Objectives Differentiate CAV, VAV, dual-duct systems

Similar presentations


Presentation on theme: "Objectives Differentiate CAV, VAV, dual-duct systems"— Presentation transcript:

1 Objectives Differentiate CAV, VAV, dual-duct systems
Finish psychrometric process (Chapter 8) Calculate heat transfer for direct air – liquid water contact devices Heat rejection Cooling towers Sections ,10.5

2 Humidification hw Specific enthalpy of water added to system
hg Specific enthalpy of saturated water vapor

3 Evaporative Cooling (aka air washing)

4 Condition Line for a Space

5 Single-Zone Systems Zone – any space with a thermostat

6 Air conditioning

7 Recirculation

8 Reheat

9 Evaporative Cooler

10 Air-to-air heat exchanger

11

12

13

14

15 Comment Look at material on CAV w/ reheat, VAV, and dual-duct systems in text Will form basis of first take home exam problem Skipping Chapter 9

16 Why do we have Direct Contact Processes?
Humidification (and dehumidification – see 10.4) Heat rejection Water has better heat transfer properties than air Non dimensional parameter Lewis number, Le = α/D = hc/hD/cP Ratio of heat transfer to mass transfer Assume Le = 1 for evaporative coolers hc convection heat transfer coefficient hD mass transfer coefficient cp specific heat α thermal diffusivity D mass diffusivity

17 Air Washer Sprays liquid water into air stream
Typically, air leaves system at lower temperature and higher humidity than it enters

18 Schematic

19 Air Washers/Evaporative Coolers
Heat and mass transfer is mutually compensating Can evaluate based on temperature drop, humidification, or comparison to other energy exchangers

20 Cooling Tower Similar to an evaporative cooler, but the purpose is often to cool water Widely used for heat rejection in HVAC systems Also used to reject industrial process heat

21

22

23

24 Solution Requires f-factor Can get from Stevens diagram (page 272)
Can also be used to determine Minimum water temperature Volume of tower required Can be evaluated as a heat exchanger by conducting NTU analysis

25 Real World Concerns We need to know mass transfer coefficients
They are not typically known for a specific direct-contact device Vary widely depending on packing material, tower design, mass flow rates of water and air, etc. In reality, experiments are typically done for a particular application Some correlations are in Section 10.5 in your book Use with caution