Page 1 AMDS Selection. Page 2 Contents Introduction Selection Consideration Selection Process Software Demonstration.

Similar presentations


Presentation on theme: "Page 1 AMDS Selection. Page 2 Contents Introduction Selection Consideration Selection Process Software Demonstration."— Presentation transcript:

1 Page 1 AMDS Selection

2 Page 2 Contents Introduction Selection Consideration Selection Process Software Demonstration

3 Page 3 Introduction

4 Page 4 Sample of Installation

5 Page 5 Selection Consideration

6 Page 6 Main Factors to consider during Piping Selection Location of equipmentLocation of equipment Indoor UnitIndoor Unit Outdoor UnitOutdoor Unit Refnet & Distributor JointRefnet & Distributor Joint Unit & Piping Selection These item will influence the piping layout and length of the design

7 Page 7 Some other factors to consider during Piping Selection Equivalent Piping LengthEquivalent Piping Length Type of Joint for branchesType of Joint for branches Outdoor capacity factorOutdoor capacity factor Piping length & height factorPiping length & height factor Refrigerant Pipe SpecificationRefrigerant Pipe Specification Unit & Piping Selection

8 Page 8 Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow: Equivalent length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap Equivalent Piping Calculation

9 Page 9 Restriction of Piping Length

10 Page 10 Important Factor to Consider Example: Outdoor Model : MDS100BR Pipe Diameter : 28.6 mm Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m

11 Page 11 When the equivalent length is more than 90% of the maximal real length of the main tubing, the gas pipe need to be increase to one size bigger (diameter). After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow: Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch Criteria 1 Criteria 2 Important Factor to Consider

12 Page 12 Important Factor to Consider Maximum allow actual length for 10Hp is 125m Calculated Equivalent Length is 116.1m Ratio of Equivalent Length over Maximum allow Actual Length= 92.88% Equivalent length is more than 90% of the maximal real length. Hence the gas Pipe of MDS100BR need to change. Example:

13 Page 13 Refrigerant Copper Pipe Specification : MDS-B Unit & Piping Selection

14 Page 14 Important Factor to Consider Example: Hence the gas Pipe of MDS100BR need to change from 28.6 mm to 39.40 mm After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X 0.5 + 20 Expanded Equivalent Length = 68.05 m

15 Page 15 Type of Joint for branchesType of Joint for branches Influence the piping layout designInfluence the piping layout design Outdoor capacity factorOutdoor capacity factor Influence by the design ambient temperature and indoor temperatureInfluence by the design ambient temperature and indoor temperature Piping length & height factorPiping length & height factor Influence by the location of outdoor and the total piping lengthInfluence by the location of outdoor and the total piping length Refrigerant Pipe SpecificationRefrigerant Pipe Specification Use to determine the branches diameterUse to determine the branches diameter Unit & Piping Selection

16 Page 16 Selection of branch joint / distributors for MDS Unit & Piping Selection

17 Page 17 MDS-Y1~Y4 dimensional drawing Unit & Piping Selection

18 Page 18 MDS-Y6 dimensional drawing Unit & Piping Selection

19 Page 19 MDS-Y7 dimensional drawing Unit & Piping Selection

20 Page 20 MDS-C1 dimensional drawing Unit & Piping Selection

21 Page 21 MDS-C2~C3 dimensional drawing Unit & Piping Selection

22 Page 22 Using Distribution Header may lead to imbalance refrigerant flow. Unit & Piping Selection

23 Page 23 Connection Type of Refnet Joint/Distributors Refnet Joint Refrigerant Pipe Work

24 Page 24 Connection Type of Refnet Joint/Distributor Distributor Refrigerant Pipe Work

25 Page 25 Connection Type of Refnet Joint/Distributors Refnet Joint Distributor Refrigerant Pipe Work

26 Page 26 Connection Type of Refnet Joint/Distributors Refnet Joint Distributor Refrigerant Pipe Work

27 Page 27 Cooling Capacity Correction Factor Unit & Piping Selection

28 Page 28 Heating Capacity Correction Factor Unit & Piping Selection

29 Page 29 Cooling cap. factor Cooling Capacity Correction Factor Unit & Piping Selection

30 Page 30 Heating Capacity Correction Factor Unit & Piping Selection

31 Page 31 Refrigerant Pipe Specification : MDS-A Unit & Piping Selection

32 Page 32 Refrigerant Pipe Specification : MDS-B Unit & Piping Selection

33 Page 33 Selection Process

34 Page 34 Example C A B D E F Building Type: Bungalow Unit & Piping Selection

35 Page 35 Requirement Cooling only model Ambient temperature : 40.0 °CAmbient temperature : 40.0 °C Indoor temperature : 21.0 °CIndoor temperature : 21.0 °C Other Information Piping length : 70mPiping length : 70m Height between I/O : 4mHeight between I/O : 4m Outdoor Unit located below indoorsOutdoor Unit located below indoors Unit & Piping Selection Example

36 Page 36 Indoor Requirement Unit & Piping Selection

37 Page 37 Example Total Indoor capacity is 32.3 kW Unit & Piping Selection

38 Page 38 Example Selection Criteria Total Indoor capacity must be range between 50% ~ 120% of the outdoor capacity.Total Indoor capacity must be range between 50% ~ 120% of the outdoor capacity. We recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor capacityWe recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor capacity Unit & Piping Selection

39 Page 39 Example Selected Outdoor : MDS120B Cooling Capacity: 32.5kW Comply to selection criteria Unit & Piping Selection

