1111Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS17-8-2015 Challenges for Reliable Offshore Transformers Dr. Jan Declercq, Raymond Van Schevensteen Pauwels International N.V. Belgium
2
2222Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS27-8-2015 Transformers as critical components Wind turbines are electricity generator units; therefore all components are critical: Mechanical: blades, gearbox, tower,… Electrical: generator, converter, transformer, circuit breaker, control unit,… Medium Voltage Transformer has to be designed as generator step-up transformer and fully integrated in wind turbine performance and specifications … and now Multi Megawatt Turbines for offshore installation
3
3333Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS37-8-2015 Operating conditions are different Normal transformer in normal environment 1000 kVA in apartment
4
4444Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS47-8-2015 Operating conditions are different Generator step-up transformer in WTG
5
5555Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS57-8-2015 Operating conditions are different Generator step-up transformer in wind turbine Multi Mega Watt offshore
6
6666Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS67-8-2015 So MMW WTG needs GSU Transformer EHV transmission Generation 100 MW >220 kV Transmission Sub-transmission 110 – 70 kV Embedded generation Distribution 0.5-4 MW 30 kV Overloading, power quality, economics, environment, maintenance, reliability
7
7777Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS77-8-2015 Types of medium voltage transformers Mineral liquid-filled transformers Cast resin transformers SLIM ® and Bio-SLIM ® technology Fire & bio-degradable liquid and Nomex ® insulation Same operating range of voltages and power What about other specifications?
8
8888Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS87-8-2015 Functional Specifications of transformers Power Liquid-filled up to 10 MVA and high voltages 36 kV and above No load losses As low as possible, always energized Liquid filled 50 % less losses compared to dry type Ex. 2 kW * 8760 h/y * 0.05 EUR/kWh per turbine per year Load losses at working temperature customized to needs Medium voltage 12 kV, 24 kV, 36 kV insulation level up to BIL 200 kV Low Voltage 400 V, 660 V, 690 V, 1000 V, 3000 V, 6000 V Impedance 6 % up to 14 % for weak grids Dimensions Mass for nacelle, reduced dimensions, “fits the door“ These specifications are not sufficient to guarantee performance and reliability
9
9999Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS97-8-2015 Operating conditions Thermal Stresses Average 60% loading but … Full loading for several days Short term peak overloads Sharp load fluctuationsHarmonics Higher air temperature in turbine 1,000 1,500 2,000 02004006008001000120014001600
10
10 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS107-8-2015 Operating conditions Thermal Stresses Load P Current I Losses RI 2 Temperature Lifetime T ins 98 C Thermal stresses give mechanical stresses and accelerated ageing So verify insulation materials, overload tests, higher MVA, cooling inside
11
11 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS117-8-2015 Operating conditions Electrical Stresses Different electrical environment Switching surges from Circuit Breakers Overfluxing from overvoltages Lightning strikes Frequency variations Voltage dips Causing higher electrical stresses on electrical insulation system Increased risk for initiating Partial Discharges So verify electrical performance, specify extra testing Example PD tests, chopped wave
12
12 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS127-8-2015 SWITCHING PRE-STRIKE OR RE-STRIKE SOURCE VICTIM RESONANCES IN TRANSFORMER WINDINGS VOLTAGE TRANSIENT THROUGH CABLE COUPLING Switching surges It is an EMC problem: breaker and transformer can be less compatible in the specific network arrangement
13
13 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS137-8-2015 Operating conditions Mechanical Stresses Mechanical environment Compact design Optimized dimensions for inside installation Optimized connections In case of nacelle design, vibration tests including connection of cables Verify mechanical design and test accordingly Verify sensitivity of mechanical stresses on electrical insulation system
14
14 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS147-8-2015 Operating conditions Chemical Stresses Environment Cooling air Humidity Dust, salt Aggressive environment People Verify protection of electrical system Specify higher IP class, C5 offshore painting, air filters, extra housing Maintenance interventions for transformer or peripherial equipment
15
15 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS157-8-2015 Specify good protection and materials Cast resin F1 or class K3 liquid Cast resin transformer versus silicone liquid filled transformer tested according Cenelec Operating conditions Safety
16
16 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS167-8-2015 Operating conditions Safety Tests performed at Ineris France, February and April 2004
17
17 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS177-8-2015 New challenges Wind offshore: WTG go to higher MVA ratings from 2 MW to 6 MW Connection voltages mostly 33 kV Extreme reliability (MTBF > 500 years) Reduced maintenance So optimize transformer technology, design, manufacturing and testing to meet the wind turbine demands
18
18 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS187-8-2015 New markets Wind offshore: >3 MVA transformers for offshore and nacelle UK, 7 GW projects Belgium, NL 300 MW Spain, 2000 MW Denmark, 400 MW Germany, 68 GW
19
19 Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS197-8-2015 Conclusions for offshore transformers Different transformer technologies are available for multi- megawatt turbines Dimensions, losses, reliability (MTBF), protection, electrical environment are important because the operating conditions in a turbine are severe! Fire behavior of dry type and high temperature liquid filled transformers are comparable Good protection and prevention is always needed, independent of transformer technology Verify compatibility for aggressive offshore environment Improve specifications for WTG transformers Improve testing specifications for WTG transformers IEC TC14 Transformer Committee will write standards for wind turbine use (approved 2005, start 2006)