1 Refer to Service Manual for details Fault codes

2 To retrieve fault codes from the remote controller.......... Press the ‘CHECK’ button for approximately ½ second Fault codes To clear fault codes from the remote controller.......... Press the ‘CHECK’ button and hold for approximately 15 seconds

3 To retrieve fault codes from the outdoor unit interface PCB Set SW01, SW02 & SW03 to ‘1’ Fault codes UI - - Outdoor unit no. Fault code (‘- -’ = no fault)

4 Code 0b Cause Float switch operation Float switch open circuit > 2 minutes Fault codes

5 Code 04 Cause No communication between inverter and interface PCB Fault codes

6 Code 08 Cause TS & TE sensors detect wrong change in temperature during heating operation > 5ºC after 5 minutes Fault codes

7 Code 11 Cause Indoor fan motor alarm Fan motor circuit connection fault Capacitor fault Fan motor fault Indoor PCB fault Fault codes

8 Code CF Cause No communication between fan motor PCB and main PCB at indoor unit. Fault codes

9 Code 14 Cause G-Tr short circuit protection Outdoor unit power source errorWiring error on inverter PCB AC fuse disconnectionInverter compressor fault Inverter PCB fault Fault codes

10 Code 17 Cause Inverter compressor DC current detected during off cycle Fault codes

11 Code 1d Cause Overload protection (if measured by DC sensor four times) Inverter compressor overload current Fault codes

12 Code 1F Cause High motor current (if measured by DC sensor four times) Excessive current detected after high current release Fault codes

13 Code 21 Cause Inverter compressor high pressure switch operation Pressure sensor >363 psig Fault codes

14 Code 22 Cause High pressure Pressure sensor > 406 psig Fault codes

15 Code 87 Cause Missing phase Missing phase on outdoor unit power supply Fault codes

16 Code 89 Cause Indoor units over capacity No. of connected indoor units over capacity Incorrect set-up of indoor unit capacity Fault codes

17 Code 8d Cause Reduction in the number of connected outdoor units Outdoor unit system set-upOutdoor unit power source Comms. cable error between o/d unitsBUS communication error Interface PCB fault Fault codes

18 Code 8F Cause Duplicated terminal outdoor addresses Address set-up of outdoor unit duplicated Interface PCB error Fault codes

19 Code 93 Cause Indoor unit TC1 sensor fault Fault codes

20 Code 94 Cause Indoor unit TC2 sensor fault Fault codes

21 Code 95 Cause Communication error between indoor/outdoor units PQ connection error between indoor/outdoor units Connection error at indoor PCB Outdoor interface PCB error Fault codes

22 Code 96 Cause PQ connection error between indoor/outdoor units Incorrect number of indoor units Wiring connection error on central controller Fault codes

23 Code 97 Cause BUS communication alarm Connection error in XY network No outdoor communication received by central controller Number of indoor units has fallen since last set-up Fault codes

24 Code 98 Cause BUS communication alarm Duplicated network addresses Miswiring of XY communication cables Indoor PCB/central controller error Fault codes

25 Code 99 Cause Remote controller alarm Duplicated No. 1 indoor unit Miswiring of remote controller cables Remote controller error Indoor PCB error Fault codes

26 Code 9A Cause Unauthorised temperature change Used during self-check function TC1 detects temperature change >5ºC during off cycle Fault codes

27 Code 9F Cause Insufficient change in indoor coil temperature TC1 and TC2 do not fall more than 4ºC below TA sensor Indoor PMV connection error Fault codes

