CGVision OPC-interface for BMS A.Klepper – 01/04/11 Rev.B 6.2.

Similar presentations


Presentation on theme: "CGVision OPC-interface for BMS A.Klepper – 01/04/11 Rev.B 6.2."— Presentation transcript:

1 CGVision OPC-interface for BMS A.Klepper – 01/04/11 Rev.B 6.2

2 A.Klepper – 01/04/11 Rev.B 2 LAN-connection between PC with CGVision and PC with BMS Software LAN (RJ45) Ethernet (LAN) with TCP/IP USB Building Managment System (BMS) (e.g. TAC – Vista) PC Workstation with CGVision LAN (RJ45) IP-Interface Client 1 ZB-S CG-S Bus / FTT10A ZB-S ZB-S Systems BMS as OPC-Client IP-Interface Client 2 ZB-S CG-S Bus / FTT10A ZB-S ZB-S Systems incl. OPC-Server CG-S/IP-Interface

3 A.Klepper – 01/04/11 Rev.B 3 Ethernet LAN IP-Interface Client 1 ZB-S CG-S Bus / FTT10A ZB-S BMS as OPC-Client IP-Interface Client 2 ZB-S CG-S Bus / FTT10A ZB-S Incl. OPC-Server Explanation: BMS software has access, directly via LAN, to the BMS variable of the OPC-Server: nviStatusBMS SNVT_state_64

4 A.Klepper – 01/04/11 Rev.B 4 Possible messages of each device: nviStatusBMS SNVT_state_64 1.OperationBit 0 2.Failure priority 1Bit 1 3.Failure priority 2Bit 2 4.Communication failure CG-SBit 7 5.Manual reset necessaryBit 8 6.Battery operationBit 9 7.Durationtest activeBit 10 8.Device is blockedBit 11 9.Battery failureBit 12 10.Circuit failureBit 13 11.Mains failureBit 14 12.Sum failureBit 15 13.Communication failure internalBit 16 14.Deep disharge protectionBit 17 15.Interruption battery circuitBit 18 16. Charging failureBit 19 17. ISO failureBit 20 18. Min. operation time not reachedBit 21 19. Emergency light failureBit 22 20. Functiontest activeBit 23 21. Battery overvoltageBit 24 22. Battery sum failureBit 25 23. Failure charging unit Bit 26 24. Failure boosterBit 27 25. ISO failure +Bit 30 26. ISO failure -Bit 31 27. SMC (smart media card) failureBit 32 28. Mains failure deviceBit 33 29. Mains failure S3/S4Bit 34 30. Mains failure LON RS485Bit 35 31. Failure config. DLS/TLSBit 36 32. Device blocked via S1/S2Bit 37 33. Device blocked via menuBit 38 34. Device blocked via BMS (LON)Bit 39 35. Delay on mains returnBit 40

5 A.Klepper – 01/04/11 Rev.B 5 Example for BMS visualisation : BIT: 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0....0 0 0 0 No.: 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40........61 62 63 64 BMS visualisation nviStatusBMS SNVT_state_64 Example : OperationBit 0 Emergency light failureBit 22 Luminiare failure Device 1 in operation

6 A.Klepper – 01/04/11 Rev.B 6 Detailed information: Described in the interface description of OPC interface for BMS


Download ppt "CGVision OPC-interface for BMS A.Klepper – 01/04/11 Rev.B 6.2."