Fire Detector Placement

Slides:



Advertisements
Similar presentations
International Building Code
Advertisements

Initiating Devices Manual Fire Alarm Boxes Ionization Smoke Detectors
Philip Anderson National Sales Manager System Sensor Canada.
Denver Fire Alarm Test Prep
NFPA 72 and NFPA 101 Supervised Automatic Sprinkler System Overview
Carbon Dioxide Systems 1.Carbon dioxide properties 2.Storage 3.Uses 4.Limitations 5.Types of systems 6.Local Application 7.Total Flood.
LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS
3.1.9 Student Book © 2004 Propane Education & Research CouncilPage Replacing Valves and Fittings in ASME Tanks Replacing ASME tank valves and fittings.
Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned company, operating in 23 countries. We are passionate about.
Week 8 Stairs and Fireplaces. Objectives This chapter discusses stairs and fireplaces: types, sizes, code requirements, design considerations, and how.
© Siemens Industry, Inc Confidential / Drive Your Business Forward Ignite the Power of New Products and Partnerships Siemens Fire Partner Summit.
Local Application Total Flooding System: (NFPA 12) A system consisting of a supply of carbon dioxide arranged to discharge into, and fill to the proper.
Competency: Design and Draw Stair Systems
N.F.P.A. 13R Justin Bohlmann FIR-204.
Doug Hohbein Chief Plans Examiner Nebraska Fire Marshal Agency
Welding, Cutting, & Burning. GENERAL HAZARDS General hazards of welding include: –Impact –Penetration –Harmful dust –Smoke –Fumes –Heat –Light radiation.
Fire Alarm System Notification Appliances
NICET Exam Prep Level II, Class 3.
IBC 2006 Chapter 5 Building Height and Areas After determining occupancies, the code analysis determines what height and areas are allowable for the occupancy.
Chapter 19 Electrical Plans.
CTC 422 Design of Steel Structures
HOT WORK PROCEDURES Welding and Hot Work, such as brazing or grinding present a significant opportunity for fire and injury. CCR Title 8 Sub Chapter 7,
Enclosure Fire Dynamics
Fire.
Updates to NFPA 13 What’s New in the 2013 Edition Kenneth E. Isman, P.E., F.S.F.P.E. For the European Fire Sprinkler Network’s Fire Sprinkler International.
Floor Systems and Foundation Support
Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National.
CNG STATION & GARAGE MODIFICATION CODES & STANDARDS Graham Barker Business Development Manager.
OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH
SMOKE DETECTOR PERFORMANCE FOR LEVEL CEILINGS WITH DEEP BEAMS AND DEEP BEAM POCKET CONFIGURATIONS Daniel J. O’Connor P.E. Schirmer Engineering Corporation.
Patrick Thornton, SNS/FPE June 9, 2008
Fire Alarm System Initiating Devices
Q What does this picture show and who is in the best position?
Fire and Emergency Services Company Officer — Lesson 17 Fire and Emergency Services Company Officer, 4 th Edition Chapter 17 — Preincident Planning.
Means of Egress and Fire Protection
Atrium Fire Protection
Fire-Related Properties of Materials Chapter 7. Mehta, Scarborough, and Armpriest : Building Construction: Principles, Materials, and Systems © 2008 Pearson.
Preparing Foundations for Cylinders & ASME Tanks
Ultra High-speed Explosion Suppression Systems and Ultra High-speed Water Spray Systems Chapter 7 Page 209.
QUIRKY HQS INSPECTIONS Seanna Collins Lincoln Housing Authority September 16, 2015.
R ULE 2 – T HE C OURT What You Need To Know. T HE C OURT AND M ARKINGS There shall be at least 6 feet of unobstructed space outside the boundary lines.
Fire Safety By Alicia Civile and Alexandra Fernandez.
Chapter 23 Lighting Design Process: Final Phases © 2006 Fairchild Publications, Inc.
MINNESOTA CHAPTER AUTOMATIC FIRE ALARM ASSOCIATION Requirements of the 2003 Minnesota State Fire Code relating to Group R Occupancies September 14, 2006.
Chapter 5-Fire Safety Developing Effect Ways to Prevent and Deal With Fires in Your Home.
Engineering Analysis of NFPA 285 Tested Assemblies
Means of Egress and Fire Protection. Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers each year There is a long.
Student Book © 2004 Propane Education & Research CouncilPage Performing Gas Distribution System Leak Checks Requirements for vapor distribution.
ID 308 Construction + Materials IV: Construction Documents Prof. Brody Endicott College Systems Coordination.
2 IMPACT - THE FIRE PERMIT = Hot Work Permit 3 Welcome ! This course is linked to the use of IMPACT, so it is assumed that: You know how to use IMPACT.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
code calculations, construction drawings
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
Chapter 24 Chimneys and Fireplaces Copyright Goodheart-Willcox Co., Inc. May not be posted to a publicly accessible website. Explain how masonry chimneys.
ROOFS CHAPTER 7. ROOF SHAPES: GABLE ROOF SHAPES: HIP.
Subpart F - Fire Protection & Prevention ( ) Flammables/combustibles - Approved containers Fire protection program/equipment 2A fire extinguishers.
ME444 ENGINEERING PIPING SYSTEM DESIGN
Plumbing Radiant Heating & Cooling Turf Conditioning Permafrost Ice and Snow Melt Ecoflex ® SupportSustainabilityEngineered PolymerCommercial SystemsIntroductions.
Hot /Cold Aisle Containment  Traditional Data Center/Telco designs are changing significantly!
Structural Steel Construction
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
Flammable Liquids Directorate of Training and Education
Carbon Dioxide System Design
Dangers of Engineered Wood I-Beam Floors
The Indoor Air Quality in a Multi-garage
Smoke Detector Installation Guidelines
Chapter 19 Electrical Plans.
Fabric Air Dispersion Systems
NICET Fire Alarm Tech Level 1 Practice Test # 10
Smokes extraction principle
Presentation transcript:

