IDC 机房精确送风节能技术介绍 福州 2012.12. 一、精确送风技术介绍 二、仓科信息楼节能经验总结 关键字:机房评估、送风方式、 系统组网、关键技术 关键字:机房介绍、实施要点.

Slides:



Advertisements
Similar presentations
Attack: Left - Wing.
Advertisements

The Three Rs of Copyright Law Your Name. Copyright on the Internet Know the rules. Use ethical judgments. Practice the three Rs.
The Three Rs of Copyright Law Your Name. Copyright on the Internet Know the rules. Use ethical judgments. Practice the three Rs.
Apply the Distance & Midpoint formulas Find the distance and the midpoint Find the missing endpoint.
Technology How Can You Use Technology Better. Intro - I am a technology expert I am a boss I have an EA.
Chapter 6 Differential Analysis of Fluid Flow. 06_01.
Are Health Care Workers At Risk?. Non-infected (n=5) Infected 75% (n=15) DoctorsNurses Non-Infected (n=4) Infected 79% (n=15) Non-infected (n=18) Infected.
9.7 Segment Lengths in Circles
Ch Electricity IV. Measuring Electricity (p )  Electrical Power  Electrical Energy.
Mrs. Rivas Practice 6-2 to 6-5 Worksheet. Mrs. Rivas.
Congruence in Right Triangles
Rotation #1 - Serve Net M/L 6 M3M3 OH 2 OH 5 S1S1 RS 4 Rotation #1 - Serve.
Base Defense Net M/L MOH S RS Base Defense. Rotation #1 - Serve Net M/L 6 M3M3 OH 2 OH 5 S1S1 RS 4 Rotation #1 - Serve.

Sequence VID Consortium FTP Matrix Oils – Phosphorus Retention During AMA Mileage Accumulation Jim Linden GM R&D February 22, 2007.
March 2010 Target Group Control System of production furnace for SPES project Results and progress status march 2010.
Copyright © 2011, Research To Practice, All rights reserved. National Patterns of Care Study in Breast Cancer Launched October US-based community.
EXAMPLE 3 Find lengths using Theorem Use the figure at the right to find RS. SOLUTION 256= x 2 + 8x 0= x 2 + 8x – 256 RQ 2 = RS RT 16 2 = x (x +
A. Beuret MedAustron Power Converters ~ 300 units required for Magnet Could be distributed into 5 family.
INAlA TECHNOLOGIEs Installation Training:
INAlA TECHNOLOGIEs Installation Training:
INAlA TECHNOLOGIEs Installation Training:
Land Connect Developers launches in P-II Zone, North Delhi.
Sl. No. ParticularsPercentage of consideration 1On Booking / Signing of Agreement15% 2Upon Commencement of Ground Floor20% 3Upon.
© Oxford University Press 2011 IP The National Grid: Power transmitted The National Grid: Power transmitted.
© IDC, IIT Bombay 2 Will This Bicycle Work? © IDC, IIT Bombay 3 Conceptual Models.
Barracuda: Content Security Appliance Market Leader Source: IDC Worldwide Quarterly Security Appliance Tracker, Q4 2014, Mar 2015 Note: Total Shipments.
Integrated Purpose-Built Backup Market Leader
Connector Function Input I/O Output I/O
UMAC 구성예 (1) ▪ CPU (w/ WD Board) - Ethernet (TCP/IP)
Learning Targets I can identify similar polygons. I can write similarity statements. I can find missing parts of similar figure.
PRICE LIST Basic Price (For 1, 2, 3 & 3+SQ Only) : Rs. 6000/- (Per Sq. Ft.) PLC (Park Facing) : Rs. 100/- (Per Sq. Ft.) PLC (upto 5th Floor) : Rs. 100/-
Apply the Distance & Midpoint formulas
Consecutive Dispensing
Analysis of Wind Speed Data for Determining Wind Energy Potential in Billings, MT and Huron, SD By Keaton Belli EAS 4803.
RS 232- interface 2fold, MDRC EA/S 232.5
150 lm/W Reference guide SAW8Q24D (MJT 5630D 2-cell) Driver sales team
Date of download: 3/6/2018 Copyright © ASME. All rights reserved.
RS 45/M-160/M BLU RS 28/M-190/M New.
Toshiba S-MMS vs LG MULTI V Plus II
Hayt et. al. Chapters
Year: 1997 Low commitment Medium commitment High commitment
Heat Pumps For Energy Efficient / Economical Hot water Generation
آشنایی با توربین انبساطی و کاربرد آن‌ در نیروگاه‌های تولید برق
IV. Measuring Electricity
Art of Reading Smoke
Pedagogical Implications of PowerPoint
ttyTHS0 (1.8V) ttyTHS1 (1.8V) DAC GPS HMC764 =1kW =2.6kW 0-12V opa277
Source Transformation
Number of flowering plants 1999 (log-scale) Compatibility (%)
Warm-Up Add or subtract. 1) (5x2 + 4x + 2) + (-2x + 7 – 3x2)
доц. д-р Виолета Цакова катедра “Интелектуална собственост”, УНСС
OCP Engineering Workshop 2017
ISKCON DISCIPLES COURSE
Title of notes: The Percent Proportion
Complex Numbers Exam Questions
A Weighted False Discovery Rate Control Procedure Reveals Alleles at FOXA2 that Influence Fasting Glucose Levels  Chao Xing, Jonathan C. Cohen, Eric Boerwinkle 
Survey of the 2.45GHz microwave field
Difference between Compound Interest & Simple Interest.
Part 1 Table: current, VBE, Vin vs. Vout Sketch Error estimate Vout1
*** Series 3RS Version 1, ***
Дзяржаўны герб нашай краіны × П М Д З І Ц К Г.
All about right triangles
If AD = 10, DC =6, and ED = 15, find DB.
Calculating Ion Concentration from pH
Add an e to the end. Change the m to an s. What did you make?
Finding Interest and amount Start.
a4%97/%e0%a4%89%e0%a4%ae%e0%a5%8d%e0%a4%ae%e0%a5%80%e0%a4%a6 %e0%a4%b5%e0%a4%be%e0%a4%b0-
Percentage of a number.
Calculated Parameter Value
Presentation transcript:

IDC 机房精确送风节能技术介绍 福州

一、精确送风技术介绍 二、仓科信息楼节能经验总结 关键字:机房评估、送风方式、 系统组网、关键技术 关键字:机房介绍、实施要点

一、精确送风技术介绍

一、背景 4 随着计算机本身和应用技术的发展,计算机功能越来越来越强,运算速度越来越快。 而计算机日趋小型化,电子元件的排列越来越密集,使计算机单位体积的散热量也越来越 大。其高功耗、高集成度、高热密度、高保障要求的特点明显区别于传统机房的计算机, IDC 机房的机架排列方式和机架内发热特点也与传统机房不同,因此气流组织的问题在 IDC 机房中至关重要,将直接影响到机房的可靠性、可用性、经济性。 精确送风就是将空调送出的冷空气,通过可控制的风道送到通讯设备的前端,最大 程度的利用空调送出的冷量与通讯设备的发热量进行交换,改善机房的冷热气流组织,有 效避免通讯设备出现高温或局部过热现象。 系统以 “ 先冷设备、再冷环境 ” 的工作方式,根据不同机柜发热量的需求,采用冷通道 封闭的方式,实现冷量根据机架发热 “ 按需分配 ” 的可变风量精确送风,既避免机房热区带 来的安全隐患,又能实现机房冷量的合理分配,大大地提高空调的利用效率,节省电能。

二、机房评估 机房总功率和电量 UPS 配置、转换效率 配电系统效率 IT 设备总功率和效率 空调总制冷能力 空调运行总功率和电量 空调轮机运行状态 冷能配送方式(直吹式、上 送风、下送风) 冷能配送效率 设备受冷方式 机柜散热结构 冷热气体混合度 冷能利用率 回风气流返回路径 回风气流顺畅度 回风气温 空调的设定回风温度 分布式温度划分 隔温保温措施 缝隙封堵 辅助设施优化

