Heating Losses- Infiltration and Ventilation

Slides:



Advertisements
Similar presentations
Environmental Controls I/IG
Advertisements

Formulas.
HEAT LOSS & HEAT GAIN HEAT FLOW. Heat flows from high temperature to low temperature There are 3 types/methods of heat flow/transfer: 1.Conduction- through.
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov Calculating Envelope Energy Loss WEATHERIZATION ENERGY AUDITOR.
Energy Savings Impacts of the Advanced Energy Design Guide: Small Office Buildings Bing Liu, P.E. Research Engineer Pacific Northwest National Laboratory.
Building Envelope. Energy Conservation House design and orientation Lifestyle changes Energy efficiency.
Environmental Controls I/IG
Load Calculations Dr. Sam C M Hui MECH3005 – Building Services
The Three Tiered Philosophy
Chilled Beam Presentation
Infiltration/Ventilation HVAC 7a CNST 305 Environmental Systems 1 Dr. Berryman.
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – August 2010eere.energy.gov Energy Movement WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY.
Landscaping to Help Conserve Energy Master Gardener Volunteers Training.
The House as a System 1. Air Temperature and Water Vapor.
Heating energy calculation methods Anti Hamburg Lecture TTK-UAS.
HVAC 7ab CNST 305 Environmental Systems 1 Dr. Berryman
Environmental Controls I/IG Lecture 12 Cooling Loads Cooling Degree Hours Energy Performance Ratings Annual Fuel Consumption Lecture 12 Cooling Loads Cooling.
Conduction Cooling Loads
Heat Loss & Gain Calculations 1. How Heat Moves in Homes Conduction is the transfer of heat through solid objects, such as the ceilings, walls, and floors.
Heating and Air Conditioning I Principles of Heating, Ventilating and Air Conditioning R.H. Howell, H.J. Sauer, and W.J. Coad ASHRAE, 2005 basic textbook/reference.
Heat Transmission HVAC CNST 305 Environmental Systems 1 Dr. Berryman.
Energy use in buildings Dr. Atila Novoselac Associate Professor Department of Civil, Architectural and Environmental Engineering, ECJ
 On average, home heating uses more energy than any other system in a home  About 45% of total energy use  More than half of homes use natural gas.
HVAC523 Heat Gain. Heat First law of thermal dynamics states that HEAT TRAVELS FROM HOT TO COLD. 95 degree outside air will flow through the building.
BEM CLASS 5 Building Thermodynamics – 2 Air-conditioning Load Calculation – latent heat, solar and internal gains.
ARCH-432 Vapor Retarders and Air Barriers Attendance In what modern day country was the first cavity wall developed and used? For what purpose? A. Spain.
Ductless Heat Pumps Sizing Example
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
Energy use in buildings Dr. Atila Novoselac Associate Professor Department of Civil, Architectural and Environmental Engineering, ECJ
ASHRAE A Ventilation Standard for Residential Structures Ventilation and Acceptable Indoor Air Quality in Low- Rise Residential Buildings.
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
HVACR416 - Design Heat Loss / Heat Gain Part 2. External Loads The greatest external load is the sun. The suns heat can get into a building in one of.
Energy Conservation February 8, Steve Wilson, MBA, CEM, CDSM, BEP The Energy Guy.
 On average, home heating uses more energy than any other system in a home  About 45% of total energy use  More than half of homes use natural gas.
HVACR416 - Design Heat Loss / Heat Gain Part 1. Why? The primary function of Air Conditioning is to maintain conditions that are… o Conductive to human.
EXAMPLE EXERCISE CALCULATING HEAT LOSS & HEAT GAIN  Several exhibits in the class packet are necessary to understand the entries into the Heat Loss /
INTRODUCTION TO HEAT LOAD HEAT LOAD12 3 TOPICS COVERED INTRODUCTION DESIGN CONSIDERATIONS DEFINITIONS/CONCE PT/FORMULA THE FORM LOAD COMPONENTS –External.
Heat Gains into a Building
 On average, home heating uses more energy than any other system in a home  About 45% of total energy use  More than half of homes use natural gas.
Introduction to Energy Management. Lesson 4 Determining the Loads on the HVAC System.
Development of a new Building Energy Model in TEB Bruno Bueno Supervisor: Grégoire Pigeon.
VENTILATION AND FENESTRATION
Design What is the first step in designing a high-performance building? Would it be: Identify synergies Select the correct HVAC system Design around human.
SYSTEM SELECTION & SPACE REQUIREMENTS INTRODUCTION SYSTEM SELECTION SPACE REQUIREMENTS SAMPLE QUESTIONS.
Heat transfer Steady state conditions not for dynamic systems in buildings through walls, roofs, floors, windows, doors building structures and U-values.
Heat Loss and Gain Civil Engineering and Architecture
Technology in Architecture
Maria’s Restaurant Chapter 1 Section 3
Chapter 6: INFILTRATION
RESIDENTIAL HVAC (HEAT LOSS & GAIN)
Heat gain and heat loss in buildings
Heat loss and heat gain in buildings: Outside air (OA) (Additional information) Required to be brought inside a building envelope to continuously replace.
Heat Loss and Gain.
Heat Loss and Gain Heat Transfer Winter Heat Loss Summer Heat Gain
Conduction Cooling Loads
Branching and Decisions
Introduction – Who am I? Environmental Project Manager – Trident Technical College Mechanical Engineer Licensed Builder South Carolina Accredited Commercial.
Things you need to know before you play the game
Chapter 6A: INFILTRATION BACKGROUND
Technology in Architecture
Technology in Architecture
Technology in Architecture
Technology in Architecture
Technology in Architecture
A Ventilation Standard for Residential Structures
Lecture Objectives Learn about Cooling Load Calculation
Objective Revie the Cooling Cycle Learn about air distribution systems
Maria’s Restaurant Chapter 1 Section 3
Chapter 6B: INFILTRATION CALCULATION
Presentation transcript:

Heating Losses- Infiltration and Ventilation ARCH-432

Attendance Which civilization made it a point to layout whole cities to take advantage of passive heating? In what direction did the city streets run? Greece Rome Egypt Persia Babylonia The ancient Greeks did this. Shown is Priene (5th Century B.C.), which has all of the streets laid out in an East-West fashion, thus allowing all homes to point South.

Attendance The ancient Greeks did this. What was shown is Priene (Priēnē); (5th Century B.C.), which had all of the streets laid out in an East-West fashion, thus allowing all homes to point South. The ancient Greeks did this. Shown is Priene (5th Century B.C.), which has all of the streets laid out in an East-West fashion, thus allowing all homes to point South.

Attendance “Only primitives and barbarians lacked knowledge of houses turned to face the winter sun, dwelling beneath the ground like swarming ants in sunless caves.” Aeschylus Ess ca less One of the earliest writer of Greek tragedy – before him plays had single actors who could only respond to a chorus (group of people). Aeschylus increase the tragedy to two actors with dialog.

Greetings Capt. Kirk Aeschylus

Attendance Aeschylus pronounced Ess ca less One of the earliest writer of Greek tragedy – before him plays had single actors who could only respond to a chorus (group of people). Aeschylus increase the tragedy to two actors with dialog.

Big Picture Moment roof Infiltration and Ventilation Ceiling Partition Exterior wall Glass conduction Floor Infiltration and Ventilation Ceiling Partition I. Heat Loss A. Five main types of heat loss 1. Transmission (conduction) 2. Infiltration (convection) 3. Ventilation (convection) 4. Radiation (radiation) 5. Moisture migration

Five main types of heat loss 1. Transmission (conduction) roof Exterior wall Glass conduction Floor Infiltration and Ventilation Ceiling Five main types of heat loss 1. Transmission (conduction) 2. Infiltration (convection) 3. Ventilation (convection) 4. Radiation (radiation) 5. Moisture migration I. Heat Loss A. Five main types of heat loss 1. Transmission (conduction) 2. Infiltration (convection) 3. Ventilation (convection) 4. Radiation (radiation) 5. Moisture migration

Summary of Heat Losses Wall Roof Floor Windows Doors Infiltration Ventilation Envelope Losses

What You Need To Know The difference between ventilation and infiltration Calculation methods for both ventilation and infiltration

What You Need To Be Able To Do Calculate infiltration/ventilation loads Be able to reduce/mitigate infiltration and ventilation loads Employ techniques for increasing ventilation effectiveness

Terms Infiltration Exfiltration Ventilation Direct Outside Air System (DOAS)

Infiltration “The uncontrolled introduction of outside air into a building.” I. Infiltration A. The uncontrolled introduction of fresh air into a building. 1. Most subjective of all losses 2. Oftentimes the largest of all heat losses. Sometimes comprises up to 30% of the total heating load. 3. Ends up being an “educated guess”

Infiltration The uncontrolled introduction of fresh air into a building. 1. Most subjective of all losses 2. Oftentimes the largest of all heat losses. Sometimes comprises up to 30% of the total heating load. 3. Ends up being an “educated guess” I. Infiltration A. The uncontrolled introduction of fresh air into a building. 1. Most subjective of all losses 2. Oftentimes the largest of all heat losses. Sometimes comprises up to 30% of the total heating load. 3. Ends up being an “educated guess”

Why Is This Important? All buildings leak A tight building will leak .5 AC/H A leaky building can leak 3 AC/H Regardless of climate, air leaking into walls causes problems

Ventilation The mechanical introduction of outside air (OA) to: Replace Oxygen Dilute contaminants Pressurize the building

