1 Technology in Architecture
Lecture 7 Degree Days Heating Loads Annual Fuel Consumption Simple Payback Analysis

2 Heating Degree Days Balance Point Temperature (BPT): temperature above which heating is not needed DDBPT= BPT-TA

3 Sample Calculation January TA=28ºF DD65=65-28= 37 Degree-days/day
x 31 days = 1,147 degree-days M: p. 1620, T.C.19

4 Heating Loads

5 Heating Loads Computed for worst case scenario: Do not include:
Pre-dawn at outdoor design dry bulb temperature Do not include: Insolation from sun Heat gain from people, lights, and equipment Infiltration in nonresidential buildings Ventilation in residential buildings SR-3

6 Outdoor Dry Bulb Temperature
M: T.B.1, p. 1571 Outdoor Dry Bulb Temperature Use Winter Conditions RESCAN S11: T.B

7 Determine Temperature Difference
Indoor Dry Bulb Temperature (IDBT): 68ºF Outdoor Dry Bulb Temperature (ODBT): 13ºF ΔT=IDBT-ODBT=68ºF - 13ºF = 55ºF

8 Determine Envelope U-values
Calculate ΣR and then find U for walls, roofs, floors. Obtain U values for glazing from manufacturer or other reference

9 Determine Area Quantities
Perform area takeoffs for all building envelope surfaces on each facade: gross wall area window area door area net wall area 1200 sf - 100’ 368 sf - 64 sf 768 sf 12’ 4’ 4’ 8’ Elevation

10 Floor Slabs For floor slabs at grade, there are two heat loss components: slab to soil losses edge losses M: p. 1680, F.E.1

11 TI=Indoor Air Temperature TGW=Ground Water Temperature
Slab to Soil Losses Q=Uslab x 0.5 x Aslab x (TI-TGW) TI=Indoor Air Temperature TGW=Ground Water Temperature

12 Edge Losses Method I Determine F2 based on heating degree days
M: p. 1680, T.E.11/F. E.1

13 Select F2 based on insulation configuration
Slab Edge Losses Method II Select F2 based on insulation configuration M: 1681, T.E.12

14 TI= Indoor air temperature TO=Outdoor air temperature
Slab Edge Losses Q=F2 x Slab Perimeter Length x (TI-TO) where, TI= Indoor air temperature TO=Outdoor air temperature

15 Heating Load Example Problem
Building: Office Building Location: Salt Lake City ΔT=IDBT-ODBT=68-13=55ºF Building: 200’ x 100’ (2 stories, 12’-6” each) Uwall= Btuh/sf-ºF Uroof= Btuh/sf-ºF Uwindow= Btuh/sf-ºF Uslab= Btuh/sf-ºF Udoor= Btuh/sf-ºF Slab Edge: R-15 vertical insulation, 2’ deep. Degree Days = 5,983

16 Heating Load Example Problem
Determine Building Envelope Areas (SF) Building: 200’ x 100’ (2 stories, 12’-6” each) N E S W Gross Wall 5,000 2,500 5,000 2,500 Windows 1, , Doors Net Wall 3,980 1,980 2,950 1,980 Roof/Floor Slab 20,000

17 Heating Loads Insert roof values Insert wall values
, N ,980 55 E ,980 55 S ,950 55 W ,980 55 Insert roof values Insert wall values Insert glass values Insert door values Insert floor values N ,000 55 E S ,000 55 W N/A N/A N/A N/A SR-3

18 TI=Indoor Air Temperature TGW=Ground Water Temperature
Slab to Soil Losses Q=Uslab x 0.5 x Aslab x (TI-TGW) TI=Indoor Air Temperature TGW=Ground Water Temperature Ground Water= 53ºF ΔT=68ºF-53ºF=15ºF

19 Heating Loads Insert floor values SR-3 0.025 20,000 55
, N ,980 55 E ,980 55 S ,950 55 W ,980 55 Insert floor values N ,000 55 E S ,000 55 W N/A N/A N/A N/A ,000 15 SR-3

20 Select F2 based on insulation configuration
Slab Edge Losses Method II Select F2 based on insulation configuration Slab Edge: R-15 vertical insulation, ’ deep. F2=0.52 M: 1681, T.E.12

21 Heating Loads Insert floor values SR-3 0.025 20,000 55
, N ,980 55 E ,980 55 S ,950 55 W ,980 55 Insert floor values N ,000 55 E S ,000 55 W N/A N/A N/A N/A ,000 15 SR-3