三、工作示意图 上送风方式精确送风 冷热空气隔离 空调冷量直接送至机架,先冷设备 按需供冷,智能调节机架送风量

三、工作示意图 下送风方式精确送风 改善以往底部送风,受底层设备阻挡,导致上层设备过热隐患 侧向送风,设备均匀受冷 送风量可变调节,提升冷源利用效率

四、系统组网图 新风

五、关键技术 A 、全密封冷通道精确送风 全密封标准化前门送风器 可快速在线施工,无需对原有机架做任何改造 冷热气流高效隔离,提高冷源利用效率

五、关键技术 B 、风量智能调节 智能动态调节风量,根据机架热量按需供冷 故障告警 RS485 总线联网监控 全自动运行,节省管理成本 自动 / 手动双模式切换

五、关键技术 C 、机柜温度检测 检测机架的前后侧空间温度,通过风量控制模块动态调节机架送风量 实时监测机架内发热状况,为监控终端提供高低温告警信息 快速定位过热点,提高维护效率 为设备运行环境提供分析数据

六、设备介绍

系统介绍 通过图形化界面显示空调、风阀工作状态、机 房温度 为用户提供直观、简洁的数据查看方式 所有设备运行状态均能以组态的方式呈现 组态界面可按分组、分层等方式灵活配置, 可根 据用户需要快速切换机房设备分布图 机房精确送风系统平台 空调组态图设备柜组态图风阀组态图机房分布监控

二、仓科信息楼节能经验总结

机房面积为 579 ㎡,楼层高度 4.3m ,活动地板离地高度 0.5m ; 机柜布置有 13 列,共 161 架,发热设备设计总功率为 549KW ; 阿尔西空调 50E2A3 共 12 台,总制冷量: 600KW ,总风量: m³/h 供冷方式为活动地板下送风,空调自然上回风模式。 机房现状

1. 空调回风管道布置 2. 服务器机柜的冷热气流隔离 3. 机柜供冷精确控制 4. 引入外界新风系统 5. 精确送风、新风与空调的联动控制 精确送风节能技术实施要点

 在每条热通道正上方布置一条回风管道,连接至南北两侧空调 回风口,提高机柜热空气回收效率,避免远端设备热源滞留,引起 局部热岛现象。  回风管道采用镀锌钢板材质,不用做隔热处理,既起到回收热 空气目的,又达到散热的作用。  网格化管网设计 1. 空调回风管道布置

网格 化管 网 送风区 域可变 按需 回风 互为 主备 1. 空调回风管道布置

2. 服务器机柜的冷热气流隔离 柜内服务器层间间隙采用盲板封堵,避免冷空气损失。 进风口 出风口 盲板 侧面

增加盲板后的效果 盲板

在机柜前后侧分别布置湿度、温度传感器,实时检测机架内发热状况; 通过检测机柜的入口温度与出口后侧的温度来联动风阀控制模块对风量进行自动调节。 3. 机柜供冷精确控制

4. 引入外界新风系统 机房共配置 8 套下送风新风机组,总风量 m³/h 。 分别位于机房西北两侧。

4. 引入外界新风系统  一年中有多少天可以引入新风? 根据福州地区历年月平均温度测算 引入条件:室外温度 ≤20 ℃

多种传感器配合工作 多道滤网过滤室外空气 节能控制主机统一管理 4. 引入外界新风系统

5. 关于精确送风、新风与空调联动控制的技术分析 技术概要: 对于精确风量调节、空调供冷、新风引入而 言,其三者都是围绕机柜送风而服务的。机柜工 作环境最重要的两个量是温度与湿度。

 机房发热功率的大小与新风或空调设备开启数量存在正比 关系。  当室外环境达到新风引入条件时,新风系统运行需对空调 进行联动控制。当室外环境条件不满足引入新风时,释放 对空调的控制权,由空调接管。  节能控制主机对空调、风机持续进行巡检。 5. 关于精确送风、新风与空调联动控制的技术分析

 关闭空调台数的控制:新风供应的总冷量 / 单台空调的制 冷量 = 关闭空调的台数  新风的总供冷量 =( 排风温度 - 进风温度 )* 新风总送风量 * 空气热比容 * 空气密度  即使是未满足新风引入条件时,也可对空调进行控制。  当机房设备总发热量远小于空调配置总冷量时,空调是没 必要全部投入运行的,这个时候就需要节能控制系统接管 空调。因此节能系统一直在不停实时采集设备的送回风温 度,对空调进行控制调节。 5. 关于精确送风、新风与空调联动控制的技术分析

温州创力随时恭候您的垂询: 地址:温州市高新产业园区 10 号小区 电 话: 售后热线: 传真: 感谢您对创力电子有限公司的关心与支持!