Objective Provide an analysis of the existing Waltz-Mill system. Provide an analysis of the existing Waltz-Mill system. Determine the affect on the system.

Similar presentations


Presentation on theme: "Objective Provide an analysis of the existing Waltz-Mill system. Provide an analysis of the existing Waltz-Mill system. Determine the affect on the system."— Presentation transcript:

1 Objective Provide an analysis of the existing Waltz-Mill system. Provide an analysis of the existing Waltz-Mill system. Determine the affect on the system of adding an additional motor load. Determine the affect on the system of adding an additional motor load. Determine the necessary changes to safely add the new load and increase the power factor on T6 and T7. Determine the necessary changes to safely add the new load and increase the power factor on T6 and T7.

2 Existing System Analysis With SKM Power Tools Software A Load Flow analysis was performed with the following data. A Load Flow analysis was performed with the following data. BKR5306kVA.8 T10568kVA.8 BKR15 450.75k VA.8 T11220kVA.8 BKR10 225.81k VA.8 BKR13 375.89K VA.8 LocationLoadPFT11300kVA.8 T21275kVA.8 BKR2 416.71k Va.8 BKR3 No load

3 Existing System Analysis With SKM Power Tools Software The following values will be found under the current conditions The following values will be found under the current conditions Percent loading for each feeder circuitPercent loading for each feeder circuit Percent loading for each transformerPercent loading for each transformer Nominal voltage and percent voltage drop at each switchgearNominal voltage and percent voltage drop at each switchgear Optimal transformer tapsOptimal transformer taps

4 System Analysis with new load System Analysis with new load 500hp motor load added to secondary bus T7. 500hp motor load added to secondary bus T7. Determine the size of the cable and breaker. Determine the size of the cable and breaker. Increase power factor on secondary bus of T6 and T7 to.97 by adding a capacitor bank. Increase power factor on secondary bus of T6 and T7 to.97 by adding a capacitor bank.

5 Results and Recommendations Load flow analysis of existing system before tap optimization. Load flow analysis of existing system before tap optimization. Includes percent loading for all transformers and feeders. Includes percent loading for all transformers and feeders.

6 Results and Recommendations Tap settings were optimized to minimize loss in the system. Tap settings were optimized to minimize loss in the system. Load Flow results with optimized tap settings

7 Results and Recommendations The full load ampacity for the motor was found with the equation for FL A. The full load ampacity for the motor was found with the equation for FL A. The breaker was sized at 125% FL A. The breaker was sized at 125% FL A. The size of the capacitor bank needed to improve the PF to.97 was found with the equation for Q B. The size of the capacitor bank needed to improve the PF to.97 was found with the equation for Q B. Added motor and capacitor bank to T7

8 Results and Recommendations Added capacitor bank to correct T6 power factor to 0.97

9 Results and Recommendations The motor drew up to 683.92A The motor drew up to 683.92A 3-1/C, 500MCM, nonmagnetic cable was chosen (ampacity of 810A) 3-1/C, 500MCM, nonmagnetic cable was chosen (ampacity of 810A) A GE SK, Spectra motor circuit protector with trip settings between 600- 1200A was selected. A GE SK, Spectra motor circuit protector with trip settings between 600- 1200A was selected. This trip current should be set to 800A. This trip current should be set to 800A. Load flow analysis of system with motor and capacitor banks added