INTRODUCTION TO HEAT LOAD HEAT LOAD12 3 TOPICS COVERED INTRODUCTION DESIGN CONSIDERATIONS DEFINITIONS/CONCE PT/FORMULA THE FORM LOAD COMPONENTS –External.

Similar presentations


Presentation on theme: "INTRODUCTION TO HEAT LOAD HEAT LOAD12 3 TOPICS COVERED INTRODUCTION DESIGN CONSIDERATIONS DEFINITIONS/CONCE PT/FORMULA THE FORM LOAD COMPONENTS –External."— Presentation transcript:

1

2 INTRODUCTION TO HEAT LOAD

3 HEAT LOAD12

4 3 TOPICS COVERED INTRODUCTION DESIGN CONSIDERATIONS DEFINITIONS/CONCE PT/FORMULA THE FORM LOAD COMPONENTS –External (Skin) –Internal –Others HEAT CLASSIFICATION –Room Sensible/Latent –Effective Room Sensible/Latent –Effective Room Total –Grand Total Heat –Refrigeration Load

5 HEAT LOAD14

6 5 DESIGN CONSIDERATION Design conditions –internal/external Orientation of building Use of space Dimension of space Ceiling height Columns and beams Construction materials Surrounding condition Windows Doors Stairways, Elevators & Escalators People Lighting Motors, appliances Ventilation Operation hrs.

7 HEAT LOAD1 6

8 7 DEFINITIONS AIR CONDITIONING –A process which heats, cools, cleans and circulates air and control its moisture content. This process is done simultaneously and all year round

9 HEAT LOAD18 DEFINITION SENSIBLE LOAD –Results when heat entering the condition space that caused the Dry Bulb (db) to increase LATENT LOAD –results when moisture entering/leaving the space causes the humidity to increase/decrease

10 LETS LOOK AT THE HEAT LOAD FORM

11 HEAT LOAD110 LOAD COMPONENTS PSYCHROMETRIC LOAD PSYCHROMETRIC LOAD –ALL SENSIBLE –ALL LATENT –COMBINATION PHYSICAL LOAD PHYSICAL LOAD –EXTERNAL LOAD –INTERNAL LOAD –OTHER LOAD (EQUIP./DUCT/etc.)

12 HEAT LOAD111 PHYSICAL LOAD a) EXTERNAL LOAD (1) Solar heat gain through glass –Direct sun rays pass through glass windows as radiant energy into space. –Can be reduced by use of internal/external shading devices, overhangs, or shadows cast by other building

13 HEAT LOAD112 PHYSICAL LOAD a) EXTERNAL LOAD (2) Solar and transmission gain through walls and roofs –Heat is caused to flow through external walls and roofs by two sources sun rays striking the external surfaces high outdoor air temperatures

14 HEAT LOAD113 PHYSICAL LOAD a) EXTERNAL LOAD (3) Transmission gains through glass, partition, floors –When an adjacent area is at a higher temperature than the space, heat will flow through windows, ceilings, partitions, or floors by means of transmission

15 HEAT LOAD114 PHYSICAL LOAD a) EXTERNAL LOAD (4) Infiltration –Wind blowing against the side can cause air from outside to enter space. Caused localised sensible and latent heat gain Ventilation –When outdoor air is introduced DIRECTLY into space, it will appear as load to the space.

16 HEAT LOAD115 PHYSICAL LOAD b) INTERNAL LOAD (1) People Power/Motor Lights Appliances & Equipment

17 HEAT LOAD116 PHYSICAL LOAD b) INTERNAL LOAD (2) People –Human body generates heat within itself and releases it by radiation, convection and evaporation from the surface (Sensible), and by convection and evaporation in the respiratory tract (Latent) –Heat generated depends on temp. and activity level –Both Sensible and Latent will enter space

18 HEAT LOAD117 PHYSICAL LOAD b) INTERNAL LOAD (3) Lights –Illuminants convert electrical power into light and sensible heat. –Lighting is either fluorescent or incandescent Motors –Direct heat to space Equipment & Appliances –Computers, Kettle, Refrigerators, Kitchen Equipment

