Presentation is loading. Please wait.

Presentation is loading. Please wait.

Resident Physics Lectures

Similar presentations


Presentation on theme: "Resident Physics Lectures"— Presentation transcript:

1 Resident Physics Lectures
Christensen, Chapter 2B Tube Ratings George David Associate Professor Department of Radiology Medical College of Georgia

2 Heat Units A unit of energy Single Phase Definition
Kilovoltage X tube current X exposure time kVp X mA X sec Three Phase (constant potential/high frequency) Definition 1.35 X Kilovoltage X tube current X exposure time 1.35 X kVp X mA X sec

3 ? Heat Units 70 kVp 200 mA 0.25 second
Single Phase Exposure Heat Units 70 kVp 200 mA 0.25 second 70 X 200 X 0.25 = 3500 heat units ?

4 ? Heat Units 60 kVp 100 mA 0.1 second
Three Phase Exposure Heat Units 60 kVp 100 mA 0.1 second 60 X 100 X 0.1 X 1.35 = 810 heat units ?

5 Heat is the Enemy X-Ray Tube Heat

6 Tube Rating Chart Indicates load limit tube can safely accept
Based upon Tube construction High Voltage Waveform

7 Tube, Target, & Ratings surface area bombarded by electrons
focal spot size (actual) target angle anode diameter Melting point Heat transfer Anode rotation speed

8 Tube Rating Charts single exposure
multiple rapid exposure (angiographic) capability

9 Single Exposure Rating Charts
Tube specific Incorporated in virtually all generators prevents illegal single exposures Better ratings (more heat allowed) for Large focal spot High speed anode rotation

10 Typical Single-Exposure Tube Rating Chart
shows maximum exposure time for single exposure at given kV & mA

11 Example What is the maximum exposure time at 90 kVp & 300 mA?

12 ? Example What is the maximum exposure time at 120 kVp & 400 mA?
Can’t do 120 kVp at 400 mA for any exposure time. ?

13 Single Exposure Rating Charts
Actually 8 charts combining: generator single phase (1F) three phase (3F) focal spot small large anode speed standard (3400 rpm) high (9600 rpm) 1F SFS 3400 RPM 3F SFS 3400 RPM 1F LFS 3400 RPM 3F LFS 3400 RPM 1F SFS 9600 RPM 3F SFS 9600 RPM 1F LFS 9600 RPM 3F LFS 9600 RPM

14 On-Board Tube Rating Charts
Checks to see if legal exposure at low-speed rotation. Automatically switches to high speed anode rotation as needed Locks out illegal exposures Safe at 3400 rpm? Safe at 9600 rpm? No No No Exposure Allowed Yes Yes Allow 3400 rpm Exposure Allow 9600 rpm Exposure

15 Kilowatt Rating Ability of x-ray tube to make single exposure of reasonable duration (usually .1 sec.) Found on tube rating chart standard assumptions Use 0.1 sec. exposure time Three phase chart high speed rotor rotation

16 Kilowatt Rating (cont.)
Units 1 watt = 1 volt X 1 amp 1 watt = 1 kilovolt X 1 mA 1 kilowatt (kW) = 1 kilovolt X 1 mA / 1000 kW rating for a standard 0.1 sec exposure kW rating = kVp X mA / 1000 use maximum mA at given .1 sec

17 Kilowatt Rating (cont.)
100 kVp exposure usually used For a 100 kVp, .1 sec exposure kW rating = mA / 10 Use maximum mA at 100 kVp, .1 sec. Each focal spot has its own kW rating X Interpolate! ~32 kW

18 Anode Thermal Characteristics Chart
2 charts in one cooling curve in absence of heating anode heating for continuous heat input (fluoroscopy)

19 Continuous Heating - Fluoroscopy
Fluoro almost always single phase Find appropriate curve HU/sec = kVp X mA Follow from current heat to right for fluoro time

20 Continuous Heating - Fluoroscopy
Technique 100 kVp 6 mA 600 HU/sec Start with 50,000 HU Fluoro for 3 minutes x ~105,000 HU x 3 minutes

