Presentation is loading. Please wait.

Presentation is loading. Please wait.

Automatic Sprinkler Systems

Similar presentations


Presentation on theme: "Automatic Sprinkler Systems"— Presentation transcript:

1 Automatic Sprinkler Systems
FET 112 – Fire Protection Systems Objective #2

2 Automatic Sprinkler Systems

3 Automatic Sprinkler System
“For fire protection purposes, an integrated system of underground and overhead piping designed in accordance with fire protection engineering standards……usually activated by heat and discharges water over the fire area.”

4 History and Development of Automatic Sprinkler Systems
Early “sprinkler” systems involved the use of steel pipe with drilled holes or perforations provided along the length of pipe This type of system involved a manually operated water supply Corrosion, plugged holes, poor distribution of water onto the fire

5 History and Development of Automatic Sprinkler Systems
The concept for the use of a heat-actuated device dates back to approximately 1860, but it was not until 1875 that this concept was incorporated into a device Henry Parmelee is given credit for the first “automatic” sprinkler Brass Cap soldered over a perforated distributor designed to screw onto a nipple

6 NFPA 1995 report: U.S. Experience with Sprinklers…
“NFPA has no record of a fire killing more than two people in a completely sprinklered public assembly, educational, institutional, or residential building where the system was properly operating.”

7 Automatic Sprinkler System
Detects a fire Sounds an alarm Controls or extinguishes the fire Enhances life safety Reduces severity of loss Minimizes business interruption Most reliable and effective of all fire protection devices / systems

8 Automatic Sprinkler System Common Misconceptions
Heat from lighting a cigarette can activate the system When one “goes off”, they all “go off” Easily activated by accident Will cause severe water damage Leaks and drips are common problems Not cost effective

9 Automatic Sprinkler System Why Do They Fail?
Construction 6% Impairments 8% Other Causes 11% Obstructions 8% Partial Protection 8% Maintenance 35% Inadequate Water 10% Occupancy 14% National Fire Protection Association

10 Automatic Sprinkler System
INSPECTOR’S TEST CONNECTION CROSS MAIN BRANCH LINES BULK MAIN (RISER) WATER MOTOR ALARM FIRE DEPT. CONNECTION ALARM VALVE AUTOMATIC SPRINKLERS MAIN DRAIN CONNECTION O.S. & Y. GATE VALVE TO CONTROL WATER SUPPLY TO SYSTEM WATER SUPPLY Automatic Sprinkler System

11 Automatic Sprinkler System Design Considerations
Occupancy / storage / hazards Environment Building construction Size / height of building Special features Location Water supply

12 Occupancy Classifications
Light Hazard: Low Combustibility / low quantity of contents Ordinary Hazard Group 1: Combustibility is low, quantity is moderate, moderate rate of heat release Examples - parking garages / bakeries / canneries / laundries Ordinary Hazard Group 2: Combustibility / quantity is moderate to high, heat release moderate to high Examples - dry cleaners / printing / wholesale -retail sales

13 Occupancy Classifications
Extra Hazard Group 1: Combustibility and quantity very high, probability of rapidly developing fires with high heat release, little or no flammable / combustible liquids Examples - feed mills / paper - wood - rubber products manufacturer Extra Hazard Group 2: Same as group 1 with moderate to substantial amounts of flammable / combustible liquids or extensive shielding of combustibles Examples - woodworking with flammable finishing, flammable liquids spraying, flow coating, mobile or modular housing manufacturers

14 Automatic Sprinkler System Types of Systems
Wet pipe system Dry pipe system Deluge system Preaction system Antifreeze system (loop)

15 Wet Pipe System System entirely filled with water
Heat opens system and water begins to flow immediately Flowing water causes an alarm to sound Water controls or extinguishes the fire No action required to restore system except replacing activated sprinklers Must be non-freezing locations

16 Wet Pipe System RISER SYSTEMSIDE SUPPLY PRESSURE SYSTEM PRESSURE
CLAPPER (CLOSED) PILOT VALVE TO ALARM MAIN DRAIN O.S. & Y. VALVE SUPPLY SIDE

17 Wet Pipe System

18 Dry Pipe System Used in unheated or artificially cooled areas (40º F or less) System filled with air or nitrogen under pressure Sprinklers opening releases air or nitrogen causing dry pipe valve to trip (open) System fills with water and flows out opened sprinklers Following activation system must be drained and reset

19 Dry Pipe Sprinkler System (Set)
AIR PRESSURE FILLER CUP FOR WET SEAT SYSTEM MAIN DRAIN O.S. & Y. VALVE INTERMEDIATE CHAMBER WATER PRESSURE GUAGE TO ALARM CLOSED CLAPPER AIR

20 Dry Pipe Sprinkler System (Tripped)
AIR PRESSURE GUAGE WATER PRESSURE GUAGE FILLER CUP FOR WET SEAT SYSTEM TO ALARM OPEN CLAPPER 2” DRAIN O.S. & Y. VALVE

