Indoor Environmental Quality: Investigating the Problem

Similar presentations


Presentation on theme: "Indoor Environmental Quality: Investigating the Problem"— Presentation transcript:

1 Indoor Environmental Quality: Investigating the Problem
John W. Martyny, Ph.D., CIH

2

3 Causes of IAQ problems. Outdoor pollution Indoor pollution
Building material off-gassing Inadequate ventilation

4

5 How are IAQ Investigations Conducted?

6 IAQ Investigations Building Characterization Symptom Survey
Ventilation System Evaluation Source Identification Sampling Remediation

7 Building Characterization
Type and age of building Construction materials Primary uses Cleaning practices

8 Type and Age of Building
Previous ventilation systems. What remodeling has taken place? What were the prior uses? Is asbestos a concern? Is mold a concern?

9 Construction Materials
Wood Construction vrs Metal Fire proofing material Crawl spaces Carpeting and wall coverings

10 Primary Uses Is a manufacturing area included?
What is the occupant density? Computer usage. Has the primary usage changed?

11 Cleaning Practices Who cleans the building?
When is the building cleaned? Cleaning product storage. Cleaning product MSDS information?

12 Symptom Surveys Questionnaires vrs. Interviews The survey must:
Cover a majority of the staff. Be pre-tested. Eliminate bias. Not suggest answers. Not be a group effort.

13 Questionnaire Topics Demographic Questions Comfort Questions
Medication Questions Diagnosed Illness Questions Symptom Questions Air Quality Control Questions Job Satisfaction Questions

14 Ventilation System Evaluation
Visual inspection of System. Carbon dioxide (tracer gas) measurements. Look for the following: Water infiltration Maintenance history General condition Use of local exhaust Placement of exhausts and intakes

15

16

17

18

19

20

21

22 Ventilation System Characterization
System Type Constant Volume Variable Air Volume Unit Ventilators Zones Single Zone Multi-Zone Reheat or No Reheat Ducts - Lined or Unlined

23

24

25

26

27

28

29

30 Unit Ventilators Not actually an air handling system.
Mount on outside wall. Provide some filtration, conditioning, and movement.

31

32 Constant Volume Systems
Provides a constant supply airflow rate to zones with similar thermal loads. Air temperature is controlled at the air handler or with reheat coils. Outside air is determined by: Outside air temp. Damper settings Temperature demand

33 Variable Air Volume Systems
Provides a constant temperature air to the duct system. Air from the duct system is supplied to the zone to manage thermal load by the use of VAV boxes. Outside air is determined by: Thermal demand of zone. Outside air temperature. VAV box and damper minimum settings.

34 Results of CO2 and ACH Sampling
CV VAV UV GM of CO 2 715 ppm 666 573 CO Range ( ppm) 318 – 1,763 295 – 1,450 % of Time > 1000 0% 11% 9% Mean ACH 4.6 2.8 2.7 Range ACH 1.9 – 7.5 0.8 – 4.6 0.4 – 4.6

35 Particle Ratio Results
CV VAV UV GM Ratio < 1 m 0.68 0.57 0.38 GM Ratio 1 – 3 1.39 3.08 5.47 GM Ratio > 3 3.20 4.80 14.76

36 Complaints by System Type
Type of Complaint More than Expected Less than Too cold VAV CV Individuals w/ complaints Eye Symptoms Headache Symptoms UV Nasal Symptoms VAV, CV Throat Symptoms Dustiness Complaints

37 Source Identification
Look for the following: Manufacturing areas Print shops Construction Cleaning agents

38 Sampling Initial Site Assessment Secondary Sampling

39 Initial Site Assessment
HVAC system measurements: Carbon dioxide, air flow. Ambient air measurements Carbon monoxide, carbon dioxide, temperature, relative humidity.

40

41

42 Secondary Sampling Should only be conducted when: HVAC measurements
Specific information is to be collected Knowledgeable personnel are present HVAC measurements Tracer gas, duct velocities Ambient Air Chemicals - VOC’s, aldehydes, MVOC’s, odors, particulates, etc. Bioaerosol Sampling Medical monitoring

43 Why conduct tracer gas testing?
To determine air exchange rate for a building or area of a building. To determine fresh air distribution for a building or area of a building. To determine ventilation infiltration. To determine exhaust system effectiveness.

44 Tracer Gas Testing Methods
Tracer gas characteristics. Tracer gas introduction methods: Injection Constant Flow Duct injection Hood Testing Concentration measurement methods GC Infrared

45 Tracer Gas Testing Methods (Cont)
Tracer gas introduction: Air Change Studies Contamination Studies Hood Studies

46 Results What do results indicate? Limitations!
Comparisons with carbon dioxide methods for ventilation.

47

48 Why conduct bioaerosol Sampling?
Should only be done by experienced personnel and under limited conditions. To attempt to document the presence of a bioaerosol. To attempt to determine the type or species of a bioaerosol. To attempt to determine the cause of specific diagnosed diseases. To attempt to determine the effectiveness of a mitigation program.

49 Why not to conduct bioaerosol sampling.
To determine the presence or absence of a bioaerosol. To determine if an area is safe. To determine the cause of frequent colds, flu, rashes, etc.. To show that mold from the carpet, etc. is entering the air.

50 Where to conduct bioaerosol sampling.
Choosing sampling areas. Choosing control areas. Choosing outside control areas. How many samples to collect?

51 Types of bioaerosol sampling.
Bulk Sampling Viable Sampling Non-viable sampling Dust sampling By-product sampling

52

53

54

55 Particulate Sampling Methodology Results - What do they mean????
Mass collection Particle counters Condensation nuclei counters Results - What do they mean???? Mass Mass/particle size Particle numbers Ratios

56

57

58

59 Sampling complications
Interpretation of results is difficult. Generally low probability of identifying a problem. High cost Grab samples may give non-typical results. Source identification may not be possible Source reduction will still need to be done.

60 Remediation Increase outside air Decrease outside air Control sources
Local exhaust ventilation Elimination Control devices Contain construction or remodeling Isolate manufacturing areas

61

62

63 Factors confounding IAQ investigations
Ergonomic problems Smoking policies Comfort Complaints

64 Comfort Factors Complaint Low School High School Cold 32% 73% Hot 21%
50% Stuffy 7% 52% Moldy 14% 10% Dusty 11% 23% Noisy 0% 19% Dry 11% 25% Crowded 0% 17%