22 Infiltration Residential buildings use infiltration to provide fresh air “Air change/hour (ACH) method” or “Crack length method” Prone to subjective interpretation Vulnerable to construction defects Provides a relatively approximate result

23 ASHRAE Standard 62.1-2016 (M: p. 1696, T.F.1)
Ventilation Analysis Non-residential buildings use ventilation to provide fresh air and to offset infiltration effects. ASHRAE Standard (M: p. 1696, T.F.1) Estimates the number of people/1000 sf of usage type Prescribes minimum ventilation/person for usage type

24 ASHRAE 62.1-2016 Defines space occupancy and ventilation loads
M: p. 1697, T.F.1

25 Ventilation Load — Sensible
40,000 sf x 5people/1,000sf = 200 people 200 people x 17 cfm/person = 3,400 cfm 3,400 cfm x 60min/hr = 204,000cfh

26 Heating Loads Input Ventilation Load—Sensible SR-3 0.025 20,000 55
, N ,980 55 E ,980 55 S ,950 55 W ,980 55 Input Ventilation Load—Sensible N ,000 55 E S ,000 55 W N/A N/A N/A N/A ,000 15 204, SR-3

27 Ventilation Load — Latent
Determine ΔW WI= #H2O/#dry air -WO= #H2O/#dry air ΔW= #H2O/#dry air

28 Heating Loads Input Ventilation Load — Latent SR-3
, ,500 N , ,583 E , S , ,762 W , ,880 Input Ventilation Load — Latent N , ,050 E ,525 S , ,100 W ,525 ,210 N/A N/A N/A N/A , ,000 ,160 204, ,960 204, ,308 SR-3

29 Heating Load Total Load 469,435 Btuh 5.9 6.8 8.8 SR-3 14.5 0.3 63.8
, , ,500 5.9 N , ,583 E , ,880 S , ,762 W , , ,105 Total Load 469,435 Btuh 6.8 N , ,050 E ,525 S , ,100 W , ,200 14.5 ,210 1,210 0.3 N/A N/A N/A N/A , ,000 ,160 41,160 8.8 204, ,960 204, , ,268 63.8 SR-3 469,435

30 Annual Fuel Consumption

31 Annual Fuel Usage (E) E= UA x DDBPT x 24 AFUE x V where:
UA: heating load/ºF DDBPT: degree days for given balance point AFUE: annual fuel utilization efficiency V: fuel heating value

32 Calculating UA QTotal= UA x ΔT UA= QTotal/ΔT From earlier example:
QTotal=469,435 Btuh ΔT= 55ºF UA=469,435/55=8,535 Btuh/ºF

33 Determine AFUE Annual Fuel Utilization Efficiency of an electric heating system is 100% M: p. 311, T.9.4

34 Determine Heat Content (V)
Heat content is the quantity of Btu/unit Note: Natural Gas is sold in therms (100 cf) M: p. 309, T.9.2

35 Annual Fuel Usage Example
What is the expected annual fuel usage for a house in Salt Lake City if its peak heating load is 35,750 Btuh? UA=Q/ΔT UA=35,750/55= 650 Btuh/ºF

36 Determine AFUE Annual Fuel Utilization Efficiency of an electric heating system is 100% M: p.311, T.9.4

37 Determine Heat Content (V)
Heat content is the quantity of Btu/unit M: p. 309, T.9.2

38 Annual Fuel Usage — Electricity
E= UA x DD x 24 AFUE x V EELEC =(650)(5,983)(24)/(1.0)(3,413) =27,347 kwh/yr If electricity is $0.0735/kwh, then annual cost = $2,010

39 Annual Fuel Usage — Gas E= UA x DDBPT x 24 AFUE x V
=1,111 therms/yr If gas is $0.41/therm, then annual cost = $456

40 Simple Payback Analysis

41 Simple Payback Heating System Cost Comparison First Electricity 6,000
($) Electricity 6,000 Oil 8,000 Gas 8,900

42 Simple Payback Heating System Cost Comparison
First Annual Incremental Incremental Simple Cost Fuel Cost First Cost Annual Savings Payback ($) ($/yr) ($) ($/yr) (yrs) Electricity 6,000 2, Oil 8,000 1,152 2, Gas 8, ,900 1, If money is available, select gas furnace system

43