40 Page 40 Example Selected Outdoor and Indoor ModelSelected Outdoor and Indoor Model Unit & Piping Selection

41 Page 41 Example Outdoor Capacity factor Cooling only modelCooling only model Ambient temperature : 40.0 °CAmbient temperature : 40.0 °C Indoor temperature : 22.0 °CIndoor temperature : 22.0 °C 1.03 Unit & Piping Selection

42 Page 42 Example Piping length & height factor Piping length : 70mPiping length : 70m Height between I/O : 4mHeight between I/O : 4m Outdoor Unit located below indoorsOutdoor Unit located below indoors 91% Unit & Piping Selection

43 Page 43 Example Total Capacity = Outdoor Capacity X Outdoor Capacity Factor= Outdoor Capacity X Outdoor Capacity Factor X Piping length & height FactorX Piping length & height Factor = 32.5 kW X 1.03 X 94%= 32.5 kW X 1.03 X 94% = 31.47 kW= 31.47 kW Comply to requirement Unit & Piping Selection

44 Page 44 Example C A B D E F Unit & Piping Selection Building Type: Bungalow

45 Page 45 Example 1.Selection pipe diameter ABC D E MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Unit & Piping Selection

46 Page 46 Refrigerant Pipe Specification : MDS-B Unit & Piping Selection

47 Page 47 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Main pipe diameter : ø 15.88mm / ø 28.6mm Downstream capacity Point AA-B-C : 14.9 kW A-D-E : 17.4 kW Point BB-C : 8.4 kW D-E : 8.4 kW Unit & Piping Selection

48 Page 48 Refrigerant Pipe Specification : MDS-B Point AA-B-C : 14.9 kWA-D-E : 17.4 kW Unit & Piping Selection

49 Page 49 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Main pipe diameter : ø 15.88mm / ø 28.60mm A-D diameter : ø 12.70mm / ø 22.23mm A-B diameter : ø 9.52mm / ø 19.05mm Unit & Piping Selection

50 Page 50 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Point B B-C : 8.4 kW B-CCD25C : 6.5 kW Unit & Piping Selection

51 Page 51 Refrigerant Pipe Specification : MDS-B Point BB-C : 8.4 kWB-CCD25C : 6.5 kW (follow indoor pipe size) Unit & Piping Selection

52 Page 52 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW A-B: ø 9.52 / ø 19.05 B-CCD25C: ø 9.52 / ø15.88 B-C: Unit & Piping Selection

53 Page 53 Example Unit & Piping Selection

54 Page 54 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Main Pipe: ø 15.88 / ø 28.6 B-C: ø 9.52 / ø15.88 A-B: ø 9.52 / ø19.05 A-D: ø12.7 / ø22.23 D-E: ø9.52 / ø15.88 Unit & Piping Selection

55 Page 55 Example Selection of branch Select the refnet joint of point A A (liquid) : MDS-Y2 A (gas) : MDS-Y1 A-D diameter : ø 12.70 / ø 22.23 A-B diameter : ø 9.52 / ø 19.05 All unit in mm A Main Pipe diameter : ø 15.88 / ø 28.60 Unit & Piping Selection

56 Page 56 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Main Pipe: ø 15.88 / ø 28.6 B-C: ø 9.52 / ø15.88 A-B: ø 9.52 / ø19.05 A-D: ø12.7 / ø22.23 D-E: ø9.52 / ø15.88 Unit & Piping Selection

57 Page 57 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW Unit & Piping Selection

58 Page 58 Example Formula: G = ∑ Li* Gi Using liquid tube length to calculate required refrigerant. Add in refrigerant. G : Refrigerant charge amount L i : The each section of liquid tube length in all (m) G i : Charge amount per length ( g/m ) Unit & Piping Selection

59 Page 59 Example ABC DE MDS120B CCD 25C WMD 20G WMD 10G WMD 20G CKD 30A WMD 10G 6.5 kW 5.6 kW 2.8 kW 5.6 kW 9.0 kW 2.8 kW ø 15.88 (10m) ø 9.52 (5m) ø 9.52 (2m) ø 9.52 (4m) ø 6.35 (2m) ø 6.35 (5m) ø 6.35 (2m) ø 9.52 (5m) ø 12.7 (25m) Total Piping Length 15.88mm – 10m 12.7mm – 25m 9.52mm – 21m 6.35mm – 14m Unit & Piping Selection

60 Page 60 Example Additional charge amount : = ∑ Li* Gi = (Piping Length for 15.88mm X Refrigerant Charge Amount) + (Piping Length for 12.7mm X Refrigerant Charge Amount) + (Piping Length for 9.52mm X Refrigerant Charge Amount) + (Piping Length for 6.35mm X Refrigerant Charge Amount) = (10 X 180) + (25 x 120) + (21 x 80) + (14 x 50) = 7180 g Liquid tube diameter (mm) 6.359.5212.715.88 Refrigerant charge amount (g/m) 5080120180 Total Piping Length 15.88mm – 10m12.7mm – 25m 9.52mm – 21m6.35mm – 14m Unit & Piping Selection

61 Page 61 EXV Box EXV Box EXV Box EXV Box Electronic Expansion Valve Unit & Piping Selection

62 Page 62 Electronic Expansion Valve 2 units 1 unit 2 units Unit & Piping Selection

63 Page 63 Software Demonstration

64 Page 64 Unit & Piping Selection

65 Page 65 The End