9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate.

Similar presentations


Presentation on theme: "9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate."— Presentation transcript:

1 9/19/2015 1 Variable Speed Lowdown

2 TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

3 TYPICAL US SYSTEM  Series loop, fin-tube baseboard  CI bb/radiators/convectors  Radiant floor heating  Mutliple zones, circs or ZV’s  Approx 2,100 – 2,500 hrs of operation

4 WHY USE A VARIABLE SPEED CIRCULATOR?  Good question…  Best applications…  Zone valve or RFH  Zone pump?  Electrical savings?

5 5 007’s @ 80W each = 400 Watts 400 Watts ÷ 1000 = 0.4 kW ELECTRICAL SAVINGS????

6 9/19/2015 TACO – EMERSON SWAN MEETING 6

7 5 007’s @ 80W each = 400 Watts 400 Watts ÷ 1000 = 0.4 kW 0.4 kW × 2,500 “on” hrs = 1,000 kWh 1,000 kWh × 15¢/kWh = $150.00/yr ELECTRICAL SAVINGS????

8 1 007 (80W) + 5 Zone Sentry zone valve (1.44W each)= 87.2 Watts 87.2 Watts ÷ 1000 = 0.0872 kW 0.0872 kW × 2,500 “on” hrs = 218 kWh 218 kWh × 15¢/kWh = $32.25/yr WITH ZONE VALVES…

9 1 Pump (20W) + 5 Zone Sentries (1.44W each)= 27.2 Watts 27.2 Watts ÷ 1000 = 0.0272 kW 0.0272 kW × 2,500 “on” hrs = 68 kWh 68 kWh × 15¢/kWh = $10.20/yr WITH SUPER DUPER ECM…

10 5 ZONE SYSTEM  70,000 BTUH  7 GPM @ 5’ head  Where does system really work?

11 GPM = BTUH  T = BTUH  T = 70,000 < 14.5 0  T × 500 GPM  500 9.5  500 NUMBERS DON’T LIE…

12 1 ZONE CALLING  10,000 BTUH  1 GPM @ 5’ head  Where does it really work?

13 GPM = BTUH  T = BTUH  T = 10,000 10 0  T × 500 GPM  500 2 NUMBERS STILL DON’T LIE…

14 The Result? And when it’s 35 0 out?

15 SO WHAT ABOUT THE VR 1816? 9/19/2015 15

16 9/19/2015 16

17 9/19/2015 17

18 9/19/2015 18

19

20 SO, PROGRAMMING THE VR 1816???? 9/19/2015 20

21 KEEP IT SIMPLE…  CP Settings – zone pump:  85’ total length = CP I (5’ hd)  165’ total length = CP II (10’ hd)  250’ total length = CP III (15’ hd)  Based on ML × 1.5 ×.04 9/19/2015 TACO – EMERSON SWAN MEETING 21

22 9/19/2015 22

23 STEPLESS/INFINITE ADJUST  Min = 003  Low = 006  Med = 007/0015 Low  High = 008/0015 Med  Max = 0015 Hi  Or for guys who actually calculate flow & head… 9/19/2015 TACO – EMERSON SWAN MEETING 23