Moisture Load

Infiltration Calculation Methods Crack method Air Change Method ‘Averaging’ method (‘I don’t know so I’m going to throw a dart’ method)

Crack Method Presumes that an accurate estimate can be obtained by estimating the rate of infiltration per foot of crack for doors and windows CFM = Ft. of Crack x Infiltration Rate QS = 1.1 x CFM x (T2 – T1) in BTU/HR I. Crack Method A. Presumes that an accurate estimate can be obtained by estimating the rate of infiltration per foot of crack. 1. For doors, you must also add the volume of air that “infiltrates” when the door is in use. B. The CFM is then defined as CFM = Ft. of Crack x Infiltration Rate. C. Use Table 3.4 of your text.

Add Infiltration Through Open Door Determine Door Usage ת = Number of People per Minute Determine CFM per person (D) CFM = ת x D I. Add Infiltration Through Open Door A. Determine Door Usage 1. Owner or Architect will be the best source for ת, the number of people per minute B. Determine the CFM per Person (D) 1. From Table 3.5 CFM = ת x D LEED-NC Credit EQ 5 for providing vestibules.

Infiltration by Crack Method Add CFM from Crack losses to CFM for Open Door losses

Mitigate These Losses How do you reduce or mitigate these losses? (Review) Really good weather-stripping Pressurization Vestibules Revolving doors Seal cracks and openings CO2 sensors DOAS systems

Mitigation Strategies Pressurization QS = 1.1 x CFM x (T2 – T1) Vs. QS = 1.1 x (CFH/ft of crack x ft of crack)/60 x ΔT You own the variables!

Infiltration Variables Review Wind velocity and direction Stack effects Corner rooms Exhaust fans on or off Pressure zoning Frequency of use Maintenance I. Infiltration Variables A. Wind velocity and direction B. Stack effects C. Corner Rooms 1. Remember, the wind blows on one side at a time! A. Use either the greater of the two CFM values or 70% of the total. D. Exhaust fan operation E. Pressure zoning F. Frequency of use G. Maintenance

Stack Effect Review

CFM = Volume (ft3)/Frequency (minutes) Air Change Method Often used in residential construction and in large warehouses and similar buildings CFM = A.C.H. x Volume (ft3)/60 or CFM = Volume (ft3)/Frequency (minutes) I. Air Change Method A. Oftentimes used in residential construction and in large buildings like warehouses and other similar commercial structures. CFM = A.C. H. x Volume (ft3)/60 or CFM = Volume (ft3)/Frequency (minutes) B. Can also be determined by Code 1. For example, the UBC requires you to use not less than .5 CFM/square foot

Air Change Method Uses same formula for sensible Equals one room change Designer will use 0.3 to 2.0 air changes per hour (ACH) Occupancy Climatic condition (i.e. winter vs. summer) Construction (tight or loose) Least accurate of the three methods Qsens = 1.1 x CFM x T

Table 2-8

Heat Loss Due to Infiltration Btu H = (.018) x (ACH) x V x (Ti – To) ACH = air exchanges per hour V = volume Ti = inside temperature To = outside temperature

Heat Loss Due to Infiltration OR

Heat Loss Due to Infiltration Btu H = 1.1 x CFM x (Ti – To) CFM = (ACH x volume) / 60 min per hour

Heat Loss Due to Infiltration Please Note: For tight construction use 0.5 for ACH. For medium construction use .85 for ACH. For loose construction use 1.3 for ACH. For really bad construction use 2.0 for ACH For the summer months (cooling) use 70% of the winter values.

Infiltration & Ventilation Btu Hour Loss due to Infiltration Main Area CFM Ht. W. L. 1.10 air exch. vol. In cf / 60 Temp. Ch.   12 46.66 74.66 0.5 41,803.63 348.36 76 29,123.19 Btu Hour Loss due to Ventilation Main Area sf cfm exchange Occup. 3,483.64 0.180 34.84 66,983.35 Ra Rp Occup/1000 0.18 5 10.00

Heat Gains Due to Infiltration Latent Load BtuH = 4500 x (air exchanges x (volume) /60) x (W Final – W Initial) (W Final – W Initial) = Difference Ratio Pounds of Moisture per dry air

Heat Loss Due to Ventilation Btu H = 1.1 x [(Ra x square feet of building ) + (number of people in the building x Rp )] x (Ti – To)

Heat Loss Due to Ventilation

Heat Loss Due to Ventilation Ra = Area Outdoor Air Rate Rp = People Outdoor Air Rate Example: Pharmacy Ra = .18 Rp = 5

Heat Loss Due to Ventilation Btu H = 1.1 x [ (.18 x 3,632) + (30 x 5)] x 76o = 67,214

Ventilation and / or Infiltration