Galaxy 7000 characteristics
Mise à jour Février – Version AB -
2
Market, Channels, Price positionning, ...
Galaxy 5000 at a glance, Market, Channels, Price positionning, ...
3
G7K planning Emea-Lam Expert sales training Sales force training Emea
02/08 3/08 4/08 5/2008 6/2008 7/2008 8/2008 9/2008 3/2009 4/2009 Expert sales training Sales force training Emea Financial tools dispatched Opening of quotes : unitary and // modular Opening of order intake : unitary and // modular Opening of order intake : // with CSS First deliveries Emea/Lam : unitary and // modular First deliveries Emea/Lam : // with CSS In April 2009 are also included : Modular up till 8 Eco-mode Frequency converter
4
Technological design Mastered quality
5
Techological design : Brand new digital electronics
Integrated electronics, fewer components Topology derivated from Galaxy 5000 Fixed frequency 5 kHz, 4kHz Transformerless topology Output sizing : PF = 0,9 Air cooling with heat pipes All fan redundancy (at 25°c) and fault detection
6
Technological design : topology
7
Technological design: What is where ?
IGBT Rectifier Charger IGBT Inverter Control command boards DC Caps Power supplies boards Input and output static switches Input filters
8
Techological design: Why a transformerless topology ?
footprint Efficiency Costs Best solution to maximise the triptic : Need of 3% thdi Dc Bus at 800 v no need of output transformer. Save cost Save footprint Experience with Comet, Galaxy 3000, Galaxy 5000 Up to date topology Is it the only topology without transformer ?
9
Techological design: Transformer less issue
Galaxy 7000 G6K The truth about G6K output transformer No use : DC voltage is 800 v Voltage elevator 450 v 230 v 400 v Choke for smoothing Sinus Still exists Supressing H3 and H5 (triangle/zigzag) Higher IGBT ratings (cheaper and cheaper) Galvanic isolation between M1 input and output Have to add one transformer at the output
10
Techological design: Transformer less issue : at the input level
Galaxy 5000 PW Phenomenoms Transformer will lower the impact of over voltage. In input EMC filter: capacitor Phase earth + common mode choke lower the impact of over voltage Low frequency disturbances : Lightning : over voltage High frequency disturbances : « arcing » The inverter transformer will play no role and will transmit all disturbances EMC filter includes device for better protection
11
Techological design: Transformer less issue : at the UPS level
Galaxy 5000 Phenomenoms PW DC voltage at the output of the UPS caused by a problem of electronic regulation Electronic regulates to have no DC voltage. If electronic trouble, inverter transformer is saturated, the inverter is overloaded and transfer to by-pass Electronic regulates to have no DC voltage. If electronic trouble, control loop orders a transfer to by-pass DC current at the output of the UPS (power supply with only one diode) Transformer can suppy up till 5 % G5K can supply up till 10% of DC Current UPS inverter fault between phase or on DC Bus Only electronic regulation can guaranty the non transmission to the load Only electronic regulation can guaranty the non transmission to the load
12
Phenomenoms and beliefs
Techological design: Transformer less issue : at the output level Galaxy 5000 Phenomenoms and beliefs PW Short circuit capacities Short circuit is divided upon 2 legs at the primary of the transformer IGBT are bigger and able to provide excellent results Check table Transfo with Delta Y widings suppresses these harmonics : smaller inverter IGBT ratings Harmonics coming from the load, mainly H3 Higher IGBT ratings Transformer can be used to adapt the output voltage Electronics can sets up precisely Electronics can set from -3 to +3% the output voltage
13
Galaxy 7000 Characteristics
Mechanical Electrical Communication Architectures
14
Mechanical characteristics:
UPS 250 – 300 – 400 kVA 500 kVA I P Empty battery cabinets & Auxiliary cabinets 400 712 1 012 1 412
15
Mechanical characteristics:
