Presentation is loading. Please wait.

Presentation is loading. Please wait.

R. S. Govindaraju, J. E. Alleman, T. J. Cooper, T. P. Chan, V. Jain School of Civil Engineering Purdue University (SPR-2455, SPR-2456, SPR-2487) I-70 Greenfield.

Similar presentations


Presentation on theme: "R. S. Govindaraju, J. E. Alleman, T. J. Cooper, T. P. Chan, V. Jain School of Civil Engineering Purdue University (SPR-2455, SPR-2456, SPR-2487) I-70 Greenfield."— Presentation transcript:

1 R. S. Govindaraju, J. E. Alleman, T. J. Cooper, T. P. Chan, V. Jain School of Civil Engineering Purdue University (SPR-2455, SPR-2456, SPR-2487) I-70 Greenfield Rest Area Constructed Wetland Wastewater Treatment System Research Project March 19, 2004

2 June 11, 20152 Project location

3 June 11, 20153 ST-2ST-1 W-1 W-2 W-3 Biofiel d F-2 AS-3 AS-2 AS-1 AS-4 F-3 F-1 M-1 M-2 LS-2 LS-1 LS-3 LS-4 M-3 M-4 Effluent Inflow Septic tank Automatic sampler V-notch weir Lift station / dosing chamberMagnetic flow meter Wetland cell Recirculation North Rest Stop South Rest Stop Design layout

4 June 11, 20154 Hydraulic issues Undersized wetland dosing pumps (LS-1)  Surges from the eastbound side  High rate of recirculation (~83%) Solutions  Reduce recirculation rate  Addition of surge tank

5 June 11, 20155 Flow measurements Weir / flume measurements are NOT accurate  Backup due to overcapacity of LS-1 and LS-4  Inadequate calibration  Inherent error due to low flows Magnetic flow meters  More reliable  Erroneous spikes in the data

6 June 11, 20156 02/0102/0802/1502/22 0 1000 2000 3000 4000 5000 6000 Date Daily Flow Total (gal) Inflow (M-1) Outflow (M-4) Flume 1 Flume 2 Flume 3

7 June 11, 20157 9/25/2003

8 June 11, 20158 02/0102/0802/1502/2202/2903/07 0 2000 4000 6000 8000 10000 12000 Date Daily Flow Total (gal) Inflow (M-1) Outflow (M-4) Biofield (M-3) 02/0102/0802/1502/2202/2903/07 150 200 250 300 350 400 450 Daily Streamflow (cfs) Big Blue River

9 June 11, 20159 Wastewater test results 12/22/2003 SamplepH TSS (mg/L) NH 3 -N (mg/L) BOD 5 (mg/L) Sampler #18.8011083280 Sampler #38.246062225 Sampler #48.176065215

10 June 11, 201510 Wastewater test results 3/5/2004 SamplepH TSS (mg/L) NH 3 -N (mg/L) BOD 5 (mg/L) Sampler #18.40140136310 Sampler #27.94110122294 Sampler #37.7260131310 Sampler #47.656080226

11 June 11, 201511 Current status Only receiving wastewater from west-bound side No recirculation Flow-through with no drain-and-fill Biofield shut down till desired effluent quality is attained

12 June 11, 201512 To-do list Installation of SCADA system Surge tank addition Installation of weather station Re-calibration of weir and flume meters


Download ppt "R. S. Govindaraju, J. E. Alleman, T. J. Cooper, T. P. Chan, V. Jain School of Civil Engineering Purdue University (SPR-2455, SPR-2456, SPR-2487) I-70 Greenfield."

Similar presentations