21 Cooling Start on cooling curve with current heat units
110,000 for this example Cool for 2 minutes x x ~40,000 HU x 2 minutes

22 Angiographic Rating Chart
Provides maximum heat units per exposure for given # of exposures per second total exposures Total # of Exposures 2 5 10 20 30 1 37,000 24,000 16,000 10,000 7400 25,000 17,000 12,200 8,000 6,200 3 19,000 13,600 7,000 5,300 4 15,500 11,400 8,600 6,000 4,500 Exposures per second Maximum Load in Peak kV X mA X sec.

23 Example How many total exposures can be done at 90 kVp 100 mAs
3 frames / sec. 90 X 100 = 9000 (Maximum Load) Total # of Exposures 2 5 10 20 30 1 37,000 24,000 16,000 10,000 7400 25,000 17,000 12,200 8,000 6,200 3 19,000 13,600 7,000 5,300 4 15,500 11,400 8,600 6,000 4,500 13 Exposures per second Maximum Load in Peak kV X mA X sec.

24 Tube Rating Considerations
ability of tube to withstand multiple exposures during several hours of heavy use depends upon anode storage / cooling curves housing storage / cooling curves housing cooling can be improved with fans oil / water circulators

25 Tube Damage Warning

26 Anode Damage heat capacity exceeded
melted spots on anode thermal shock (high mA on cold anode) can cause cracks in anode (tube death)

27 Protecting the Anode Tube warm-up
Eliminates thermal shock from high mA exposures on cold anode Warm-up needed whenever tube cold once in the morning not sufficient if tube not used for several hours

28 High Voltage Arcs electrons move from filament to tube housing instead of to anode can be caused by filament evaporation deposition of filament on glass envelope as result of high filament currents long filament boost time reduce by not holding first trigger longer than needed very short exposure with instantaneously very high mA Generator often drops off line + arcing

29 Tube Insert Damage Bearing Damage Filament break
prevents proper rotation of anode anode can run too slow anode can stop results in thermal damage to anode (melted spots) Filament break renders one focal spot completely inoperative

30 Reducing Tube Wear: Lower mA
80 kVp 500 mA, 0.1 sec 80 kVp 100 mA, 0.5 sec or Both exposure are 50 mAs Same radiation to image receptor Same dose to patient Don’t smoke that tube

31 Reducing Tube Wear: Lower mA
80 kVp 500 mA, 0.1 sec 80 kVp 100 mA, 0.5 sec or Low mA reduces tube wear filament temperatures lower reduces filament evaporation Don’t smoke that tube

32 Reducing Tube Wear: Lower mA
80 kVp 500 mA, 0.1 sec 80 kVp 100 mA, 0.5 sec or use lowest mA (and largest focal spot) consistent with patient motion considerations Large focal spot allows higher mA to be used Don’t smoke that tube

33 Reducing Tube Wear: Raise kVp
100 mAs 90 kVp 40 mAs or High kVp exposures require less heat units for same film density higher kVp more penetrating High kVp also reduces patient exposure More penetrating beam BUT higher kVp reduces contrast Use highest kVp consistent with required contrast Don’t smoke that tube

34 Reducing Tube Wear Reduce use of high speed anode rotation
use longer times instead of higher kV and/or mA High speed rotation greatly increases bearing wear generators automatically select high speed for high combinations of kV & mA BUT longer exposure times increase exposure time & patient motion use lowest mA consistent with patient motion considerations Don’t smoke that tube

35 Reducing Tube Wear Reduce first trigger holding time
Reduces bearing wear Reduces tube rotation time Reduces filament evaporation filament evaporation can lead to tube arcing Holding first trigger sometimes necessary synchronizing breathing for children Don’t smoke that tube

36 Oil Leaks May be accompanied by air bubble in housing
Eventually causes high voltage arcing Requires immediate service attention


Download ppt "Resident Physics Lectures"

Similar presentations


Ads by Google