21 Dry Pipe Valve Set Tripped

22 Dry Pipe System

23 Dry Pipe System Quick Opening Devices
Required if system capacity exceeds 500 gallons or time for water flow to test connection exceeds 60 seconds. Accelerator: Sprinkler opening causes air pressure to drop. Accelerator activates, sending air pressure under clapper causing dry pipe valve to trip Exhauster: Sprinkler opening causes exhauster to open, allowing air to escape to atmosphere. Dry pipe valve trips quicker

24 Quick Opening Device Accelerator RESTRICTED ORIFICE AIR AIR
FLEXIBLE DIAPHRAGM RESTRICTED ORIFICE AIR AIR ACCELERATOR VALVE CLAPPER TO ALARM AIR SEAT WATER SEAT WATER BALL DRIP INTERMEDIATE CHAMBER WATER Accelerator

25 Quick Opening Device (Exhauster)
RISER SYSTEM RESTRICTED ORIFICE 40 40 AIR TO ATMOSPHERE

26 Deluge System Special use system All sprinklers are open
Valve to system is opened by a heat / smoke detection system Water flows from all sprinklers upon activation Requires draining / resetting following activation Valve must be in heated location

27 Deluge System ATMOSPHERIC PRESSURE OPEN SPRINKLER TO ALARM AUTOMATIC
OR MANUAL ACTIVATING DEVICE SUPPLY PRESSURE ATMOSPHERIC PRESSURE OPEN SPRINKLER TO ALARM MAIN DRAIN

28 Deluge System

29 Preaction System Developed for properties highly susceptible to water damage Requires 2 activations for water discharge Piping is filled with air/ sprinklers closed A fire detection system opens valve flooding system with water and sounding an alarm Water does not flow until heat opens a sprinkler May allow time for manual fire suppression System requires draining / resetting

30 Preaction System ATMOSPHERIC PRESSURE CLOSED SPRINKLER TO ALARM
AUTOMATIC OR MANUAL ACTIVATING DEVICE SUPPLY PRESSURE ATMOSPHERIC PRESSURE CLOSED SPRINKLER TO ALARM MAIN DRAIN

31 Preaction System

32 Review of the Three Types of Preaction Systems

33 Non-Interlocked Preaction systems
Designed so the Deluge Valve will open when EITHER the detection system operates OR a loss of pneumatic (air) pressure in the sprinkler system occurs When the Deluge Valve opens, water will flow into the sprinkler piping and out of any open sprinklers and any other opening on the system. In the event of non-operation of the release system, the system will operate as a dry system.

34 Single-Interlocked Preaction systems (most common)
Activation of a fire detection system will fill the system piping with water Used where: It is desirable to have water available at the sprinkler when the sprinkler operates The sprinkler piping is subject to: Damage Freezing conditions Accidental water discharge must be minimized

35

36 Double-Interlocked Preaction systems
Activation of BOTH the detection system and operation of an automatic sprinkler are necessary to cause discharge of water in the hazard area Activation of one only will not cause the valve to open Detection only – alarm condition Sprinkler activation – loss of air pressure

37

38 Antifreeze System (Loop)
Used in small unheated area such as a loading dock Connected to a wet pipe system Capacity of antifreeze system should not exceed 40 gallons Must meet local / state health regulations Solution must meet proper type / mixture

39 Antifreeze System (Loop) – (cont.)
Heat opens the sprinklers releasing antifreeze followed by water from wet pipe system System requires restoration following the activation Annual testing of solution required

40 Antifreeze System (Loop)
SPRINKLER FILLING CUP WET PIPE SYSTEM WATER VALVE HEATED AREA UNHEATED AREA ANTI- FREEZE SOLUTION CHECK VALVE DRAIN VALVE

41 Residential Sprinkler Systems

42 History – Residential Systems
Automatic Sprinkler Systems have been successfully used to protect various occupancies, including commercial and industrial buildings for over 100 years However, a residence has historically been the place where most people die In 1973, a report of the National Commission on Fire Prevention and Control titled, “America Burning” brought to light this fact 80% of fire deaths were in the home

43 Residential Installation
Although increasing, it is estimated that less than 3 percent of the one- and two-family homes in the United States have them installed

44 Residential Sprinkler Systems
Handout of NFPA 13R – Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height NFPA 13D – Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes

45 Residential Sprinkler Systems (cont.)
NFPA 13R addresses cost-effective sprinkler protection with LIFE SAFETY as its PRIMARY GOAL and PROPERTY PROTECTION as a SECONDARY GOAL NFPA 13R provides a high, but not an absolute, level of life safety and a somewhat lesser degree of property protection

46 Residential Sprinkler Systems (cont.)
A sprinkler system designed and installed with NFPA 13R is expected to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated Criteria was developed by Underwriters Laboratory (UL) and Factory Mutual Research Corporation (FMRC) during actual fire tests

47 Residential Sprinkler Systems (cont.)
The main differences between a commercial sprinkler system (NFPA 13) and a residential sprinkler system is the sprinkler heads and the incoming service arrangement Response Time vs. Conductivity of the head