800 kVA 1 200 kVA 2 000 kVA Centralised Static switches 1 012 1 412 2 424 I P 800 kVA 1 200 – kVA External maintenance by-pass 1 012 1 412
16
Mechanical characteristics: centralised static switch
1 200 kVA kVA 800 kVA 1 012 mm 1 412 mm
17
Mechanical characteristics: Easy to install and connect
Back to the wall : footprint savings Connecting switches in the same place than all the other 3 phases UPS Long solid terminal blocks: easy connection > 1000 mm Ready for TNC, TNS, TT, IT : same product, just connect differently the neutral. 490 mm : large distance to bend cables
18
Galaxy 7000 Characteristics
Mechanical Electrical Communication Architectures
19
Electrical performances: Input AC Normal
3 phases 250v / 470v 45 to 65 Hz Phase rotation detection Zone Back-feed 250 V 380 V 470 V Voltage AC Normal 70% 100% Nominal power Advantages No need of neutral at the input : no need of extra transformer Safety of connection shortage up till 3 ms without going to battery thanks to capacitors sizing
20
Electrical performances : IGBT rectifier
THDI < 5 % (with Thdv between 3 to 4%) Power factor > 0,99 Thdi (%) Advantages No disturbance of upstream electrical network Lower rating for cables breakers Fully compliant with genset 5% 6% % % Load level 25% 50% 75% 100%
21
Electrical performances :IGBT rectifier
Transfer from battery to Mains Current Time When running on Genset : Customisable maximum current customisable max bat. recharging current * Soft start (customisable time for ramp-up) * Sequential re-start Advantages Load step I battery chopper Current Time No Genset overloads whatever the sequence
22
Electrical performances : Charger
Floating Automatic test, manual test, Autonometer Recharging voltage according to temperature Independant electronic for Monitoring and regulation (NF C58-311) Input on relay card to stop the charger if battery room ventilation fault (NFC15-100) Management of 2 CB to control the charger DC Ripple voltage <1% Advantages Availability Easy to manage Increase battery life expectancy
23
Electrical performances: batteries
Sealed, vented lead-acid, Ni-cad From 44 to 48 blocs Floating voltage : from 600 to 654 v Circuit breaker protection to avoid deep discharge Advantages Re-charging time Boosted re-charging time Autonomy Ex. for 0,9 load Cos phi Flexibility N° of blocks Back-up times : up till 8 hours Availability Fast recharging
24
Electrical performances : Power according to temperature
Nominal load level % Improvement due to digital electronic Automatic adjustment More power, more overloads 538 kVA 430 kVA 323 kVA 269 kVA 525 kVA 420 kVA 315 kVA 263 kVA 100% , ,5 513 kVA 410 kVA 308 kVA 256 kVA 500 kVA 400 kVA 300 kVA 250 kVA T°c 20° 25°c 30°c 35°c
25
Electrical performances: output
v set-up at +-3% 50 ou 60 Hz +/-0,001Hz (auto regulation) Regulation : static : +/-1% on load impact : +/-2% (100ms) THDU< 2% (linear loads) THDU < 3% (non linear loads) Constant active power up till 0,9 leading PF , at 25°c. Advantages Quality of energy flexibility all type of loads set the precise voltage for long lengths of cables
26
Electrical performances : output : overloads
Thermal overload 150% for 1minute 125% for 10 minutes Operating at 35° permanently 1.5 In / 30sec 1.25 In / 10min
27
Electrical performances: output: short circuit capacities
Valid for 150 ms Check what breaker it can trip Advantages Helps discrimination Energy availability
28
Electrical performances: High efficiency (120 kVA)
94,5 94,3 94 94 94,2 93,7 93,6 Advantages Contributes to lower the TCO Allows to reduce sizing of air conditioning or ventilation of the UPS room 92,2 Load level 25% % % %
29
Galaxy 7000 Characteristics
Mechanical Electrical Communication Architectures
30
Local Communication: comfort & safety for the right decisions
3 levels of information Main menu button Help button General, by Led: Detail by the large display Mimic diagram for operational status: High resolution : 1/4 VGA (320x240) Intuitive menus 2500 events time stamping Step by step help for manipulations On/Off button operational even if comunication board is faulty.
