Presentation is loading. Please wait.

Presentation is loading. Please wait.

Sequence of Events Recording for Kardia Power Station Greece Ian Loudon Omniflex International Marketing and Sales.

Similar presentations


Presentation on theme: "Sequence of Events Recording for Kardia Power Station Greece Ian Loudon Omniflex International Marketing and Sales."— Presentation transcript:

1 Sequence of Events Recording for Kardia Power Station Greece Ian Loudon Omniflex International Marketing and Sales

2 Omniflex ► Omniflex South African Manufacturer of Industrial Electronic Products ► Founded 1965 as Conlog became Omniflex 1996 ► 50% of Turnover exported ► Sales Office JHB, UK, Australia Head Office Durban ► Wonderware and Sequence of Events recording since 1988 ESKOM, Sasol, Natref

3 Introduction This Project improves an ageing Coal Fired Power Station Root Cause Analysis by 90% Kardia Power Station Greece

4 Agenda IntroductionIntroduction Project Solution BenefitsBenefits ConsiderationsConsiderations SummarySummary

5 Kardia Power Station Greece Up to 50% of Greece’s Electricity from Coal (Lignite) 6 Lignite Fired Stations Agios Dimitrios Amyntaio Florina Kardia Megalopolis Ptolemais How much coal is required to run a 100-watt light bulb 24 hours a day for a year?

6 Background to the Project Location : Greece Operator : Public Power Corp Configuration : 4 X 300 MW Operation : Since 1975 …… Fuel : Lignite Boiler : Stein, Ganz-Rock T/G supplier : Alstom, LMZ, Teploenergo EPC: Zarubezhenergoproekt T/G Turbine Generator EPC Engineering Procurement Construction

7 Business Objective ► Plant Optimization ► Reduce Downtime ► Effective Alarm Localization ► Nuisance Alarm Identification ► High Availability ► Cost effective Solution

8 Operational Objectives ► Root Cause Analysis ► Alarm History ► Local Alarm Indication ► Fast and Reliable Event Capture ► Redundancy of I/O Processors

9 Agenda IntroductionIntroduction Project Solution BenefitsBenefits ConsiderationsConsiderations SummarySummary

10 Selection of Solution ► Local SI for Local Support ► Wonderware SCADA selected for ► Ease of configuration ► Minimal effort to integrate Date and Time Stamp at source event streams through OPC server

11 Sequence of Events Recording System

12 System Implementation ► 960 Relay Contact Inputs COS monitoring ► 960 Alarm Statuses Annunciated ► Input discrimination to 200μseconds ► Minimum Pulse Width 500μseconds ► Time Stamping Accuracy 200μseconds

13 System Diagnostics

14 Historical Alarms

15 Alarm Summary

16 Time Synchronization ► GPS Station Time ► OPC server Service

17 Controller Redundancy ► Dual Controller ► Includes Queue Services

18 Topology Field Inputs Marshalling Panel Ethernet Conet CAN SCADA OP C Modbus Primary Secondary

19 Disadvantages of Poll Response Disadvantages of a poll/response network · Poll/Response uses %100 of available bandwidth. · The data "Transport" is the "Application". You can't break them apart. · One protocol for all field equipment limits deployment of new technology & impedes migration to new topologies. · It is not a "managed" network. · One-to-One data relationship between the Host and field equipment Master Slave

20 Producer Consumer Subscription Producer eg SOE System Middleware Message Broker Eg Queue Service Consumer Application 1 Consumer Application 2 Consumer Application 3 Subscribe Publish Advantages: Network Traffic Minimized Efficient use of Network Bandwidth Multiple consumers

21 System Implementation ► In House Engineering and Testing and Configuration, SCADA, OPC, Maxiflex 1 week ► Local Panel Alarm Annunciators via Modbus RS485 ► Wonderware SCADA Final Configuration On Site ► Copy Paste for Second System 2 Days In House Engineering and Testing

22 Agenda IntroductionIntroduction Project Solution BenefitsBenefits ConsiderationsConsiderations SummarySummary

23 Benefits / Goals Achieved ► Plant Optimization  ► Reduce Downtime  ► Effective Alarm Localization  ► Nuisance Alarm Identification  ► High Availability 

24 Benefits / Goals Achieved ► Root Cause Analysis  ► Alarm History  ► Local Alarm Indication  ► Fast and Reliable Event Capture  ► Redundancy of I/O Processors 

25 Realised Benefits ► 90% improvement in Root cause analysis ► 25% improvement in Generating Availability ► 40 to 50% time saving in Maintenance ► Huge Saving on Hard Wired Annunciation ► Project Implementation Short ► End User Empowerment on system usage, migration and on going improvement ► Rapid Deployment of next Generator system

26 Agenda IntroductionIntroduction Project Solution BenefitsBenefits ConsiderationsConsiderations SummarySummary

27 Lessons Learned ► Learn to Speak Greek ! Real Greek ► Partnering with local Wonderware SI’s essential ► Preconfigured Wonderware for Front end Hardware from Factory simplifies field work

28 Agenda IntroductionIntroduction Project Solution BenefitsBenefits ConsiderationsConsiderations SummarySummary

29 Conclusions ► Wonderware was a good choice for seamless integration of Date and Time stamped events into an HMI for management of Alarm and Events. ► Wonderware Presence worldwide presented this opportunity for us from a South African and UK Base.

30 Project summary ► “The system works well and enables incidents to be tracked very efficiently”. Ilias Kalaitzis,Project Engineer, Control Systems

31 Project Summary ► Project Delivered in 2008 on time during Shut Down of Generator Unit Period 16 Weeks Entirety ► Second Unit simple Copy and Paste for SOE Configuration. Completed Dec 2008 ► We are expecting orders for the balance of 2 Generator Sets

32 Questions ? Solutions by Design


Download ppt "Sequence of Events Recording for Kardia Power Station Greece Ian Loudon Omniflex International Marketing and Sales."

Similar presentations


Ads by Google