Presentation is loading. Please wait.

Presentation is loading. Please wait.

Hydronic Balancing „Cocon Q “ Pressure independent dynamic control valve.

Similar presentations


Presentation on theme: "Hydronic Balancing „Cocon Q “ Pressure independent dynamic control valve."— Presentation transcript:

1

2 Hydronic Balancing

3 „Cocon Q “ Pressure independent dynamic control valve

4 Hydronic Balancing „Cocon Q“ Valve for hydronic balancing and regulation of heating and cooling systems Main features: 1.Combination of automatic regulator and regulating valve 2.Constant, high valve authority 3.Adjustment / Control of the presetting with mounted actuator possible 4.Direct reading of presetting in l/h or m³/h 5.Good optical display of the presetting 6.Presetting is lead lockable 7.Pump setting optimization 8.Small dimensions, especially “Cocon QTZ” 9.Complete flow and size range 10.Multiple control options 11.For chilled ceiling, fan coil unit, air handling unit, convector, one-pipe-system, surface heating and cooling etc.

5 Hydronic Balancing Combination of automatic regulator and regulating valve Legend 1. Diaphragm unit 2. Control valve 3. Balancing valve 4. Handwheel 5. Diaphragm 6. Sleeve “p1” is the inlet and “p3” the outlet pressure of the valve. “p2” is the pressure actuating the diaphragm unit and maintaining the differential pressure “p2” – “p3” at a constant level.

6 Hydronic Balancing Combination of automatic regulator and regulating valve Differential pressure [bar] Flow rate [0 – 100%] 1. Limit the flow rate with the handwheel 2. Control the flow rate with the actuator 2-point control 3-point control Proportional control (0-10V) Flow rate [0-100%] Valve stroke [%] Linear valve characteristic when used with proportional actuators

7 Hydronic Balancing Valve Authority Valve Authority, a = P1 P1 + P2 Ideal is a valve authority of a = 1

8 Hydronic Balancing Constant and high valve authority “Cocon Q” „p2 – p3“ is kept constant, even where high differential pressure variations („p1“ – „p3“) occur during part load conditions Therefore, the valve authority of the regulating valve „Cocon Q“ amount to 100% (a = 1)

9 Hydronic Balancing Adjustment / Control of the presetting with mounted actuator possible

10 Hydronic Balancing Direct reading of presetting in l/h or m³/h „Cocon QTZ“ „Cocon QTR“ and „Cocon „QFC“

11 Hydronic Balancing Good optical display of the presetting of the “Cocon QTZ” in different installation positions

12 Hydronic Balancing Presetting is lead lockable

13 Hydronic Balancing 1.Check the min. differential pressure in the manual, depending on the presetting Pump setting optimization e.g. for the Cocon QTZ 2.Check the differential pressure of the “Cocon Q” with the “OV-DMC2” 3.Adjust the pump setting. Thus the last “Cocon QTZ” has a bit more (e.g. 5%) than the min. differential pressure. Save Energy due to optimum setting!

14 Hydronic Balancing Small dimensions, especially “Cocon QTZ” Less space required to install the „Cocon QTZ“ with actuator

15 Hydronic Balancing Flow and size range NameDIMThreadMotor/Act.Flow range “Cocon QTZ” DN10ThreadOptional30-210 l/h DN15ThreadOptional30-210 l/h DN15ThreadOptional90-450 l/h DN15ThreadOptional150-1.050 l/h DN20 LFThreadOptional150-1.050 l/h DN20 HFThreadOptional180-1.300 l/h DN25ThreadOptional300-2.000 l/h DN32ThreadOptional600-3.600 l/h “Cocon QTR” DN40ThreadOptional1.500-7.500 l/h DN50ThreadOptional2.500-10.000 l/h Q = Flow T = Thread Z = dezincification resistant brass Q = Flow T = Thread R = Bronze

16 Hydronic Balancing Flow and size range NameDIMThreadMotor/Act.Flow range „Cocon QFC“ DN40FlangeOptional1,5 – 7,5 m³/h DN50FlangeOptional2,0 – 8,0 m³/h DN65FlangeOptional5,0 – 22,0 m³/h DN80FlangeOptional7,5 – 30,0 m³/h DN100FlangeOptional12,5 – 50,0 m³/h DN125FlangeOptional27,0 – 90,0 m³/h DN150FlangeOptional36,0 – 150,0 m³/h Q = Flow F = Flange C = Cast iron

17 Hydronic Balancing “Cocon QTZ” Control options ActuatorCurrentControl 2-Point3-PointProportional Electro- thermal 24 V1012816/26 1012951 (0-10V) 230 V1012815/25 Electro- motive 24 V 10127011012700 (0-10V) 230 V10127101012703 EIB 1156065/66 LON 1157065 ActuatorCurrentControl 2-Point3-PointProportional Electro- thermal 24 V1012816/26 1012951 (0-10V) 230 V1012815/25 Electro- motive 24 V 10127011012700 (0-10V) 230 V10127101012703 EIB 1156065/66 LON 1157065 ActuatorCurrentControl 2-Point3-PointProportional Electro- thermal 24 V1012816/26 1012951 (0-10V) 230 V1012815/25 Electro- motive 24 V 10127011012700 (0-10V) 230 V10127101012703 EIB 1156065/66 LON 1157065

18 Hydronic Balancing electromotive actuators for “Cocon QTR” (DN40+50) 24V supply voltage 0-10V control voltage or 2-point or 3-point control 8 mm piston stroke characteristic lines: linear, equal percentage or quadratic adjustable installation position: vertical upright up to horizontal, not overhead Cocon QTR Item-No. 115 80 10

19 Hydronic Balancing electromotive actuators for “Cocon QFC/QTR” (DN40-150) –24V supply voltage –0-10V or 4-20 mA control voltage or 2-point or 3-point control –up to 40 mm piston stroke –characteristic lines: linear, equal percentage or quadratic adjustable –installation position: vertical upright up to horizontal, not overhead Cocon QTR / QFC Electromotive actuator Squeeze connection 24 V115 80 30 24 V, with spring return115 80 31

20 Hydronic Balancing Installation examples

21 Hydronic Balancing for better energy efficiency …


Download ppt "Hydronic Balancing „Cocon Q “ Pressure independent dynamic control valve."

Similar presentations


Ads by Google