28 Code A0 Cause TD1 sensor open/short circuit Misconnection at CN502 Fault codes

29 Code A1 Cause TD2 sensor open/short circuit Misconnection at CN503 Fault codes

30 Code A2 Cause TS1 sensor open/short circuit Misconnection at CN504 Fault codes

31 Code A6 Cause High discharge temperature Sensor TD1 detects > 130ºC three times Cooling bypass PMV error Fault codes

32 Code A7 Cause High suction temperature Sensor Ts detects > 60ºC for 10 minutes - three times Fault codes

33 Code AA Cause Pd pressure sensor alarm Connection error at CN501 Interface PCB error Fault codes

34 Code Ab Cause Misconnection of Pd/Ps pressure sensors Pd/Ps sensor error Compressor inverse operation Fault codes

35 Code AE Cause High discharge temperature at low load Sensor TD1 detects > 110ºC three times Fault codes

36 Code AF Cause Phase rotation incorrect or incomplete Fault codes

37 Code b4 Cause Ps sensor alarm Ps sensor error Ps sensor connection error Compressor error Fault codes

38 Code b5 Cause External alarm circuit Notified by resistive connection(10K ohms) to CN17 on indoor unit PCB Fault codes

39 Code b6 Cause External stop circuit Notified by short circuit across CN17 on indoor unit PCB (Repeated as Eb code at outdoor unit) Fault codes

40 Code Eb Cause External stop circuit Notified by short circuit across CN17 on indoor unit PCB (Repeated as b6 code at indoor unit) Fault codes

41 Code b7 Cause Fault in networked slave unit Code available at central controller when slave units in group have fault code (Full code available at local remote controller and inverter outdoor unit) Fault codes

42 Code b9 Cause Indoor pressure sensor alarm Output voltage error Fault codes

43 Code bb Cause High discharge temperature Sensor TD2 detects > 130ºC three times Fault codes

44 Code bd Cause Inverter unit - DOL compressor operation detected during off cycle Pd & Ps pressure sensors Discharge temperature sensors Fault codes

45 Code bE Cause Low pressure Suction pressure < 3 psig Fault codes

46 Code d1 Cause Master outdoor unit set-up alarm No. of connected inverter units incoorect Incorrect set-up of master outdoor unit Outdoor unit interface PCB fault Fault codes

47 Code d2 Cause Defective slave outdoor unit Fault codes

48 Code d3 Cause TH sensor alarm (IGBT) Fault codes

49 Code d4 Cause TK1 sensor alarm TK1 sensor open/short circuit Faulty connection at CN516 Interface PCB fault Fault codes

50 Code d5 Cause TK2 sensor alarm TK2 sensor open/short circuit Faulty connection at CN515 Interface PCB fault Fault codes

51 Code d6 Cause TK3 sensor alarm TK3 sensor open/short circuit Faulty connection at CN507 Interface PCB fault Fault codes

52 Code d7 Cause Oil level low Measured by TK1, TK2 and TK3 Fault codes

53 Code d8 Cause No oil flow during management process Measured by TK1 primary side No temperature change Fault codes

54 Code d9 Cause No oil flow during management process Measured by TK2 secondary side No temperature change Fault codes

55 Code dA Cause Inverter heat sink TH IGBT sensor too hot Fault codes

56 Code db Cause No oil flow during management process Measured by TK1 and TK2 No temperature change Fault codes

57 Code dC Cause Oil temperature too high Measured by TK1 primary side at > 50ºC Fault codes

58 Code dd Cause Fixed speed unit - compressor operation detected during off cycle PD & PS pressure sensors Discharge temperature sensors Fault codes

59 Code dE Cause Indoor address undefined Incorrect set-up of indoor PCB Defective indoor PCB Communication noise interference Fault codes

60 Code dF Cause Outdoor address undefined Defective interface PCB Communication noise interference Fault codes

61 Code E1 Cause DOL compressor high pressure switch #1 Pressure sensor > 363 psig Fault codes

62 Code F0 Cause DOL compressor high pressure switch #2 Pressure sensor > 363 psig Fault codes

63 Code E5 Cause Inverter compressor klixon Pressure sensor <363 psig Fault codes

64 Code E6 Cause DOL compressor klixon #1 or overload relay (manual reset) Pressure sensor < 363 psig Fault codes

65