31
Local Communication: Qualitative information for good management
Choose the welcoming screen Alarm when going over a customisable load level Manage the statistics : Average load level Number of overloads Number of switch to batteries Time spent on batteries Number of switch to by-pass Time spent on by-pass Manage a parallel configuration Total output measures Measures of any UPS in the configuration from any UPS Specific alarms to connect with bloc by bloc battery monitoring Individual Life cycle monitoring for DC and AC capacitors, fans, batteries Update with statistics menus in the user manual
32
Remote communication: Hot plug hardware
Should be replace at the end of 2009 by common Platform exAPC &MGE Remote communication: Hot plug hardware Industrial Network Mangement card: (option) ETHERNET 10/100BT + JBUS/RS485/RS232 Network Mangement card (option): ETHERNET 10/100BT + BUS/RS485/RS232 + Modem Supervise through web browser Interface with SNMP supervision Instructions for shutdown Notify alarms through Interface with Environement sensor for T° and Humidity monitoring Feed a BMS Supervise through web browser Interface with SNMP supervision Instructions for shutdown Notify alarms through Interface with Environement sensor OR feed a BMS Modem for remote Telservice 66069 :standard Alarm relay card
33
Remote communication: Softwares
34
Remote communication: EPM Software
EPM v.1: EPM v.2: all the EPM v.1 features and more: 3-Phase systems details embedded in EPM + log of 3-ph. data Support of « UPS multi-modules configur. and high availability UPS architectures » with « power flow views »: - hot-standby redundancy - modular parallel - parallel with centralised bypass - parallel with STS … etc. Additional views and graphical tools: - automatic map view - building view… Available Q1’06
35
Communication performances Remote : UPS general power off
Shuts UPS down shuts mains 2 static switch off (customisable on or off) Shuts PFC off shuts charger off opens baterry Circuit breaker Advantages Compliant with the UPS standard Compliant with sensitive application recommandation (hospitals)
36
Galaxy 7000 Characteristics
Mechanical Electrical Communication Architectures
37
Architectures and running modes Unitary versions
Hot Standby Unitary Unitary Eco Mode Frequency converter Not running in parallel mode Running in parallel mode
38
Architectures and running mode Parallel versions : up till 8 units
Power extension Modular parallelling
39
Architectures and running mode With Upsilon STS
40
Galaxy 7000 Catalogue
41
The options Available today, batch 1 Available in april 2006, batch 2
Backfeed mains1 and 2, M1 & M2 common Communication boards Isolation transformers External by-Pass cubicles : 800 kVA 1200 kVA 2000 kVA Battery circuit breaker kit : IP32 Top entry Available in april 2006, batch 2 Battery coupling pre-equiped battery blocs for battery monitoring
42
Standards and certifications
Normes Construction et sécurité CEI / CEI 60950 Performances et topologie CEI / EN CEM immunité CEI / EN niveau 4 (décharges électrostatiques : 15 KV air, 8 kV contact) CEI / EN niveau 3 (champs électro magnétiques rayonnés : 10 V/m) CEI / EN niveau 4 (transitoires rapides : 4 kV sur câbles secteur) CEI / EN niveau 4 (onde de choc forte énergie : 2 kV couplage entre lignes CEI / EN niveau 3 (immunité conduite : 10 Veff sur câbles secteur) CEI / EN niveau 4 (immunité rayonnée : 30 A/m) CEM émission CEI : C3 distribution contrôlée en standard / C2 classe A en option Harmoniques CEI / CEI Conception fabrication ISO / ISO 9001 Certification et marquage CE / LCIE