Calculated Parameter Value

Similar presentations


Presentation on theme: "Calculated Parameter Value"— Presentation transcript:

1 Calculated Parameter Value
Table 4. Inverter summary Parameters Calculated Parameter Value Inductive Load(Pind) 3139W As per Table 3 Resistive Load(Pres) 9876W Total Continuous output power (TP) 13kW Efficiency (hinv) 90% As per inverter data sheet [13] Input power to the inverter (TP1) 14.5kW Using Equation4 Input DC voltage (Vdc) 360VDC Input DC current to inverter (Idc) 40ADC Using Equation5 Total Inverter Power (Pinv1) 24kW Using Equation 1 Power factor (PF) 0.8 KVA rating (PKVA) 30KVA Using equation 3 Energy coming from inverter (Edaily) 26kWh (in Summer) From Table 3 Energy input to inverter (Einv) 28.8kWh Using equation 6 Output AC voltage 240VDC Number of phase Three phase Types Solar PCU or Hybrid type MPPT voltage from PV (CCvolt) 500VDC Abhik Milan Pal et al. Designing of a Standalone Photovoltaic System for a Residential Building in Gurgaon, India. Sustainable Energy, 2015, Vol. 3, No. 1, doi: /rse-3-1-3 © The Author(s) Published by Science and Education Publishing.


Download ppt "Calculated Parameter Value"