Fire Detector Placement Chapter 14 Page 425

Objectives Describe how detectors are listed by Underwriters Laboratories (UL) Explain why detectors are not permitted to be positioned too close to the corners of a room where the ceiling meets the wall Determine the spacing of detectors in a room with a smooth flat ceiling Determine locations of detectors in a room with unusually configured walls

Objectives Space detectors in a corridor Discuss rules for placement of detectors on sloped ceilings Determine the locations of detectors on ceilings with solid joists or beams Explain why detectors are not permitted to be located too close to supply air ducts

Objectives Describe the effect of floor-mounted partitions on a ceiling jet Determine the optimum locations for beam detectors, flame detectors, gas detectors, and duct detectors

Heat Detector Listings Heat detectors are listed by UL as follows: Heat detector type Temperature rating Listed smooth ceiling spacing between detectors Listed smooth ceiling spacing to wall or partition Contact arrangement Detector model number

Smoke Detector Listings Smoke detectors are listed by UL under category UROX as follows: APPLICATION DETECTOR TYPE COMPATIBILITY RESTRICTIONS INSTALLATION CRITERIA

Spot-Type Detector Spacing Corner Placement for Spot-Type Detectors: The 4-Inch Rule Smooth Ceiling Spacing of Spot-Type Detectors Spot-Type Detector Spacing for Unusual Wall Configurations Spot-Type Detector Spacing in Corridors

Spot-Type Detector Spacing Figure 14-1. Ceiling jet dynamics for corner fires; NFPA 72 prohibits spot detectors being placed within the “blind spot”

Spot-Type Detector Spacing Figure 14-5. Illustration of .7 Smax rule, or “circle of coverage”

Ex. 14-1: Ceiling Spacing of Spot-Type Detectors

Ex. 14-2: Ceiling Spacing of Spot-Type Detectors – Spacing Less than Listed Spacing

Ex. 14-2: Ceiling Spacing of Spot-Type Detectors – Spacing Less than Listed Spacing

Ex. 14-2: Ceiling Spacing of Spot-Type Detectors – Spacing Less than Listed Spacing

Spot-Type Detector Spacing Spot-Type Detector Spacing for Smooth Peaked Ceilings Spot-Type Detector Spacing for Smooth Shed Ceilings Spot-Type Detector Spacing for Solid Joist Construction

