.5%) system in operation Remove existing gas chlorine piping and equipment Install hypochlorite generators in the space vacated by the gas chlorine system

Construction Schedule and current progress Site work completed (relocated storm & sanitary sewers) Bulk tanks, piping, water softeners, pumps and dilution panel installed

Construction Schedule and current progress SOP’s written and operators trained in bulk chemical feed process Bulk chemical (12.5%) and tanks being put in operation next week Remaining work to be completed by July 2013 Remove existing gas chlorination system Install hypochlorite generation and other equipment inside the building and start-up

Key Points Ultimately, the Water District Board decided that increasing the level of safety was worth the additional capital and O&M costs Our chosen disinfection alternative was not the lowest cost alternative The chosen manufacturer’s equipment was not the lowest cost alternative Involving the operators in the decision- making was critical and strongly influenced the decision The operators (and probably their spouses) can’t wait for the workplace to be safer

For More Information www.alliancewater.com Tim Geraghty, P.E. Special Thanks to Black & Veatch and Parkson Disinfection for technical information they provided for the presentation For More Information Tim Geraghty, P.E. Division Manager Alliance Water Resources 100 Water Drive O’Fallon, MO 63368 636-561-3737 x101 tgeraghty@alliancewater.com www.alliancewater.com