19 HEAT LOAD118 ROOM SENSIBLE HEAT (RSH) EXTERNAL LOAD ONLY PRODUCES SENSIBLE LOAD INTERNAL LOAD PRODUCES BOTH SENSIBLE AND LATENT PRODUCE IN THE ROOM ONLY ROOM SENSIBLE HEAT (RSH) IS THE TOTAL AMOUNT OF ALL THE SENSIBLE HEAT PRODUCE IN THE ROOM ONLY

20 HEAT LOAD119 ROOM LATENT HEAT (RLH) SINCE SOME OF THE INTERNAL HEAT LOAD ALSO PRODUCES LATENT HEAT PRODUCE IN THE ROOM ONLY ROOM LATENT HEAT IS THE TOTAL AMOUNT OF ALL THE LATENT HEAT PRODUCE IN THE ROOM ONLY

21 HEAT LOAD120 ROOM LOADS At this point all ROOM LOADS (both Sensible and Latent) components have been considered. Adding all the sensible loads = RSH Adding all the latent loads = RLH Adding both the RSH + RLH = Room Total Heat (RTH)

22 HEAT LOAD121 If there was no heat gained or lost between the coil of the air handling unit and supply terminal,the temperature of the air leaving the coil would be the same as the temperature of the air entering the room. In a real system, however the losses exist as follows; PHYSICAL LOAD c) OTHER LOAD

23 HEAT LOAD122 SUPPLY –duct heat gain when duct pass through space of higher temp. –duct leakage loss loss of supply air due to quality of workmanship, this will result loss in sensible and latent PHYSICAL LOAD c) OTHER LOAD

24 HEAT LOAD123 SUPPLY AIR –fan heat (draw through) heat from fan motor –bypassed outdoor air because the coil is not a perfect cooling device, a portion of the air passes through the coil completely unaltered in temperature and humidity resulting in a sensible and latent loss of supply air PHYSICAL LOAD c) OTHER LOAD

25 HEAT LOAD124 EFFECTIVE ROOM SENSIBLE HEAT (ERSH) ERSH IS THE TOTAL SENSIBLE HEAT PRODUCE IN THE ROOM + ALL HEAT GAIN IS SUPPLY DUCT + BYPASS OUTDOOR AIR HEAT (SENSIBLE) ERSH = RSH + S.D HEAT GAIN + BYPASS OA

26 HEAT LOAD125 EFFECTIVE ROOM LATENT HEAT (ERLH) ERLH IS THE TOTAL LATENT HEAT PRODUCE IN THE ROOM + SUPPLY DUCT LEAKAGE LOSS + BYPASS OUTDOOR AIR HEAT (LATENT) ERLH = RLH + S.D LEAK LOSS + BYPASS OA

27 HEAT LOAD126 EFFECTIVE ROOM TOTAL HEAT (ERTH) These loads are called effective since both the coil leaving air temperature and humidity level must be effectively be lower than conditions required at the room in order to absorb the losses along the way and then absorb the room load ERTH IS THE SUM OF –ERSH + ERLH

28 HEAT LOAD127 OUTDOOR OR VENTILATION LOADS –when outdoor air enters the air conditioning system through central air handling apparatus, the resultant sensible and latent loads show up as a load on the coil and not room PHYSICAL LOAD c) OTHER LOADS

29 HEAT LOAD128 RETURN AIR –duct heat gain duct passes through space whose temp. is higher –leakage gain duct at negative pressure, an inward leakage of warm moist air possible –fan heat (blow through) when using separate return fan of blow thru type PHYSICAL LOAD c) OTHER LOADS

30 HEAT LOAD129 GRAND TOTAL HEAT (GTH) The total load seen by the coil in the Central Air Handling Unit. Also referred to as Dehumidified Load Sum Room Loads + Supply Air Losses + Outdoor Air + Return Air Losses + GTH = ERTH + OA + Return Air Heat Gain

31 HEAT LOAD130 REFRIGERATION LOAD Two additional loads are introduced to the refrigeration machine which are not experienced by the coil. They are –Piping sensible heat gain –Pumping heat gain

32 HEAT LOAD131 ENERGY & BUILDING SERVICES AIR-CONDITIONING LIGHTING OFFICE EQUIPMENT SOLAR GAIN OCCUPANCY FRESH AIR (DEHUMIDIFICATION)

33 NEXT PROCEED TO PSYCHROMETRIC CHART (PSYCHRO 1)