Presentation is loading. Please wait.

Presentation is loading. Please wait.

ECE 498HZ: Power Distribution System Analysis

Similar presentations


Presentation on theme: "ECE 498HZ: Power Distribution System Analysis"— Presentation transcript:

1 ECE 498HZ: Power Distribution System Analysis
April 14, 2016 ECE 498HZ: Power Distribution System Analysis A Primer on Distribution System Protection ECE Main Slide Hao Zhu Dept. of Electrical & Computer Engineering University of Illinois, Urbana-Champaign

2 Announcements Homework 5 due next Tuesday, April 19
Tim Yardley from the Information Trust Institute will give a talk on the cyber-security aspects of energy delivery systems Final exam: 7:00-9:00 p.m., Tuesday, May 10

3 The goal of distribution protection
Main objectives Minimize the duration of a fault Minimize the number of customers affected by the fault Secondary objectives Eliminate safety hazards as fast as possible Limit service outages to the smallest possible segment of the system Protect the consumers’ apparatus Protect the system from unnecessary service interruptions Disconnect faulted lines, transformers, or other apparatus

4 Overcurrent protection devices
Fuse: heated/destroyed under overcurrent Circuit breaker: a switch to interrupt fault currents Circuit reclosers: trips and recloses to clear/isolate faults Line sectionalizers: similar to fuses but can coordinate with breakers/reclosers to “sectionalize” the feeder

5 Fuse cutouts < 34.5 kV Need a crew visit after one operation
Figures show a 7.2/14.4kV overhead installation Fuses connected to conductors [S&C Electric, Gonen’s book] Fuses protecting dist. transformers [WikiCommons]

6 Minimum-melting time-current characteristics (TCC)
Minimum time versus current required to melt the fuse link Another TCC is the total- clearing curve: plots the maximum time versus current

7 Power fuses > 34.5kV Higher ratings than cutouts
Typically for substation or subtransmission applications Power fuses protecting Substation transformers [S&C Electric, Gonen’s book]

8 Automatic circuit breakers (CBs)
Unlike fuses, a CB can be reset (either manually or automatically) to resume normal operation conditions Controlled by overcurrent protective relays (using current transformers) Advantages: heavy-duty, good interrupting capability and design margins Vacuum CBs, McGraw-Edison [Gonen’s book] Substation CBs [WikiCommons]

9 Overcurrent relay TCC

10 Automatic circuit reclosers
Recall the Tamer’s talk on IntelliRupter Unlike CBs, reclosers use instantaneous and time-delayed trip/reclose operations Lighter duty than CBs Below link compares between the two Advantages of reclosers: preventing transient faults; automatic power restoration ABB, 3-phase reclosers

11 Recloser TCC Reclosers have several curves related to the instantaneous and delayed operations

12 Automatic line sectionalizers
Working together with CBs or reclosers For transient faults, sectionalizers allow upstream CBs or reclosers to clear them If the faults persist, sectionalizers will trip to isolate the faulty circuit This function similar to fuse cutouts ABB, 1-phase sectionalizer

13 Type of faults ~75%–90% of the total number of faults are temporary (transient) in nature Conductors contact with each other or ground due to trees, birds,.. The key is to minimize the duration for this type of faults High-speed tripping, automatic reclosing mechanisms Permanent faults require repairs by a crew Burned-down conductors, removing tree limbs… We want to minimize the number of customers under these scenarios Isolating faulted areas using fuses and sectionalizers

14 An example scheme Transformers protected by fuses
Common practice to install fuses at the head of each lateral Can clear faults by the end of lateral Reclosers or CBs installed at the substation and along the primary feeder Each has a protection zone

15 Fuse-to-fuse coordination
Fuse rating is selected based on in-series devices Compare minimum-melting TCC of fuse A with the total- clearing TCC of fuse B Use 75% of the min-melting for a safety factor of 25%

16 Recloser-to-fuse coordination
For transient faults, only reclosers activated (fuses not affected) For permanent faults, fuses activated to isolate faulty areas Sectionalizers can achieve the coordination without TCC comparisons


Download ppt "ECE 498HZ: Power Distribution System Analysis"

Similar presentations


Ads by Google