48

49 Residential Sprinkler Heads
Classified as Fast Response Sprinkler Heads Also, the spray from the residential sprinkler heads must wet the walls of the fire test chamber within their area of coverage to at least 18 inches from the ceiling

50

51

52 Water Spray Systems

53 Water Spray Systems The term water spray refers to water that is discharged from specially designed nozzles or devices to produce a predetermined Pattern Particle size Velocity Density The use of these designations cannot be taken as an indication of any specific discharge pattern or spray characteristics of the nozzle

54 Water Spray Systems (cont.)
Water Spray Systems are also called Water Fog Systems These systems are typically designed to protect a specific piece of equipment with surface coverage In addition, water spray systems are usually of the deluge type of system

55

56 Water Spray Nozzles Spray nozzles are not equipped with fusible operating elements Discharge from water spray nozzles differ from standard sprinklers in the following ways: Pattern from spray nozzles may be elliptical Water spray is forcefully directed onto the object or surface being protected The nozzle spray must overcome wind and draft conditions The required design density

57

58

59 Advantages of Wet Systems
System simplicity Relative low installation and maintenance expense Ease of modification Short down time following a fire

60 Disadvantages of Wet Systems
This type of system is not suited for subfreezing environments Not practical where piping is potentially subject to severe impact damage

61 Advantages of Dry Systems
Their ability to provide automatic sprinkler protection in spaces where freezing is possible Example locations may include: unheated warehouses and attics, outside exposed loading docks, and within commercial freezers

62 Disadvantages of Dry Systems
Increased complexity Higher installation and maintenance costs Lower design flexibility Increased response time Increased corrosion potential With the exception of unheated buildings, dry pipe systems are generally not recommended

63

64 Advantages of Deluge Systems
Faster response to fire occurrence Usually more effective in controlling or extinguishing a fire condition Single action is required for water release Used where large amounts of water is of minimal concern

65 Disadvantages of Deluge Systems
Requires fire detectors for the actuation of the system Potential water collection in the area of system operation

66 Advantages of Preaction Systems
Dual action is required for water release Used in water sensitive environments Example locations may include: archival vaults, fine art and storage rooms, rare book libraries and computer centers

67 Disadvantages of Preaction Systems
Higher installation and maintenance costs Modification difficulties Potential decreased reliability

68 Standpipes / Hose Supply

69 System Components Listed - FM / UL / ULC / other recognized testing organizations Properly designed Properly installed Adequately supported / braced Protected from cold / vandalism / other damage Regularly tested Maintained

70 Automatic Sprinkler

71 Automatic Sprinklers Sprinkler Storage Cabinet

72 Valves Identification Signs

73 Fire Department Connection
RISER MAIN DRAIN DRY PIPE VALVE FIRE DEPT. HOSE CONNECTION CHECK VALVE CONTROL VALVE AUTOMATIC BALL DRIP

74 Fire Department Connection
RISER MAIN DRAIN FIRE DEPT. HOSE CONNECTION ALARM CHECK VALVE CHECK VALVE CONTROL VALVE AUTOMATIC BALL DRIP

75 Fire Department Connection (FDC)

76 Problem?

77 Supervision Waterflow Water level / temperature (tank) Water pressure
Air pressure (dry pipe system / pressure tank Valve tamper Fire pump status Valve room temperature Other

78 Water Overflow (Standby)
MOTOR GONG PRESSURE SWITCH SUPPLY PRESSURE SYSTEM PRESSURE CLAPPER CLOSED PILOT VALVE LOCAL ELECTRIC ALARM RETARD CHAMBER

79 Water Overflow, Operating
MOTOR GONG PRESSURE SWITCH SUPPLY PRESSURE SYSTEM PRESSURE CLAPPER OPEN LOCAL ELECTRIC ALARM RETARD CHAMBER

80 Water Motor Gong

81 Waterflow

82 Valve Tamper

83 Big Problems!

84 Questions one must ask? Sprinkler System
Is the water supply adequate? Was the system properly installed, flushed and tested? Is the system and all components protected from cold, vandalism, or other damage? Does the owner thoroughly understand the system and know how it works? Is the system being properly tested and maintained?

85 Questions one must ask? Components
Are the sprinklers of the proper type, temperature classification, and obstructed? Are all sprinkler control valves accessible / open / locked / supervised? Is the sprinkler piping being used to support shelving / racks / storage / etc.? Is the fire department connection visible / accessible / in working order? Are the alarms tested / working / monitored?

86 Questions one must ask? Occupancy
Is the sprinkler system designed for the present occupancy? Is the entire occupancy sprinklered? Is there unanticipated high piled stack / rack storage / aerosols / flammable liquids / other hazards? Is the building protected from exposure fires? Are the vertical / horizontal / openings protected? Are there unsprinklered combustible spaces?

87 Final Thoughts Simply installing a sprinkler system will not guarantee adequate fire protection. The system must be properly designed, installed, tested, and maintained to be effective.

88 QUESTIONS???

89


Download ppt "Automatic Sprinkler Systems"

Similar presentations


Ads by Google