Spot-Type Detector Spacing Figure 14-8. Sectional view of a peaked ceiling; a detector must be placed within 3 feet (900 mm) of the roof peak, and spacing is measured along the floor, not along the slope

Spot-Type Heat Detector Spacing for Beamed Construction Body Of NFPA 72 Spot-Type Heat Detector Spacing for Beamed Construction—Annex of NFPA 72 NFPA 72 requirements Effect of Ceiling Height on Spot-Type Heat Detectors

Ex. 14-3: Detector Placement for Beamed Construction

Ex. 14-3: Detector Placement for Beamed Construction

Spacing Of Line-Type Heat Detectors Spacing requirements (see Table 14-1, Page 441): Line-type detectors on a ceiling must be not more than 20 inches from the ceiling Line-type detectors are mounted to the bottom of solid joists Line-type detectors are mounted to the bottoms of beams, where beams are less than 12 inches deep and less than 8 feet apart on center

Spot-Type Smoke Detector Spacing Spacing near Air Vents Spacing near Floor-Mounted Partitions Spot-Type Smoke Detection for Raised Floors and Suspended Ceilings Spot-Type Smoke Detectors in High Air Movement Areas Spot-Type Smoke Detectors for Smoke Control Systems

Spot-Type Smoke Detector Spacing P.443 Figure 14-13. Smoke detector spacing for beamed construction

Projected Beam Smoke Detector Spacing P.451 Beam detectors work on the following principles: Beam detector consists of sender and receiver NFPA 72 (2007) requires that The sender and receiver be mounted firmly to avoid movement of the projected beam and possible unwanted alarms The projected beam remain unobstructed by storage, ceiling-mounted equipment, or other objects that would result in a trouble condition on the FACU and prohibit the detectors from sensing smoke

Projected Beam Smoke Detector Spacing Smoke obscures the projected beam and reduces transmission of the infrared beam to the receiver Beam detectors are for indoor use, and are to be mounted to stable surfaces Mirrors can be used with projected beams, per manufacturer’s instructions, provided that mirrors are mounted to stable surfaces

Projected Beam Smoke Detector Spacing Spacing for smooth ceilings must be per manufacturer’s instructions For beamed construction, some manufacturers require that beam detectors be mounted in each beam pocket if Beam depth exceeds 18 inches Support beam spacing is greater than 8 feet

Projected Beam Smoke Detector Spacing For solid joists less than 8 inches in depth, some manufacturers require that the ceiling be considered as a smooth ceiling NFPA 72 requires beam detectors on sloped ceilings be installed parallel to peak

Projected Beam Smoke Detector Spacing Figure 14-23. Sloped ceiling installation for beam detectors

Flame Detector Placement A flame detector can perceive a fire that is viewed within its cone of vision Its ability to sense a fire depends on Position of the fire within the cone of vision Distance from the fire to the detector Size of the fire Matching the spectral response of the detector to the spectral emissions of the fire

Flame Detector Placement Each flame detector is listed for a specific viewing angle that defines the cone of vision Placement of flame detectors usually requires considerable field experience and consultation with the manufacturer

Gas-Sensing Detector Placement May sense a potentially hazardous condition in advance of ignition, or may sense gaseous combustion by products Spaced in accordance with NFPA 72 (2007) and their listing NFPA 72 has replaced detailed spacing requirements on gas-sensing fire detectors

An Engineering Approach To Heat Detector Placement Best way to ensure detection in a building Conduct fire testing in numerous areas Determine best detector Determine best detector locations Calculated Heat Detector Placement per NFPA 72 Annex B (2007 Edition)

Summary The placement of detectors must consider Type of fire Dynamics of the ceiling jet Attributes of the detector Properties of the ceiling or surface onto which the detectors are mounted NFPA 72 provides minimum requirements for the spacing of detectors

Summary Designers must analyze the anticipated fire and the space requiring detection Annex B of NFPA 72 provides engineered approach to positioning detectors Specific requirements for Heat detectors Smoke detectors Beam detectors Gas detectors