SDB Demand-Controlled Ventilation: Preliminary Experiments Jay Taneja Software Defined Buildings Kickoff January 11 th, 2013.

Similar presentations


Presentation on theme: "SDB Demand-Controlled Ventilation: Preliminary Experiments Jay Taneja Software Defined Buildings Kickoff January 11 th, 2013."— Presentation transcript:

1 SDB Demand-Controlled Ventilation: Preliminary Experiments Jay Taneja Software Defined Buildings Kickoff January 11 th, 2013

2 SDB Motivation SDBs can improve comfort Indoor environmental quality is multifaceted Buildings are often overventilated Demand-controlled ventilation (DCV) DCV benefits from BOSS Architecture – Incorporates non-BMS sensors and data – Transactions ensure safe system state – Communication throughout buildings

3 SDB DCV: Standards and Sensors ASHRAE 62.1 and CA Title 24 CO2 sensors Works best in enclosed spaces Target max of 800 ppm CO2

4 SDB Baseline Ventilation

5 SDB Extreme Efficiency Description Preliminary control effort to limit ventilation as much as possible Combines an occupancy model, outside air damper control sequence, and significant reductions in default airflow levels

6 SDB Extreme Efficiency Ventilation

7 SDB DCV Description Incorporate Google Calendar data Proportional control (airflow reflects CO2) Prior to meetings: Increase airflow During meetings: Modulate minimum to reflect CO2 concentration Not during meetings: Only respond if CO2 approaches 800 ppm threshold

8 SDB Demand-Controlled Ventilation

9 SDB Results Ventilation StrategyAvg. AirflowAvg. Ventilation Power Time > 800 ppm Baseline222.2 cfm0.1765 kW6h 3m (3.6%) Extreme Efficiency79.8 cfm0.0616 kW10h 57m (6.5%) DCV40.2 cfm0.0272 kW17m (0.2%) Caveats – Not all weeks created equal – Could increase airflow to reduce violations DCV offers a combination of energy savings and increased occupant comfort at minimal cost.

10 SDB Next Steps Expansion in SDH – 7/12 rooms with calendar data have sensors – DCF in cleanroom using motion sensors Grid potential as a supply-following load – Minimal ability to shed (positive slack) – Substantial ability to sink (negative slack) – Incorporate MPC for balancing objectives Integrate with BAS – write once, run anywhere

11 SDB Questions? Jay Taneja


Download ppt "SDB Demand-Controlled Ventilation: Preliminary Experiments Jay Taneja Software Defined Buildings Kickoff January 11 th, 2013."